Steam boiler control via BACnet gateway · BACnet points list

Cleaver-Brooks Hawk 5000 boiler control (ProtoNode) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

A read-only ProtoNode profile for the Hawk 5000 control: burner sequence and limit inputs, transmitter bad-quality and high/low alarm bits, steam pressure, drum level, steam and feedwater flow, stack and economizer temperatures, O2, VSD data, actuator positions, setpoints and burner control status.

This page lists 266 BACnet objects for the Cleaver-Brooks Hawk 5000 boiler control (ProtoNode) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Cleaver-Brooks’s documentation hosted by watmfg.com, not by Cleaver-Brooks itself, so treat it as unofficial.

Manufacturer
Cleaver-Brooks
Model
Hawk 5000 boiler control (ProtoNode)
Equipment
Steam boiler control via BACnet gateway
Equipment type
Boilers & water heaters
BACnet objects
266 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Default device instance
50000 + Modbus Node-ID
Also known as
Hawk 5000, CB Hawk 5000, ProtoNode RER, 750-426
Source document
Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018 (unofficial copy, hosted by watmfg.com)
Download CSV 266 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Cleaver-Brooks’s current documentation and the live device before use. Not official Cleaver-Brooks information. Terms of use.

BMS integration notes: Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)

Integration in brief

Read-only. Map steam pressure and setpoint, drum level, firing rate, blower running and the burner control fault.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Steam PressSteam pressureRead
AI 17Steam Press SPSteam pressure setpointRead
AI 2Drum LevelDrum levelRead
AI 23Firing RateFiring rateRead
BI 1Comb Air Blower RunningCombustion air blower runningRead
BI 38Load DemandLoad demandRead
BI 148Burner Control Fault AlmBurner control fault alarmRead
BI 14Lo Water Cutoff (LWCO)Low water cutoffRead

Network setup

Cleaver-Brooks Hawk 5000 boiler control (ProtoNode) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

266 of 266 shown
Type
AnalogBinary
Show
Cleaver-Brooks Hawk 5000 boiler control (ProtoNode) BACnet Points List
DescriptionStates
BImin1Comb Air Blower RunningRead
BI2FSG Purge CmdRead
BI3FSG Release To Modulate CmdRead
BI4Actuators At Lo FireRead
BI5Actuators At Hi FireRead
BI6Ready To Start/ Limits ClosedRead
BI7Ext. Start Interlock ProvenRead
BI8ALFCORead
BI9FSG Pilot Terminal EnergizedRead
BI10FSG Main Fuel Terminal EnergizedRead
BI11Fuel Selector Switch - Fuel 1 PosRead
BI12Fuel Selector Switch - Fuel 2 PosRead
BI13FSG Burner Control Com AlmRead
BImin14Lo Water Cutoff (LWCO)Read
BI15FSG Lo Fire CmdRead
BI16Burner Start Relay EnergizedRead
BI17Hi Water Cutoff (HWCO)Read
BI18Yokagawa O2 Analyzer Ready StatusRead
BI19VSD Bypass Switch - Bypass PosRead
BI20Hi Steam Press SwitchRead
BI21Aux Lo Water Cutoff (ALWCO)Read
BI22Lo Gas Press/Oil Temp Switch (LGP/LOT)Read
BI23Hi Gas Press/Oil Temp Switch (HGP/HOT)Read
BI24Lo Oil Press (LOP)Read
BI25Hi Oil Press (HOP)Read
BI26Atomizing Media Flo and Press SwitchesRead
BI27Lo Water AlmRead
BI28Comb Air Press SwitchRead
BI29Hi Water AlmRead
BI30Hi Stack/ Furnace Press SwitchRead
BI31Lo Inst Air Press SwitchRead
BI32Oil Gun Inserted Limit SwitchRead
BI33Recycle Limit RelayRead
BI34Ext. Device Start InterlockRead
BI35Non-Recycle Limit RelayRead
BI36Proof Of Lo FireRead
BI37Proof Of Hi FireRead
BImin38Load DemandRead
BI39Alm Bell RelayRead
BI40Boiler ReadyRead
BI41AB[2].8Read
BI42AB[2].9Read
BI43AB[2].10Read
BI44AB[2].11Read
BI45AB[2].12Read
BI46AB[2].13Read
BI47AB[2].14Read
BI48AB[2].15Read
BI49Bad Ql- Steam Press (06:00)Read
BI50Bad Ql- Drum Level (06:01)Read
BI51Bad Ql- Stack Temp (06:02)Read
BI52Bad Ql- Remote Modulation (06:03)Read
BI53Bad Ql- Steam Flo (06:04)Read
BI54Bad Ql- Mud Drm Shell Tmp (06:05)Read
BI55Bad Ql- Act5 (VSD) FB (06:06)Read
BI56Bad Ql- Flue Gas O2 (06:07)Read
BI57Bad Ql- F1 Flo or Usr Def (07:00)Read
BI58Bad Ql- F2 Flo or Usr Def (07:01)Read
BI59Bad Ql- Stack Draft or Usr Def (07:02)Read
BI60Bad Ql- Feedwtr Flo or Usr Def (07:03)Read
BI61Bad Ql- Ecn Out FG Tmp -Usr Def (07:04Read
BI62Bad Ql- Ecn In FW Tmp - Usr Def (07:05Read
BI63Bad Ql- Ecn Out FW Tmp -Usr Def (07:06Read
BI64Bad Ql- Air Flo or Usr Def (07:07)Read
BI65Bad Ql- Actuator1 (Air) FB (09:00)Read
BI66Bad Ql- Actuator2 (F1) FB (09:01)Read
BI67Bad Ql- Actuator3 (F2) FB (09:02)Read
BI68Bad Ql- Actuator (FGR) FB (09:03)Read
BI69Bad Ql- Actuator8 (2nd Air) FB (09:04)Read
BI70Bad Ql- Actuator9 (2nd F1) FB (09:05)Read
BI71Bad Ql- Reserved (09:06)Read
BI72Bad Ql- Reserved (09:07)Read
BI73HAlm - Steam Press (Xmtr)Read
BI74HAlm - Drum Level (xmtr)Read
BI75HAlm - Stack Temp (Xmtr)Read
BI76HAlm - Remote Modulation InputRead
BI77HAlm - Steam Flo (Xmtr)Read
BI78HAlm - Mud Drum Shell Temp (Xmtr)Read
BI79HAlm - VSD Speed Feedback (Xmtr)Read
BI80HAlm - Flue Gas O2 (Xmtr)Read
BI81HAlm - F1 Flo (Xmtr)Read
BI82HAlm - F2 Flo (Xmtr)Read
BI83HAlm - Stack Draft (Xmtr)Read
BI84HAlm - Feedwater Flo (Xmtr)Read
BI85HAlm - Econ Outlet FG Temp (Xmtr)Read
BI86HAlm - Econ Inlet FW Temp (Xmtr)Read
BI87HAlm - Econ Outlet FW Temp (Xmtr)Read
BI88HAlm - Air Flo Hi (Xmtr)Read
BI89HHAlm - Stack Tmp Hi-Hi SHUTDWN (Xmtr)Read
BI90HAlm - Hi Water Cutoff (Contact)Read
BI91HAlm - Hi Gas Pressure (Contact)Read
BI92HAlm - Hi Oil Temp (Contact)Read
BI93HAlm - Hi Oil Pressure (Contact)Read
BI94HAlm - Hi Water Alm (Contact)Read
BI95HHAlm - Hi-Hi Furn Press SHTDWNRead
BI96ReservedRead
BI97LAlm - Steam Press (Xmtr)Read
BI98LAlm - Drum Level (Xmtr)Read
BI99LAlm - Stack Temp (Xmtr)Read
BI100LAlm - Remote ModulationRead
BI101LAlm - Steam Flo (Xmtr)Read
BI102LAlm - Mud Drum Shell Temp (Xmtr)Read
BI103LAlm - VSD Speed FeedbackRead
BI104LAlm - Flo Gas O2 (Xmtr)Read
BI105LAlm - F1 Flo (Xmtr)Read
BI106LAlm - F2 Flo (Xmtr)Read
BI107LAlm - Stack Draft (Xmtr)Read
BI108LAlm - Feedwtr Flo (Xmtr)Read
BI109LAlm - Econ Outlet FG Temp (Xmtr)Read
BI110LAlm - Econ Inlet Feedwtr Temp (Xmtr)Read
BI111LAlm - Econ Outlet Feedwtr Temp (Xmtr)Read
BI112LAlm - Air Flo (Xmtr)Read
BI113LAlm - Lo wtr Cutoff (Contact)Read
BI114LAlm - Aux Lo wtr Cutoff (Contact)Read
BI115LAlm - Lo Gas Press (Contact)Read
BI116LAlm - Lo Oil Temp (Contact)Read
BI117LAlm - Lo Oil Press (Contact)Read
BI118LAlm - Lo wtr Alm (Contact)Read
BI119LAlm - Lo Comb Air Press (Contact)Read
BI120LAlm - Lo Inst Air Press (Contact)Read
BI121LLAlm - Flo Gas O2 Lo-Lo SHUTDOWNRead
BI122AB[7].9Read
BI123AB[7].10Read
BI124AB[7].11Read
BI125AB[7].12Read
BI126AB[7].13Read
BI127AB[7].14Read
BI128AB[7].15Read
BI129Burner Control Alm (Contact)Read
BI130Yokagawa O2 Analyzer Not ReadyRead
BI131Lo Atomizing Media (Contact)Read
BI132Oil Gun Pos Switch Not Made (Contact)Read
BI133Recycle Limit Relay (RLR) FaultRead
BI134Non-Recycle Limit Relay (NRLR) FaultRead
BI135Actuator1 (Air) Out Of Pos AlmRead
BI136Actuator2 (F1) Out Of Pos AlmRead
BI137Actuator3 (F2) Out Of Pos AlmRead
BI138Actuator (FGR) Out Of Pos AlmRead
BI139Act1 (Air) Feedback Outside Cal RngRead
BI140Act2 (F1) Feedback Outside Cal RngRead
BI141Act3 (F2) Feedback Outside Cal RngRead
BI142Actu (FGR) Feedback Outside Cal RngRead
BI143Ext. Start Interlock Not Closed AlmRead
BI144Actuator5 (VSD) FB / CVDeviation AlmRead
BI145A-B VSD Fault AlmRead
BI146Modbus Comm ErrorRead
BI147I/O Module ## Fault Detected AlmRead
BImin148Burner Control Fault AlmRead
BI149Hi Limit Cutoff AlmRead
BI150CPU Battery AlmRead
BI151Actuator8 (2nd Air) Out Of Pos AlmRead
BI152Actuator9 (2nd F1) Out Of Pos AlmRead
BI153Actuator8 (2nd Air) FB Outside Cal RngRead
BI154Actuator9 (2nd F1) FB Outside Cal RngRead
BI155ReservedRead
BI156ReservedRead
BI157ReservedRead
BI158No Fuel SelectedRead
BI159EIP Comm Link FAULT - Master PanelRead
BI160ReservedRead
BI161HAlm - Usr Def (07:00)Read
BI162HAlm - Usr Def (07:01)Read
BI163HAlm - Usr Def (07:02)Read
BI164HAlm - Usr Def (07:03)Read
BI165HAlm - Usr Def (07:04)Read
BI166HAlm - Usr Def (07:05)Read
BI167HAlm - Usr Def (07:06)Read
BI168HAlm - Usr Def (07:07)Read
BI169Input Bad Quality - Usr Def (07:00)Read
BI170Input Bad Quality - Usr Def (07:01)Read
BI171Input Bad Quality - Usr Def (07:02)Read
BI172Input Bad Quality - Usr Def (07:03)Read
BI173Input Bad Quality - Usr Def (07:04)Read
BI174Input Bad Quality - Usr Def (07:05)Read
BI175Input Bad Quality - Usr Def (07:06)Read
BI176Input Bad Quality - Usr Def (07:07)Read
BI177LAlm - Usr Def (07:00)Read
BI178LAlm - Usr Def (07:01)Read
BI179LAlm - Usr Def (07:02)Read
BI180LAlm - Usr Def (07:03)Read
BI181LAlm - Usr Def (07:04)Read
BI182LAlm - Usr Def (07:05)Read
BI183LAlm - Usr Def (07:06)Read
BI184LAlm - Usr Def (07:07)Read
BI185ReservedRead
BI186ReservedRead
BI187ReservedRead
BI188ReservedRead
BI189ReservedRead
BI190ReservedRead
BI191ReservedRead
BI192ReservedRead
AImin1Steam PressModbus 30001Read
AImin2Drum LevelModbus 30003Read
AI3Stack TempModbus 30005Read
AI4Remote ModulationModbus 30007Read
AI5Steam FloModbus 30009Read
AI6Mud Drum Shell TempModbus 30011Read
AI7VSD Speed FeedbackModbus 30013Read
AI8Flue Gas O2Modbus 30015Read
AI9F1 Flo or Usr DefModbus 30017Read
AI10F2 Flo or Usr DefModbus 30019Read
AI11Stack Draft or Usr DefModbus 30021Read
AI12Feedwtr Flo or Usr DefModbus 30023Read
AI13Econ Outlet FG Temp or Usr DefModbus 30025Read
AI14Econ Inlet FW Temp or Usr DefModbus 30027Read
AI15Econ Outlet FW Temp or Usr DefModbus 30029Read
AI16Air Flo or Usr DefModbus 30031Read
AImin17Steam Press SPModbus 30033Read
AI18Drum Level SPModbus 30035Read
AI19Flue Gas O2 SPModbus 30037Read
AI20Boiler EffiiciencyModbus 30039Read
AI21VSD Motor KWModbus 30041Read
AI22VSD Motor CurrentModbus 30043Read
AImin23Firing RateModbus 30045Read
AI24Drum Level %Modbus 30047Read
AI25Jackshaft Actuator (Pct)Modbus 30049Read
AI26Actuator7 (Feedwtr Valve) (Pct)Modbus 30051Read
AI27Actuator5 (VSD) (Pct)Modbus 30053Read
AI28Actuator6 (Outlet Damper) (Pct)Modbus 30055Read
AI29Actuator1 (Air) CV (POSP_SP)Modbus 30057Read
AI30Actuator2 (F1) CV (POSP_SP)Modbus 30059Read
AI31Actuator3 (F2) CV (POSP_SP)Modbus 30061Read
AI32Actuator4 (FGR) CV (POSP_ SP)Modbus 30063Read
AI33VSD Speed (Hz)Modbus 30065Read
AI34Boiler Number Derrived From IP AddressModbus 30067Read
AI35ReservedModbus 30069Read
AI36ReservedModbus 30071Read
AI37ReservedModbus 30073Read
AI38ReservedModbus 30075Read
AI39ReservedModbus 30077Read
AI40ReservedModbus 30079Read
AI41Elapsed TimeModbus 30081Read
AI42Number Of CyclesModbus 30082Read
AI43Steam Press (06:00)Modbus 30083Read
AI44Drum Level (06:01)Modbus 30084Read
AI45Stack Temp (06:02)Modbus 30085Read
AI46Remote Modulation (06:03)Modbus 30086Read
AI47Steam Flo (06:04)Modbus 30087Read
AI48Mud Drum Shell Temp (06:05)Modbus 30088Read
AI49Actuator5 (VSD) FB (06:06)Modbus 30089Read
AI50Flue Gas O2 (06:07)Modbus 30090Read
AI51F1 Flo or Usr Def (07:00)Modbus 30091Read
AI52F2 Flo or Usr Def (07:01)Modbus 30092Read
AI53Stack Draft or Usr Def (07:02)Modbus 30093Read
AI54Feedwtr Flo or Usr Def (07:03)Modbus 30094Read
AI55Econ Outlet FG Temp or Usr Def (07:04)Modbus 30095Read
AI56Econ Inlet FW Temp or Usr Def (07:05)Modbus 30096Read
AI57Econ Outlet FW Temp or Usr Def (07:06)Modbus 30097Read
AI58Air Flo or Usr Def (07:07)Modbus 30098Read
AI59Alm Tickler State RegisterModbus 30099Read
AI60Fuel 1 TypeModbus 30100Read
AI61Fuel 2 TypeModbus 30101Read
AI62Flame Strength - CB120Modbus 30102Read
AI63Flame Strength - CB780Modbus 30103Read
AI64Main Flame FlickerModbus 30104Read
AI65ReservedModbus 30105Read
AI66ReservedModbus 30106Read
AI67Burner Control Status Line 00Modbus 30107Read
AI68Burner Control Diagnostics 05Modbus 30108Read
AI69Failed I/O Module NumberModbus 30109Read
AI70IP Address 00Modbus 30110Read
AI71IP Address 01Modbus 30111Read
AI72IP Address 02Modbus 30112Read
AI73IP Address 03Modbus 30113Read
AI74IP Address 04Modbus 30114Read
Object ID lookup: Cleaver-Brooks Hawk 5000 boiler control point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Hawk 5000 boiler control (ProtoNode) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)

How many BACnet points does the Cleaver-Brooks Hawk 5000 boiler control (ProtoNode) have?

This list has 266 BACnet objects: 74 analog inputs, 192 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Cleaver-Brooks Hawk 5000 boiler control (ProtoNode) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Cleaver-Brooks Hawk 5000 boiler control (ProtoNode) BACnet documentation?

Cleaver-Brooks does not publish it on its own website. This list comes from Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products (750-426), revision 03/2018, a copy hosted by watmfg.com at https://watmfg.com/watmfg23082016/wp-content/uploads/2016/09/750-426-ProtoNode-Cloud.pdf. Ask Cleaver-Brooks or its representative for the current revision.

What are the minimum BACnet points to integrate the Cleaver-Brooks Hawk 5000 boiler control (ProtoNode)?

Start with AI 1 Steam Press (Steam pressure); AI 17 Steam Press SP (Steam pressure setpoint); AI 2 Drum Level (Drum level); AI 23 Firing Rate (Firing rate); BI 1 Comb Air Blower Running (Combustion air blower running); BI 38 Load Demand (Load demand); BI 148 Burner Control Fault Alm (Burner control fault alarm); BI 14 Lo Water Cutoff (LWCO) (Low water cutoff).

How do I check these points on the real Hawk 5000 boiler control (ProtoNode)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Cleaver-Brooks BACnet points lists

Source: Cloud Enabled ProtoNode Gateway Startup Guide (RER/LER) for interfacing Cleaver-Brooks products · 750-426 · rev. 03/2018. Object names, instances and units are reproduced as published; descriptions are our own.