Boiler interface module via BACnet gateway · BACnet points list

Cleaver-Brooks HSC Boiler Interface Module (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The ProtoNode maps the HSC boiler interface module to BACnet: boiler status, alarm word, hours, cycles, inlet and outlet temperature, firing rate and the module's inputs and outputs. Writable AVs set DHW setpoints and enables, a remote setpoint and enable, and a heartbeat.

This page lists 40 BACnet objects for the Cleaver-Brooks HSC Boiler Interface Module (ProtoNode) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
HSC Boiler Interface Module (ProtoNode)
Equipment
Boiler interface module via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
40 (9 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
Boiler Interface Module, HSC Boiler Interface, BIM, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 40 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)

Integration in brief

Enable the boiler (AV 8), write the remote setpoint (AV 5) and keep the heartbeat (AV 9) updated. Read boiler status, outlet temperature, firing rate and the alarm output.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 8Remote EnableRemote enableWrite
AV 5Remote Setpoint WriteRemote setpointWrite
AV 9Heartbeat Write TagHeartbeat written by the BMSWrite
AI 1Boiler StatusBoiler statusRead
BI 6Boiler Run OutputBoiler run outputRead
AI 10Outlet TempOutlet temperatureRead
AI 11Firing RateFiring rateRead
BI 4Alarm OutputAlarm outputRead
AI 2Alarm WordAlarm wordRead

Heartbeat & communication loss

AV 9 Heartbeat Write Tag is written by the BMS; the guide does not state the timeout.

Network setup

Cleaver-Brooks HSC Boiler Interface Module (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

40 of 40 shown
Type
Binary
Access
Show
Cleaver-Brooks HSC Boiler Interface Module (ProtoNode) BACnet Points List
DescriptionStates
AImin1Boiler StatusModbus 30021Read
AImin2Alarm WordModbus 30022Read
AI3Hours Word 1Modbus 30023Read
AI4Hours Word 2Modbus 30024Read
AI5Cycles Word 1Modbus 30025Read
AI6Cycles Word 2Modbus 30026Read
AI7BitsModbus 30027Read
AI8Inlet TempModbus 30028Read
AI9Fire DelayModbus 30029Read
AImin10Outlet TempModbus 30030Read
AImin11Firing RateModbus 30031Read
AI12Digital InputsModbus 30032Read
AI13Digital OutputsModbus 30033Read
BI1LFH ActiveRead
BI2Min Outlet Temp MetRead
BI3SpareRead
BImin4Alarm OutputRead
BI5SpareRead
BImin6Boiler Run OutputRead
BI7Pump Run OutputRead
BI8Damper OutputRead
BI9Valve OutputRead
BI10Alarm InputRead
BI11Boiler Ready InputRead
BI12Pump Prove InputRead
BI13Boiler Prove InputRead
BI14Damper Prove InputRead
BI15SpareRead
BI16SpareRead
AV1DHW1 SetpointModbus 40301-02Write
AV2DHW2 SetpointModbus 40303-04Write
AV3AQ304Modbus 40305-06Write
AV4AQ306Modbus 40307-08Write
AVmin5Remote Setpoint WriteModbus 40309-10Write
AV6DHW1 EnableModbus 40310Write
AV7DHW2 EnableModbus 40311Write
AVmin8Remote EnableModbus 40312Write
AVmin9Heartbeat Write TagModbus 40316Write
AI14HoursModbus 30034-35Read
AI15CyclesModbus 30036-37Read
Object ID lookup: Cleaver-Brooks HSC Boiler Interface Module point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HSC Boiler Interface Module (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)

How many BACnet points does the Cleaver-Brooks HSC Boiler Interface Module (ProtoNode) have?

This list has 40 BACnet objects: 15 analog inputs, 9 analog values, 16 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks HSC Boiler Interface Module (ProtoNode) BACnet points are writable?

9 of the 40 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Cleaver-Brooks HSC Boiler Interface Module (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)?

Start with AV 8 Remote Enable (Remote enable); AV 5 Remote Setpoint Write (Remote setpoint); AV 9 Heartbeat Write Tag (Heartbeat written by the BMS); AI 1 Boiler Status (Boiler status); BI 6 Boiler Run Output (Boiler run output); AI 10 Outlet Temp (Outlet temperature); AI 11 Firing Rate (Firing rate); BI 4 Alarm Output (Alarm output); AI 2 Alarm Word (Alarm word).

Does the Cleaver-Brooks HSC Boiler Interface Module (ProtoNode) need a BACnet heartbeat or have a communication timeout?

AV 9 Heartbeat Write Tag is written by the BMS; the guide does not state the timeout.

How do I check these points on the real HSC Boiler Interface Module (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.