Multi-boiler sequencer (hot water boiler plant) via BACnet gateway · BACnet points list

Cleaver-Brooks HSC Hydronic System Controller (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The ProtoNode maps the HSC boiler-plant controller to BACnet. Each condensing boiler (1-10) and non-condensing boiler (A-J) has a block of state, alarm word, hours, cycles, status bits, inlet and outlet temperature; the plant section adds header and return temperatures, active setpoints, reset-curve settings, lead/lag order, pump and damper module data and run counts. Four AVs let the BMS enable the system, send a setpoint and outdoor temperature, and write a heartbeat.

This page lists 318 BACnet objects for the Cleaver-Brooks HSC Hydronic System Controller (ProtoNode) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
HSC Hydronic System Controller (ProtoNode)
Equipment
Multi-boiler sequencer (hot water boiler plant) via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
318 (4 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
HSC, Hydronic System Controller, CB HSC, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 318 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)

Integration in brief

Enable the plant with AV 3 and write the setpoint with AV 1, keep AV 4 heartbeat updated, and optionally send outdoor air temperature on AV 2. Read system mode, header and return temperatures, boiler counts and the alarm words.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 3Remote Modbus System EnableRemote system enableWrite
AV 1Remote Modbus Setpoint ValueRemote setpointWrite
AV 4Modbus HeartbeatHeartbeat written by the BMSWrite
AI 312System ModeSystem modeRead
AI 253Main Supply Header TempMain supply header temperatureRead
AI 254System Return TempSystem return temperatureRead
AI 213Number of Cond Boilers RunningCondensing boilers runningRead
AI 215Number of Non-Cond Boilers RunningNon-condensing boilers runningRead
AI 208Alarm Word 1 ValueAlarm word 1Read

Enable & remote start

AV 3 Remote Modbus System Enable enables the plant; AV 1 Remote Modbus Setpoint Value sends the setpoint.

Heartbeat & communication loss

AV 4 Modbus Heartbeat is written by the BMS; the guide does not state the timeout.

Sensors & values from the BMS

AV 2 Remote Modbus Outdoor Air Temp takes an outdoor air temperature from the BMS.

Network setup

Cleaver-Brooks HSC Hydronic System Controller (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

318 of 318 shown
Type
Access
Show
Cleaver-Brooks HSC Hydronic System Controller (ProtoNode) BACnet Points List
DescriptionStates
AI1C Boiler 1 StateModbus 30021Read
AI2C Boiler 1 Alarm WordModbus 30022Read
AI3C Boiler 1 Hours Word 1Modbus 30023Read
AI4C Boiler 1 Hours Word 2Modbus 30024Read
AI5C Boiler 1 Cycles Word 1Modbus 30025Read
AI6C Boiler 1 Cycles Word 2Modbus 30026Read
AI7C Boiler 1 Status BitsModbus 30027Read
AI8C Boiler 1 Inlet TempModbus 30028Read
AI9C Boiler 1 Fire DelayModbus 30029Read
AI10C Boiler 1 Outlet TempModbus 30030Read
AI11C Boiler 2 StateModbus 30031Read
AI12C Boiler 2 Alarm WordModbus 30032Read
AI13C Boiler 2 Hours Word 1Modbus 30033Read
AI14C Boiler 2 Hours Word 2Modbus 30034Read
AI15C Boiler 2 Cycles Word 1Modbus 30035Read
AI16C Boiler 2 Cycles Word 2Modbus 30036Read
AI17C Boiler 2 Status BitsModbus 30037Read
AI18C Boiler 2 Inlet TempModbus 30038Read
AI19C Boiler 2 Fire DelayModbus 30039Read
AI20C Boiler 2 Outlet TempModbus 30040Read
AI21C Boiler 3 StateModbus 30041Read
AI22C Boiler 3 Alarm WordModbus 30042Read
AI23C Boiler 3 Hours Word 1Modbus 30043Read
AI24C Boiler 3 Hours Word 2Modbus 30044Read
AI25C Boiler 3 Cycles Word 1Modbus 30045Read
AI26C Boiler 3 Cycles Word 2Modbus 30046Read
AI27C Boiler 3 Status BitsModbus 30047Read
AI28C Boiler 3 Inlet TempModbus 30048Read
AI29C Boiler 3 Fire DelayModbus 30049Read
AI30C Boiler 3 Outlet TempModbus 30050Read
AI31C Boiler 4 StateModbus 30051Read
AI32C Boiler 4 Alarm WordModbus 30052Read
AI33C Boiler 4 Hours Word 1Modbus 30053Read
AI34C Boiler 4 Hours Word 2Modbus 30054Read
AI35C Boiler 4 Cycles Word 1Modbus 30055Read
AI36C Boiler 4 Cycles Word 2Modbus 30056Read
AI37C Boiler 4 Status BitsModbus 30057Read
AI38C Boiler 4 Inlet TempModbus 30058Read
AI39C Boiler 4 Fire DelayModbus 30059Read
AI40C Boiler 4 Outlet TempModbus 30060Read
AI41C Boiler 5 StateModbus 30061Read
AI42C Boiler 5 Alarm WordModbus 30062Read
AI43C Boiler 5 Hours Word 1Modbus 30063Read
AI44C Boiler 5 Hours Word 2Modbus 30064Read
AI45C Boiler 5 Cycles Word 1Modbus 30065Read
AI46C Boiler 5 Cycles Word 2Modbus 30066Read
AI47C Boiler 5 Status BitsModbus 30067Read
AI48C Boiler 5 Inlet TempModbus 30068Read
AI49C Boiler 5 Fire DelayModbus 30069Read
AI50C Boiler 5 Outlet TempModbus 30070Read
AI51C Boiler 6 StateModbus 30071Read
AI52C Boiler 6 Alarm WordModbus 30072Read
AI53C Boiler 6 Hours Word 1Modbus 30073Read
AI54C Boiler 6 Hours Word 2Modbus 30074Read
AI55C Boiler 6 Cycles Word 1Modbus 30075Read
AI56C Boiler 6 Cycles Word 2Modbus 30076Read
AI57C Boiler 6 Status BitsModbus 30077Read
AI58C Boiler 6 Inlet TempModbus 30078Read
AI59C Boiler 6 Fire DelayModbus 30079Read
AI60C Boiler 6 Outlet TempModbus 30080Read
AI61C Boiler 7 StateModbus 30081Read
AI62C Boiler 7 Alarm WordModbus 30082Read
AI63C Boiler 7 Hours Word 1Modbus 30083Read
AI64C Boiler 7 Hours Word 2Modbus 30084Read
AI65C Boiler 7 Cycles Word 1Modbus 30085Read
AI66C Boiler 7 Cycles Word 2Modbus 30086Read
AI67C Boiler 7 Status BitsModbus 30087Read
AI68C Boiler 7 Inlet TempModbus 30088Read
AI69C Boiler 7 Fire DelayModbus 30089Read
AI70C Boiler 7 Outlet TempModbus 30090Read
AI71C Boiler 8 StateModbus 30091Read
AI72C Boiler 8 Alarm WordModbus 30092Read
AI73C Boiler 8 Hours Word 1Modbus 30093Read
AI74C Boiler 8 Hours Word 2Modbus 30094Read
AI75C Boiler 8 Cycles Word 1Modbus 30095Read
AI76C Boiler 8 Cycles Word 2Modbus 30096Read
AI77C Boiler 8 Status BitsModbus 30097Read
AI78C Boiler 8 Inlet TempModbus 30098Read
AI79C Boiler 8 Fire DelayModbus 30099Read
AI80C Boiler 8 Outlet TempModbus 30100Read
AI81C Boiler 9 StateModbus 30101Read
AI82C Boiler 9 Alarm WordModbus 30102Read
AI83C Boiler 9 Hours Word 1Modbus 30103Read
AI84C Boiler 9 Hours Word 2Modbus 30104Read
AI85C Boiler 9 Cycles Word 1Modbus 30105Read
AI86C Boiler 9 Cycles Word 2Modbus 30106Read
AI87C Boiler 9 Status BitsModbus 30107Read
AI88C Boiler 9 Inlet TempModbus 30108Read
AI89C Boiler 9 Fire DelayModbus 30109Read
AI90C Boiler 9 Outlet TempModbus 30110Read
AI91C Boiler 10 StateModbus 30111Read
AI92C Boiler 10 Alarm WordModbus 30112Read
AI93C Boiler 10 Hours Word 1Modbus 30113Read
AI94C Boiler 10 Hours Word 2Modbus 30114Read
AI95C Boiler 10 Cycles Word 1Modbus 30115Read
AI96C Boiler 10 Cycles Word 2Modbus 30116Read
AI97C Boiler 10 Status BitsModbus 30117Read
AI98C Boiler 10 Inlet TempModbus 30118Read
AI99C Boiler 10 Fire DelayModbus 30119Read
AI100C Boiler 10 Outlet TempModbus 30120Read
AI101NC Boiler A StateModbus 30121Read
AI102NC Boiler A Alarm WordModbus 30122Read
AI103NC Boiler A Hours Word 1Modbus 30123Read
AI104NC Boiler A Hours Word 2Modbus 30124Read
AI105NC Boiler A Cycles Word 1Modbus 30125Read
AI106NC Boiler A Cycles Word 2Modbus 30126Read
AI107NC Boiler A Status BitsModbus 30127Read
AI108NC Boiler A Inlet TempModbus 30128Read
AI109NC Boiler A Fire DelayModbus 30129Read
AI110NC Boiler A Outlet TempModbus 30130Read
AI111NC Boiler B StateModbus 30131Read
AI112NC Boiler B Alarm WordModbus 30132Read
AI113NC Boiler B Hours Word 1Modbus 30133Read
AI114NC Boiler B Hours Word 2Modbus 30134Read
AI115NC Boiler B Cycles Word 1Modbus 30135Read
AI116NC Boiler B Cycles Word 2Modbus 30136Read
AI117NC Boiler B Status BitsModbus 30137Read
AI118NC Boiler B Inlet TempModbus 30138Read
AI119NC Boiler B Fire DelayModbus 30139Read
AI120NC Boiler B Outlet TempModbus 30140Read
AI121NC Boiler C StateModbus 30141Read
AI122NC Boiler C Alarm WordModbus 30142Read
AI123NC Boiler C Hours Word 1Modbus 30143Read
AI124NC Boiler C Hours Word 2Modbus 30144Read
AI125NC Boiler C Cycles Word 1Modbus 30145Read
AI126NC Boiler C Cycles Word 2Modbus 30146Read
AI127NC Boiler C Status BitsModbus 30147Read
AI128NC Boiler C Inlet TempModbus 30148Read
AI129NC Boiler C Fire DelayModbus 30149Read
AI130NC Boiler C Outlet TempModbus 30150Read
AI131NC Boiler D StateModbus 30151Read
AI132NC Boiler D Alarm WordModbus 30152Read
AI133NC Boiler D Hours Word 1Modbus 30153Read
AI134NC Boiler D Hours Word 2Modbus 30154Read
AI135NC Boiler D Cycles Word 1Modbus 30155Read
AI136NC Boiler D Cycles Word 2Modbus 30156Read
AI137NC Boiler D Status BitsModbus 30157Read
AI138NC Boiler D Inlet TempModbus 30158Read
AI139NC Boiler D Fire DelayModbus 30159Read
AI140NC Boiler D Outlet TempModbus 30160Read
AI141NC Boiler E StateModbus 30161Read
AI142NC Boiler E Alarm WordModbus 30162Read
AI143NC Boiler E Hours Word 1Modbus 30163Read
AI144NC Boiler E Hours Word 2Modbus 30164Read
AI145NC Boiler E Cycles Word 1Modbus 30165Read
AI146NC Boiler E Cycles Word 2Modbus 30166Read
AI147NC Boiler E Status BitsModbus 30167Read
AI148NC Boiler E Inlet TempModbus 30168Read
AI149NC Boiler E Fire DelayModbus 30169Read
AI150NC Boiler E Outlet TempModbus 30170Read
AI151NC Boiler F StateModbus 30171Read
AI152NC Boiler F Alarm WordModbus 30172Read
AI153NC Boiler F Hours Word 1Modbus 30173Read
AI154NC Boiler F Hours Word 2Modbus 30174Read
AI155NC Boiler F Cycles Word 1Modbus 30175Read
AI156NC Boiler F Cycles Word 2Modbus 30176Read
AI157NC Boiler F Status BitsModbus 30177Read
AI158NC Boiler F Inlet TempModbus 30178Read
AI159NC Boiler F Fire DelayModbus 30179Read
AI160NC Boiler F Outlet TempModbus 30180Read
AI161NC Boiler G StateModbus 30181Read
AI162NC Boiler G Alarm WordModbus 30182Read
AI163NC Boiler G Hours Word 1Modbus 30183Read
AI164NC Boiler G Hours Word 2Modbus 30184Read
AI165NC Boiler G Cycles Word 1Modbus 30185Read
AI166NC Boiler G Cycles Word 2Modbus 30186Read
AI167NC Boiler G Status BitsModbus 30187Read
AI168NC Boiler G Inlet TempModbus 30188Read
AI169NC Boiler G Fire DelayModbus 30189Read
AI170NC Boiler G Outlet TempModbus 30190Read
AI171NC Boiler H StateModbus 30191Read
AI172NC Boiler H Alarm WordModbus 30192Read
AI173NC Boiler H Hours Word 1Modbus 30193Read
AI174NC Boiler H Hours Word 2Modbus 30194Read
AI175NC Boiler H Cycles Word 1Modbus 30195Read
AI176NC Boiler H Cycles Word 2Modbus 30196Read
AI177NC Boiler H Status BitsModbus 30197Read
AI178NC Boiler H Inlet TempModbus 30198Read
AI179NC Boiler H Fire DelayModbus 30199Read
AI180NC Boiler H Outlet TempModbus 30200Read
AI181NC Boiler I StateModbus 30201Read
AI182NC Boiler I Alarm WordModbus 30202Read
AI183NC Boiler I Hours Word 1Modbus 30203Read
AI184NC Boiler I Hours Word 2Modbus 30204Read
AI185NC Boiler I Cycles Word 1Modbus 30205Read
AI186NC Boiler I Cycles Word 2Modbus 30206Read
AI187NC Boiler I Status BitsModbus 30207Read
AI188NC Boiler I Inlet TempModbus 30208Read
AI189NC Boiler I Fire DelayModbus 30209Read
AI190NC Boiler I Outlet TempModbus 30210Read
AI191NC Boiler J StateModbus 30211Read
AI192NC Boiler J Alarm WordModbus 30212Read
AI193NC Boiler J Hours Word 1Modbus 30213Read
AI194NC Boiler J Hours Word 2Modbus 30214Read
AI195NC Boiler J Cycles Word 1Modbus 30215Read
AI196NC Boiler J Cycles Word 2Modbus 30216Read
AI197NC Boiler J Status BitsModbus 30217Read
AI198NC Boiler J Inlet TempModbus 30218Read
AI199NC Boiler J Fire DelayModbus 30219Read
AI200NC Boiler J Outlet TempModbus 30220Read
AI201Rem System Pump Module Input WordModbus 30221Read
AI202Rem System Pump Module Output WordModbus 30222Read
AI203Number of Remote System PumpsModbus 30223Read
AI247Pump Module Analog In 1 Scaled ValueModbus 30224Read
AI248Pump Module Analog In 2 Scaled ValueModbus 30226Read
AI249System Pump Speed RequestedModbus 30228Read
AI250Pump PID Process VariableModbus 30230Read
AI251Pump PID SetpointModbus 30232Read
AI204Rem System Pump Lead Pump NumberModbus 30234Read
AI205Rem System Pump Lag1 Pump NumberModbus 30235Read
AI206Rem System Pump Lag2 Pump NumberModbus 30236Read
AI207Rem System Pump Lag3 Pump NumberModbus 30237Read
AImin208Alarm Word 1 ValueModbus 30300Read
AI209Alarm Word 2 ValueModbus 30301Read
AI210Digital Input Word ValueModbus 30302Read
AI211Digital Output Word 1 ValueModbus 30303Read
AI212Digital Output Word 2 ValueModbus 30304Read
AImin213Number of Cond Boilers RunningModbus 30305Read
AI214Number of Cond Boilers RequestedModbus 30306Read
AImin215Number of Non-Cond Boilers RunningModbus 30307Read
AI216Number of Non-Cond Boilers RequestedModbus 30308Read
AI217Number of Cond Boilers in SystemModbus 30309Read
AI218Number of Non-Cond Boilers in SystemModbus 30310Read
AI219Cond Lead Boiler NumberModbus 30311Read
AI220Cond Lag1 Boiler NumberModbus 30312Read
AI221Cond Lag2 Boiler NumberModbus 30313Read
AI222Cond Lag3 Boiler NumberModbus 30314Read
AI223Cond Lag4 Boiler NumberModbus 30315Read
AI224Cond Lag5 Boiler NumberModbus 30316Read
AI225Cond Lag6 Boiler NumberModbus 30317Read
AI226Cond Lag7 Boiler NumberModbus 30318Read
AI227Cond Lag8 Boiler NumberModbus 30319Read
AI228Cond Lag9 Boiler NumberModbus 30320Read
AI229Non-Cond Lead Boiler NumberModbus 30321Read
AI230Non-Cond Lag1 Boiler NumberModbus 30322Read
AI231Non-Cond Lag2 Boiler NumberModbus 30323Read
AI232Non-Cond Lag3 Boiler NumberModbus 30324Read
AI233Non-Cond Lag4 Boiler NumberModbus 30325Read
AI234Non-Cond Lag5 Boiler NumberModbus 30326Read
AI235Non-Cond Lag6 Boiler NumberModbus 30327Read
AI236Non-Cond Lag7 Boiler NumberModbus 30328Read
AI237Non-Cond Lag8 Boiler NumberModbus 30329Read
AI238Non-Cond Lag9 Boiler NumberModbus 30330Read
AI239Damper Mod 1 Input (Prove) DataModbus 30340Read
AI240Damper Mod 1 Output (Reqired) DataModbus 30341Read
AI241Damper Mod 2 Input (Prove) DataModbus 30342Read
AI242Damper Mod 2 Output (Reqired) DataModbus 30343Read
AI243Damper Mod 3 Input (Prove) DataModbus 30344Read
AI244Damper Mod 3 Output (Reqired) DataModbus 30345Read
AI245Damper Mod 4 Input (Prove) DataModbus 30346Read
AI246Damper Mod 4 Output (Reqired) DataModbus 30347Read
AI252Cond Boiler Header TempModbus 40280Read
AImin253Main Supply Header TempModbus 40282Read
AImin254System Return TempModbus 40284Read
AI255OA Temp or Remote Analog SP ValueModbus 40286Read
AI256DHW SetpointModbus 40300Read
AI257Cold Building SetpointModbus 40304Read
AI258Remote Analog Input Setpoint ValueModbus 40306Read
AVmin1Remote Modbus Setpoint ValueModbus 40308; write pointWrite
AV2Remote Modbus Outdoor Air TempModbus 40310; write pointWrite
AVmin3Remote Modbus System EnableModbus 40312; write pointWrite
AVmin4Modbus HeartbeatModbus 40314; write pointWrite
AI259Deadband Cond/Non-Cond Mode Sw TempModbus 40318Read
AI260OA Temp Low Value for Reset CurveModbus 40320Read
AI261OA Temp High Value for Reset CurveModbus 40322Read
AI262Loop Setpoint at Cold (low) OATModbus 40324Read
AI263Loop Setpoint at Warm (high) OATModbus 40326Read
AI264Min Inlet Temp for Non-Cond BoilersModbus 40328Read
AI265Non-Cond Reset ShiftModbus 40336Read
AI266NC/Cond Switch TempModbus 40338Read
AI267Read only NC Header SP (active)Modbus 40340Read
AI268Read only Cond Header SP (active)Modbus 40342Read
AImin312System ModeModbus 40344Read
AI313Cond Boiler StatusModbus 40345Read
AI314Non-Cond Boiler StatusModbus 40346Read
AI269Firing rate for Cond boiler groupModbus 40348Read
AI270Firing rate for non-Cond boiler groupModbus 40350Read
AI271Warm Weather Shutdown TempModbus 40352Read
AI272Cond Boiler 1 Run HoursModbus 40390Read
AI273Cond Boiler 2 Run HoursModbus 40392Read
AI274Cond Boiler 3 Run HoursModbus 40394Read
AI275Cond Boiler 4 Run HoursModbus 40396Read
AI276Cond Boiler 5 Run HoursModbus 40398Read
AI277Cond Boiler 6 Run HoursModbus 40400Read
AI278Cond Boiler 7 Run HoursModbus 40402Read
AI279Cond Boiler 8 Run HoursModbus 40404Read
AI280Cond Boiler 9 Run HoursModbus 40406Read
AI281Cond Boiler 10 Run HoursModbus 40408Read
AI282Non-Cond Boiler A Run HoursModbus 40410Read
AI283Non-Cond Boiler B Run HoursModbus 40412Read
AI284Non-Cond Boiler C Run HoursModbus 40414Read
AI285Non-Cond Boiler D Run HoursModbus 40416Read
AI286Non-Cond Boiler E Run HoursModbus 40418Read
AI287Non-Cond Boiler F Run HoursModbus 40420Read
AI288Non-Cond Boiler G Run HoursModbus 40422Read
AI289Non-Cond Boiler H Run HoursModbus 40424Read
AI290Non-Cond Boiler I Run HoursModbus 40426Read
AI291Non-Cond Boiler J Run HoursModbus 40428Read
AI292Cond Boiler 1 Run CyclesModbus 40430Read
AI293Cond Boiler 2 Run CyclesModbus 40432Read
AI294Cond Boiler 3 Run CyclesModbus 40434Read
AI295Cond Boiler 4 Run CyclesModbus 40436Read
AI296Cond Boiler 5 Run CyclesModbus 40438Read
AI297Cond Boiler 6 Run CyclesModbus 40440Read
AI298Cond Boiler 7 Run CyclesModbus 40442Read
AI299Cond Boiler 8 Run CyclesModbus 40444Read
AI300Cond Boiler 9 Run CyclesModbus 40446Read
AI301Cond Boiler 10 Run CyclesModbus 40448Read
AI302Non-Cond Boiler A Run CyclesModbus 40450Read
AI303Non-Cond Boiler B Run CyclesModbus 40452Read
AI304Non-Cond Boiler C Run CyclesModbus 40454Read
AI305Non-Cond Boiler D Run CyclesModbus 40456Read
AI306Non-Cond Boiler E Run CyclesModbus 40458Read
AI307Non-Cond Boiler F Run CyclesModbus 40460Read
AI308Non-Cond Boiler G Run CyclesModbus 40462Read
AI309Non-Cond Boiler H Run CyclesModbus 40464Read
AI310Non-Cond Boiler I Run CyclesModbus 40466Read
AI311Non-Cond Boiler J Run CyclesModbus 40468Read
Object ID lookup: Cleaver-Brooks HSC Hydronic System Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HSC Hydronic System Controller (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)

How many BACnet points does the Cleaver-Brooks HSC Hydronic System Controller (ProtoNode) have?

This list has 318 BACnet objects: 314 analog inputs, 4 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks HSC Hydronic System Controller (ProtoNode) BACnet points are writable?

4 of the 318 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Cleaver-Brooks HSC Hydronic System Controller (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)?

Start with AV 3 Remote Modbus System Enable (Remote system enable); AV 1 Remote Modbus Setpoint Value (Remote setpoint); AV 4 Modbus Heartbeat (Heartbeat written by the BMS); AI 312 System Mode (System mode); AI 253 Main Supply Header Temp (Main supply header temperature); AI 254 System Return Temp (System return temperature); AI 213 Number of Cond Boilers Running (Condensing boilers running); AI 215 Number of Non-Cond Boilers Running (Non-condensing boilers running); AI 208 Alarm Word 1 Value (Alarm word 1).

How do I enable BMS control of the Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)?

AV 3 Remote Modbus System Enable enables the plant; AV 1 Remote Modbus Setpoint Value sends the setpoint.

Does the Cleaver-Brooks HSC Hydronic System Controller (ProtoNode) need a BACnet heartbeat or have a communication timeout?

AV 4 Modbus Heartbeat is written by the BMS; the guide does not state the timeout.

Can the BMS supply sensor values to the Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)?

AV 2 Remote Modbus Outdoor Air Temp takes an outdoor air temperature from the BMS.

How do I check these points on the real HSC Hydronic System Controller (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.