Steam or hot water boiler control via BACnet gateway · BACnet points list
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) BACnet points list
Updated 7 November 2026Unofficial source
A read-only ProtoNode profile for the Hawk 2000 boiler control: alarm and status bits (limits, actuators, flame safeguard, sensor failures), operating modes, firing rate, setpoint, steam pressure or water temperature, water level, stack temperature, on/off points, run time and cycles.
This page lists 75 BACnet objects for the Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.
- Manufacturer
- Cleaver-Brooks
- Model
- Hawk 2000 boiler control (ProtoNode)
- Equipment
- Steam or hot water boiler control via BACnet gateway
- Equipment type
- Boilers & water heaters
- BACnet objects
- 75 (0 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Default device instance
- 50000 + Modbus Node-ID
- Also known as
- Hawk 2000, CB Hawk 2000, ProtoNode RER, 750-426
- Source document
- Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.
BMS integration notes: Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)
Read-only. Map load demand, steam pressure or water temperature, setpoint, firing rate, main fuel valve and the burner control and low water alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 57 | Boiler Load Demand | Boiler load demand | Read |
| BI 47 | Remote Enable Input | Remote enable input | Read |
| AI 9 | Steam Pres or HW Temp | Steam pressure or hot water temperature | Read |
| AI 7 | Set Point - Steam Pres/ Water Temp | Active setpoint | Read |
| AI 5 | Firing Rate | Firing rate | Read |
| BI 42 | Main Fuel | Main fuel valve open | Read |
| BI 4 | Burner Control Alarm | Burner control alarm | Read |
| BI 3 | Lo Water Cutoff (LWCO) | Low water cutoff | Read |
Network setup
- BACnet Device Instance = the controller's Modbus Node-ID + Node_Offset (default 50,000), so Node-ID 1 = 50001. Change Node_Offset in the ProtoNode web configurator to pick other instances.
- The ProtoNode RER does BACnet MS/TP or BACnet IP, selected on its S bank DIP switches.
- BACnet MS/TP: one MAC address (1-127) for the whole ProtoNode on the A bank DIP switches; baud on B0-B3 (38400 factory default).
- BACnet IP: default ProtoNode address 192.168.1.24; change it in the web configurator.
Watch out for
- Elapsed time and cycle counts appear twice: as two 16-bit word objects and as single objects.
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BI | 2 | Actuator Modbus Comm Fault | Read | |||
| BImin | 3 | Lo Water Cutoff (LWCO) | Read | |||
| BImin | 4 | Burner Control Alarm | Read | |||
| BI | 5 | Boiler Limits Open | Read | |||
| BI | 6 | Hi Stack Temp Alarm | Read | |||
| BI | 7 | Hi-Hi Stack Temp Shutdown | Read | |||
| BI | 8 | Ext Device Interlock Malfunction | Read | |||
| BI | 9 | I/O Module Fault | Read | |||
| BI | 10 | Steam Press Supply Temp Sensor Fail | Read | |||
| BI | 11 | Air Actuator Out Of Pos Alarm | Read | |||
| BI | 12 | F1 Actuator Out Of Pos Alarm | Read | |||
| BI | 14 | No Fuel Selected | Read | |||
| BI | 15 | PLC Battery Not Detected/ Lo | Read | |||
| BI | 16 | Non Recycle Limit Relay Fail | Read | |||
| BI | 17 | Recyle Limit Relay Fail | Read | |||
| BI | 18 | Remote Modulation Signal Fail | Read | |||
| BI | 34 | Purge | Read | |||
| BI | 35 | Release To Modulate | Read | |||
| BI | 36 | Lo Fire Relay | Read | |||
| BI | 37 | Hi Fire Relay | Read | |||
| BI | 38 | Ready to Start/Limits Closed | Read | |||
| BI | 39 | External Start Interlock | Read | |||
| BI | 40 | ALFCO | Read | |||
| BI | 41 | Pilot | Read | |||
| BImin | 42 | Main Fuel | Read | |||
| BI | 43 | Fuel 1 Selected | Read | |||
| BI | 44 | Fuel 2 Selected | Read | |||
| BI | 45 | Burner Control Alarm | Read | |||
| BI | 46 | LWCO | Read | |||
| BImin | 47 | Remote Enable Input | Read | |||
| BI | 49 | Recycle Limit Relay | Read | |||
| BI | 50 | External Device Start (FAD) | Read | |||
| BI | 51 | Non Recycle Limit Relay | Read | |||
| BI | 55 | Alarm Horn Relay | Read | |||
| BImin | 57 | Boiler Load Demand | Read | |||
| BI | 58 | Firing Rate Remote | Read | |||
| BI | 59 | Firing Rate Manual | Read | |||
| BI | 60 | Firing Rate Auto | Read | |||
| BI | 61 | Hot Stand By | Read | |||
| BI | 62 | Warm Up | Read | |||
| BI | 65 | Steam or Hot Water | Read | |||
| BI | 66 | Level Master Present | Read | |||
| BI | 72 | Feedwater or Return Temp Sensor | Read | |||
| BI | 73 | Outdoor Temp Sensor | Read | |||
| BI | 74 | Parallel Posing Selected | Read | |||
| BI | 78 | Hot StandBy Operating Mode Selected | Read | |||
| BI | 79 | Dual Setpoint Operating Mode Selected | Read | |||
| BI | 84 | Honeywell or Fireye | Read | |||
| BI | 85 | Hi Water Alarm | Read | |||
| BI | 86 | Actuator Out Of Pos Alarm: F2 | Read | |||
| BI | 87 | Actuator Out Of Pos Alarm: FGR | Read | |||
| BI | 88 | Actuator Out Of Pos Alarm: F1-2 | Read | |||
| BI | 89 | Actuator Out Of Pos Alarm: F2-2 | Read | |||
| BI | 91 | Modbus Comm Error: Air | Read | |||
| BI | 92 | Modbus Comm Error: F1 | Read | |||
| BI | 93 | Modbus Comm Error: F2 | Read | |||
| BI | 94 | Modbus Comm Error: FGR | Read | |||
| BI | 95 | Modbus Comm Error: F1-2 | Read | |||
| BI | 96 | Modbus Comm Error: F2-2 | Read | |||
| AImin | 5 | Firing Rate | Modbus 30009 | Read | ||
| AImin | 7 | Set Point - Steam Pres/ Water Temp | Modbus 30013 | Read | ||
| AI | 8 | Water Level | Modbus 30015 | Read | ||
| AImin | 9 | Steam Pres or HW Temp | Modbus 30017 | Read | ||
| AI | 11 | Stack Temp Before Econ | Modbus 30021 | Read | ||
| AI | 13 | Water Temp Shell/ Outdoor Temp | Modbus 30025 | Read | ||
| AI | 24 | Boiler Off Point | Modbus 30047 | Read | ||
| AI | 25 | Boiler On Point | Modbus 30049 | Read | ||
| AI | 33 | Fuel 1 Type | Modbus 30056 | Read | ||
| AI | 34 | Fuel 2 Type | Modbus 30057 | Read | ||
| AI | 37 | Elapsed Time (First 16 Bits) | Modbus 30060 | Read | ||
| AI | 38 | Elapsed Time (Second 16 Bits) | Modbus 30061 | Read | ||
| AI | 39 | Number Of Cycles (First 16 Bits) | Modbus 30062 | Read | ||
| AI | 40 | Number Of Cycles (Second 16 Bits) | Modbus 30063 | Read | ||
| AI | 43 | Elapsed Time | Modbus 30064 | Read | ||
| AI | 44 | Number Of Cycles | Modbus 30066 | Read |
No points match these filters.
Object ID lookup: Cleaver-Brooks Hawk 2000 boiler control point IDs by name
BI2Actuator Modbus Comm FaultBI3Lo Water Cutoff (LWCO)BI4Burner Control AlarmBI5Boiler Limits OpenBI6Hi Stack Temp AlarmBI7Hi-Hi Stack Temp ShutdownBI8Ext Device Interlock MalfunctionBI9I/O Module FaultBI10Steam Press Supply Temp Sensor FailBI11Air Actuator Out Of Pos AlarmBI12F1 Actuator Out Of Pos AlarmBI14No Fuel SelectedBI15PLC Battery Not Detected/ LoBI16Non Recycle Limit Relay FailBI17Recyle Limit Relay FailBI18Remote Modulation Signal FailBI34PurgeBI35Release To ModulateBI36Lo Fire RelayBI37Hi Fire RelayBI38Ready to Start/Limits ClosedBI39External Start InterlockBI40ALFCOBI41PilotBI42Main FuelBI43Fuel 1 SelectedBI44Fuel 2 SelectedBI45Burner Control AlarmBI46LWCOBI47Remote Enable InputBI49Recycle Limit RelayBI50External Device Start (FAD)BI51Non Recycle Limit RelayBI55Alarm Horn RelayBI57Boiler Load DemandBI58Firing Rate RemoteBI59Firing Rate ManualBI60Firing Rate AutoBI61Hot Stand ByBI62Warm UpBI65Steam or Hot WaterBI66Level Master PresentBI72Feedwater or Return Temp SensorBI73Outdoor Temp SensorBI74Parallel Posing SelectedBI78Hot StandBy Operating Mode SelectedBI79Dual Setpoint Operating Mode SelectedBI84Honeywell or FireyeBI85Hi Water AlarmBI86Actuator Out Of Pos Alarm: F2BI87Actuator Out Of Pos Alarm: FGRBI88Actuator Out Of Pos Alarm: F1-2BI89Actuator Out Of Pos Alarm: F2-2BI91Modbus Comm Error: AirBI92Modbus Comm Error: F1BI93Modbus Comm Error: F2BI94Modbus Comm Error: FGRBI95Modbus Comm Error: F1-2BI96Modbus Comm Error: F2-2AI5Firing RateAI7Set Point - Steam Pres/ Water TempAI8Water LevelAI9Steam Pres or HW TempAI11Stack Temp Before EconAI13Water Temp Shell/ Outdoor TempAI24Boiler Off PointAI25Boiler On PointAI33Fuel 1 TypeAI34Fuel 2 TypeAI37Elapsed Time (First 16 Bits)AI38Elapsed Time (Second 16 Bits)AI39Number Of Cycles (First 16 Bits)AI40Number Of Cycles (Second 16 Bits)AI43Elapsed TimeAI44Number Of Cycles
Integration notes
- Each Cleaver-Brooks controller on the ProtoNode is its own BACnet device; the object instances below are the same on every device.
- The profile has only AI and BI objects and the guide marks none as write points, so all are read-only.
- The guide gives no engineering units or state texts; units appear only where the object name carries them (DEG F / DEG C).
- Where a description is filled in, it gives the register from the guide's Modbus column.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hawk 2000 boiler control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)
How many BACnet points does the Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) have?
This list has 75 BACnet objects: 16 analog inputs, 59 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) BACnet documentation?
Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.
What are the minimum BACnet points to integrate the Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)?
Start with BI 57 Boiler Load Demand (Boiler load demand); BI 47 Remote Enable Input (Remote enable input); AI 9 Steam Pres or HW Temp (Steam pressure or hot water temperature); AI 7 Set Point - Steam Pres/ Water Temp (Active setpoint); AI 5 Firing Rate (Firing rate); BI 42 Main Fuel (Main fuel valve open); BI 4 Burner Control Alarm (Burner control alarm); BI 3 Lo Water Cutoff (LWCO) (Low water cutoff).
How do I check these points on the real Hawk 2000 boiler control (ProtoNode)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Cleaver-Brooks BACnet points lists
- Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC 1000 deaerator / surge tank control (ProtoNode, EtherNet/IP)
Cleaver-Brooks deaerator and surge tank packages with the ADAC 1000 PLC control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: ADAC 1000, ADAC_1000, ProtoNode RER, 750-426 - Boiler feedwater deaerator and surge tank controller via BACnet gateway
Cleaver-Brooks ADAC deaerator / surge tank control (ProtoNode)
Cleaver-Brooks deaerator and surge tank packages with the ADAC control, read through a ProtoNode RER gateway.
Also known as: ADAC, CB deaerator control, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB120 flame safeguard (ProtoNode)
Cleaver-Brooks boilers with the CB120 flame safeguard, read through a ProtoNode RER gateway.
Also known as: CB120, CB 120, ProtoNode RER, 750-426 - Boiler flame safeguard via BACnet gateway
Cleaver-Brooks CB780 flame safeguard with expanded annunciator (ProtoNode)
Cleaver-Brooks boilers with the CB780 burner management control and expanded annunciator, read through a ProtoNode RER gateway.
Also known as: CB780, CB 780, CB780E, ProtoNode RER, 750-426 - Hot water boiler control via BACnet gateway
Cleaver-Brooks Falcon Hydronic boiler control (ProtoNode)
Cleaver-Brooks hot water boilers with the Falcon hydronic burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Hydronic, ClearFire Falcon, CB Falcon, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Falcon Steam boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Falcon steam burner control, read through a ProtoNode RER gateway.
Also known as: Falcon Steam, CB Falcon steam, ProtoNode RER, 750-426 - Boiler flame safeguard and fuel-air ratio control via BACnet gateway
Cleaver-Brooks FARC with CB780 / CB783 burner control (ProtoNode)
Cleaver-Brooks boilers with a CB780/CB783 burner control and FARC fuel-air ratio control, read through a ProtoNode RER gateway.
Also known as: FARC, CB 780/783, CB783, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 1000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 1000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 1000, CB Hawk 1000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk 4000 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: Hawk 4000, CB Hawk 4000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4000 V2 boiler control (ProtoNode)
Cleaver-Brooks boilers with the HAWK 4000 V2 PLC boiler control, read through a ProtoNode RER gateway.
Also known as: HAWK 4000 V2, CB HAWK 4000 V2, HAWK_4000_V2, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk 4500 boiler control (ProtoNode, EtherNet/IP)
Cleaver-Brooks boilers with the Hawk 4500 PLC boiler control, read through a ProtoNode RER gateway over EtherNet/IP.
Also known as: Hawk 4500, CB Hawk 4500, ProtoNode RER, 750-426 - Steam boiler control via BACnet gateway
Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)
Cleaver-Brooks steam boilers with the Hawk 5000 control, read through a ProtoNode RER gateway.
Also known as: Hawk 5000, CB Hawk 5000, ProtoNode RER, 750-426 - Steam or hot water boiler control via BACnet gateway
Cleaver-Brooks Hawk ICS boiler control (ProtoNode)
Cleaver-Brooks boilers with the Hawk ICS control, read through a ProtoNode RER gateway.
Also known as: Hawk ICS, CB ICS, ProtoNode RER, 750-426 - Boiler lead/lag master panel via BACnet gateway
Cleaver-Brooks Hawk Master Panel lead/lag (ProtoNode)
Cleaver-Brooks Hawk Master Panels sequencing up to eight Hawk boilers (A-H), read through a ProtoNode RER gateway.
Also known as: Hawk Master Panel, Hawk Master, CB Master Panel, ProtoNode RER, 750-426 - Boiler interface module via BACnet gateway
Cleaver-Brooks HSC Boiler Interface Module (ProtoNode)
Cleaver-Brooks HSC boiler interface modules (one boiler each), read through a ProtoNode RER gateway.
Also known as: Boiler Interface Module, HSC Boiler Interface, BIM, ProtoNode RER, 750-426 - Multi-boiler sequencer (hot water boiler plant) via BACnet gateway
Cleaver-Brooks HSC Hydronic System Controller (ProtoNode)
Cleaver-Brooks HSC panels sequencing up to 10 condensing and 10 non-condensing boilers, read through a ProtoNode RER gateway.
Also known as: HSC, Hydronic System Controller, CB HSC, ProtoNode RER, 750-426 - Pump interface module (boiler plant pumps) via BACnet gateway
Cleaver-Brooks HSC Pump Interface Module (ProtoNode)
Cleaver-Brooks HSC pump interface modules (up to four system pumps), read through a ProtoNode RER gateway.
Also known as: Pump Interface Module, HSC Pump Interface, ProtoNode RER, 750-426 - Boiler water level controller via BACnet gateway
Cleaver-Brooks LCS Level Control System (ProtoNode)
Cleaver-Brooks LCS water level controllers (one or two tanks), read through a ProtoNode RER gateway.
Also known as: LCS, Level Control System, ProtoNode RER, 750-426 - Boiler feed pump controller via BACnet gateway
Cleaver-Brooks PCS Pump Control System (ProtoNode)
Cleaver-Brooks PCS pump controllers (up to four pumps on header pressure or tank level), read through a ProtoNode RER gateway.
Also known as: PCS, Pump Control System, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 100 power meter profile (ProtoNode)
Shark 100 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 100, Electro Industries Shark 100, ProtoNode RER, 750-426 - Electric power meter via BACnet gateway
Cleaver-Brooks Shark 200 power meter profile (ProtoNode)
Shark 200 power meters supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: Shark 200, Electro Industries Shark 200, ProtoNode RER, 750-426 - Process loop controller via BACnet gateway
Cleaver-Brooks UDC 2500 loop controller profile (ProtoNode)
Honeywell UDC 2500 loop controllers supplied on Cleaver-Brooks equipment, read through a ProtoNode RER gateway.
Also known as: UDC 2500, UDC2500, Honeywell UDC 2500, ProtoNode RER, 750-426
Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.