Steam or hot water boiler control via BACnet gateway · BACnet points list

Cleaver-Brooks Hawk ICS boiler control (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A read-only ProtoNode profile for the Hawk ICS boiler control: alarm and status bits (limits, actuators, flame safeguard, O2, sensor failures), firing-rate modes, flame strength, firing rate, O2, setpoints, steam pressure or water temperature, stack and economizer temperatures, burner status lines, run time and cycles.

This page lists 140 BACnet objects for the Cleaver-Brooks Hawk ICS boiler control (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
Hawk ICS boiler control (ProtoNode)
Equipment
Steam or hot water boiler control via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
140 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
Hawk ICS, CB ICS, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 140 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks Hawk ICS boiler control (ProtoNode)

Integration in brief

Read-only. Map load demand, steam pressure or water temperature, setpoint, firing rate and the alarm output.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 57Boiler Load DemandBoiler load demandRead
BI 47Remote enable inputRemote enable inputRead
AI 9Steam Pressure or HW TempSteam pressure or hot water temperatureRead
AI 7Set Point Steam Pressure/Water TempActive setpointRead
AI 5Firing RateFiring rateRead
BI 42Main Fuel Valve OpenMain fuel valve openRead
BI 55Alarm OutputAlarm outputRead
AI 28Brnr Control Status Line 1 HoneywellBurner control status line 1 (Honeywell)Read

Network setup

Watch out for

Cleaver-Brooks Hawk ICS boiler control (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

140 of 140 shown
Type
AnalogBinary
Show
Cleaver-Brooks Hawk ICS boiler control (ProtoNode) BACnet Points List
DescriptionStates
BI1Drive FaultRead
BI2Modbus Com ErrorRead
BI3Low WaterRead
BI4BC AlarmRead
BI5Boiler Limits OpenRead
BI6High Stack Temp AlarmRead
BI7High Stack Temp SDRead
BI8External InterlockRead
BI9I/O module faultRead
BI10Steam Sensor FailRead
BI11Air Drive out of Position AlarmRead
BI12Gas Drive out of Position AlarmRead
BI13F/A Ratio Controller FaultRead
BI14No Fuel SelectedRead
BI15Low Clogix BatteryRead
BI16Non Recycle Limit Relay FailRead
BI17Recyle Limit Relay FailRead
BI18Remote Modulation Signal FailRead
BI19Header Sensor FailRead
BI20TC Channel FailRead
BI21Low O2 AlarmRead
BI22High Limit AlarmRead
BI23ALWCORead
BI24Low Gas Pressure/Low Oil TempRead
BI25High Gas Pressure/High Oil TempRead
BI26Low Oil PressureRead
BI27High Oil PressureRead
BI28Oil Drawer Switch Not MadeRead
BI29Low Atomizing Air PressureRead
BI30Low Combustion Air PressureRead
BI31AUX Alarm 1Read
BI32AUX Alarm 2Read
BI33Blower OnRead
BI34Purge InputRead
BI35Release To modulate InputRead
BI36Low Fire SwitchRead
BI37High Fire SwitchRead
BI38Ready to start/Limits ClosedRead
BI39External Start InterlockRead
BI40ALFCORead
BI41PilotRead
BImin42Main Fuel Valve OpenRead
BI43Fuel 1 SelectedRead
BI44Fuel 2 SelectedRead
BI45FSG AlarmRead
BI46LWCO ShutdownRead
BImin47Remote enable inputRead
BI48Burner SwitchRead
BI49Recycle Limit RelayRead
BI50External Device StartRead
BI51Non Recycle Limit RelayRead
BI52Drive to Low Fire (FARC)Read
BI53Start Slave Blr (2 Blr LL)Read
BI54Load Demand OutputRead
BImin55Alarm OutputRead
BI56Boiler Ready (LL)Read
BImin57Boiler Load DemandRead
BI58Firing Rate Remote/LlagRead
BI59Firing Rate ManualRead
BI60Firing Rate AutoRead
BI61Hot Stand ByRead
BI62Warm UpRead
BI63Fuel 3 SelectedRead
BI64Aux Alarm 3Read
BI65Steam or Hot WaterRead
BI66Level Master PresentRead
BI67Variable Speed Drive PresentRead
BI68Economizer PresentRead
BI69Combustion Air Temp PresentRead
BI70Oil Temp Sensor PresentRead
BI71O2 Analyzer PresentRead
BI72Feedwater or Return Temp PresentRead
BI73Outdoor Reset SelectedRead
BI74Parallel Positioning SelectedRead
BI75Two boiler lead lag master selectRead
BI76Two boiler lead lag slave selectRead
BI77Master panel selectRead
BI78Hot stand by selectRead
BI79Dual setpoint selectRead
BI80Gas Flow SelectRead
BI81Oil Flow SelectRead
BI82Steam Flow SelectRead
BI83Water Flow SelectRead
BI84Honeywell or FireyeRead
BI85High Water AlarmRead
BI86Oil Drive out of Position AlarmRead
BI87FGR Drive out of Position AlarmRead
BI88Air Actuator FB Alarm LowRead
BI89Air Actuator FB Alarm HighRead
BI90Fuel1 Actuator FB Alarm LowRead
BI91Fuel1 Actuator FB Alarm HighRead
BI92Fuel2 Actuator FB Alarm LowRead
BI93Fuel2 Actuator FB Alarm HighRead
BI94FGR Actuator FB Alarm LowRead
BI95FGR Actuator FB Alarm HighRead
BI96VSD Deviation AlarmRead
AI1Flame Strength HoneywellModbus 30001Read
AI2Combustion Air Fan SpeedModbus 30003Read
AI3Blower Motor KwModbus 30005Read
AI4Boiler EfficiencyModbus 30007Read
AImin5Firing RateModbus 30009Read
AI6O2 LevelModbus 30011Read
AImin7Set Point Steam Pressure/Water TempModbus 30013Read
AI8Water LevelModbus 30015Read
AImin9Steam Pressure or HW TempModbus 30017Read
AI10Combustion Air PressureModbus 30019Read
AI11Stack Temp Before EconModbus 30021Read
AI12Combustion Air TempModbus 30023Read
AI13Water Temp Shell/Outdoor TempModbus 30025Read
AI14Feedwater Temp/Econ Water Out TempModbus 30027Read
AI15Stack Temp After Econ/Return HWModbus 30029Read
AI16Economizer Water In TempModbus 30031Read
AI17Analog Input User Defined #1 InputModbus 30033Read
AI18Analog Input User Defined #2 InputModbus 30035Read
AI19Analog Input User Defined #3 InputModbus 30037Read
AI20Analog Input User Defined #4 InputModbus 30039Read
AI21Safety Valve Setting or Max Water TempModbus 30041Read
AI22Header Pressure or temp 2 Boiler LLModbus 30043Read
AI23Set Point 2 Boiler LLModbus 30045Read
AI24Boiler Off PointModbus 30047Read
AI25Boiler On PointModbus 30049Read
AI26AR[25] FutureModbus 30051Read
AI27AR[26] FutureModbus 30053Read
AImin28Brnr Control Status Line 1 HoneywellModbus 30055Read
AI29Brnr Control Status Line 2 HoneywellModbus 30056Read
AI30Brnr Control Status Line 1 FireyeModbus 30057Read
AI31Brnr Control Status Line 2 FireyeModbus 30058Read
AI32Flame Signal FireyeModbus 30059Read
AI33Fuel 1 TypeModbus 30060Read
AI34Fuel 2 TypeModbus 30061Read
AI35Fuel 3 TypeModbus 30062Read
AI36Boiler IDModbus 30063Read
AI37Elapsed Time (First 16 Bits)Modbus 30064Read
AI38Elapsed Time (Second 16 Bits)Modbus 30065Read
AI39Number Of Cycles (First 16 Bits)Modbus 30066Read
AI40Number Of Cycles (Second 16 Bits)Modbus 30067Read
AI41AI[13] FutureModbus 30068Read
AI42AI[14] FutureModbus 30069Read
AI43Elapsed TimeModbus 30070Read
AI44Number Of CyclesModbus 30072Read
Object ID lookup: Cleaver-Brooks Hawk ICS boiler control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hawk ICS boiler control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks Hawk ICS boiler control (ProtoNode)

How many BACnet points does the Cleaver-Brooks Hawk ICS boiler control (ProtoNode) have?

This list has 140 BACnet objects: 44 analog inputs, 96 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks Hawk ICS boiler control (ProtoNode) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Cleaver-Brooks Hawk ICS boiler control (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks Hawk ICS boiler control (ProtoNode)?

Start with BI 57 Boiler Load Demand (Boiler load demand); BI 47 Remote enable input (Remote enable input); AI 9 Steam Pressure or HW Temp (Steam pressure or hot water temperature); AI 7 Set Point Steam Pressure/Water Temp (Active setpoint); AI 5 Firing Rate (Firing rate); BI 42 Main Fuel Valve Open (Main fuel valve open); BI 55 Alarm Output (Alarm output); AI 28 Brnr Control Status Line 1 Honeywell (Burner control status line 1 (Honeywell)).

How do I check these points on the real Hawk ICS boiler control (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.