Steam or hot water boiler control via BACnet gateway · BACnet points list

Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A read-only ProtoNode profile for the Hawk 2000 boiler control: alarm and status bits (limits, actuators, flame safeguard, sensor failures), operating modes, firing rate, setpoint, steam pressure or water temperature, water level, stack temperature, on/off points, run time and cycles.

This page lists 75 BACnet objects for the Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
Hawk 2000 boiler control (ProtoNode)
Equipment
Steam or hot water boiler control via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
75 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
Hawk 2000, CB Hawk 2000, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 75 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)

Integration in brief

Read-only. Map load demand, steam pressure or water temperature, setpoint, firing rate, main fuel valve and the burner control and low water alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 57Boiler Load DemandBoiler load demandRead
BI 47Remote Enable InputRemote enable inputRead
AI 9Steam Pres or HW TempSteam pressure or hot water temperatureRead
AI 7Set Point - Steam Pres/ Water TempActive setpointRead
AI 5Firing RateFiring rateRead
BI 42Main FuelMain fuel valve openRead
BI 4Burner Control AlarmBurner control alarmRead
BI 3Lo Water Cutoff (LWCO)Low water cutoffRead

Network setup

Watch out for

Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

75 of 75 shown
Type
AnalogBinary
Show
Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) BACnet Points List
DescriptionStates
BI2Actuator Modbus Comm FaultRead
BImin3Lo Water Cutoff (LWCO)Read
BImin4Burner Control AlarmRead
BI5Boiler Limits OpenRead
BI6Hi Stack Temp AlarmRead
BI7Hi-Hi Stack Temp ShutdownRead
BI8Ext Device Interlock MalfunctionRead
BI9I/O Module FaultRead
BI10Steam Press Supply Temp Sensor FailRead
BI11Air Actuator Out Of Pos AlarmRead
BI12F1 Actuator Out Of Pos AlarmRead
BI14No Fuel SelectedRead
BI15PLC Battery Not Detected/ LoRead
BI16Non Recycle Limit Relay FailRead
BI17Recyle Limit Relay FailRead
BI18Remote Modulation Signal FailRead
BI34PurgeRead
BI35Release To ModulateRead
BI36Lo Fire RelayRead
BI37Hi Fire RelayRead
BI38Ready to Start/Limits ClosedRead
BI39External Start InterlockRead
BI40ALFCORead
BI41PilotRead
BImin42Main FuelRead
BI43Fuel 1 SelectedRead
BI44Fuel 2 SelectedRead
BI45Burner Control AlarmRead
BI46LWCORead
BImin47Remote Enable InputRead
BI49Recycle Limit RelayRead
BI50External Device Start (FAD)Read
BI51Non Recycle Limit RelayRead
BI55Alarm Horn RelayRead
BImin57Boiler Load DemandRead
BI58Firing Rate RemoteRead
BI59Firing Rate ManualRead
BI60Firing Rate AutoRead
BI61Hot Stand ByRead
BI62Warm UpRead
BI65Steam or Hot WaterRead
BI66Level Master PresentRead
BI72Feedwater or Return Temp SensorRead
BI73Outdoor Temp SensorRead
BI74Parallel Posing SelectedRead
BI78Hot StandBy Operating Mode SelectedRead
BI79Dual Setpoint Operating Mode SelectedRead
BI84Honeywell or FireyeRead
BI85Hi Water AlarmRead
BI86Actuator Out Of Pos Alarm: F2Read
BI87Actuator Out Of Pos Alarm: FGRRead
BI88Actuator Out Of Pos Alarm: F1-2Read
BI89Actuator Out Of Pos Alarm: F2-2Read
BI91Modbus Comm Error: AirRead
BI92Modbus Comm Error: F1Read
BI93Modbus Comm Error: F2Read
BI94Modbus Comm Error: FGRRead
BI95Modbus Comm Error: F1-2Read
BI96Modbus Comm Error: F2-2Read
AImin5Firing RateModbus 30009Read
AImin7Set Point - Steam Pres/ Water TempModbus 30013Read
AI8Water LevelModbus 30015Read
AImin9Steam Pres or HW TempModbus 30017Read
AI11Stack Temp Before EconModbus 30021Read
AI13Water Temp Shell/ Outdoor TempModbus 30025Read
AI24Boiler Off PointModbus 30047Read
AI25Boiler On PointModbus 30049Read
AI33Fuel 1 TypeModbus 30056Read
AI34Fuel 2 TypeModbus 30057Read
AI37Elapsed Time (First 16 Bits)Modbus 30060Read
AI38Elapsed Time (Second 16 Bits)Modbus 30061Read
AI39Number Of Cycles (First 16 Bits)Modbus 30062Read
AI40Number Of Cycles (Second 16 Bits)Modbus 30063Read
AI43Elapsed TimeModbus 30064Read
AI44Number Of CyclesModbus 30066Read
Object ID lookup: Cleaver-Brooks Hawk 2000 boiler control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hawk 2000 boiler control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)

How many BACnet points does the Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) have?

This list has 75 BACnet objects: 16 analog inputs, 59 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Cleaver-Brooks Hawk 2000 boiler control (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks Hawk 2000 boiler control (ProtoNode)?

Start with BI 57 Boiler Load Demand (Boiler load demand); BI 47 Remote Enable Input (Remote enable input); AI 9 Steam Pres or HW Temp (Steam pressure or hot water temperature); AI 7 Set Point - Steam Pres/ Water Temp (Active setpoint); AI 5 Firing Rate (Firing rate); BI 42 Main Fuel (Main fuel valve open); BI 4 Burner Control Alarm (Burner control alarm); BI 3 Lo Water Cutoff (LWCO) (Low water cutoff).

How do I check these points on the real Hawk 2000 boiler control (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.