Rooftop unit economizer controller · BACnet points list
Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM) BACnet points list
Updated 12 November 2026Unofficial source
The ZIP Economizer is a rooftop unit economizer controller that runs free cooling, integrated cooling, DCV, ventilation, purge and compressor lockouts from thermostat calls. With the ECON-ZIP-COM module it is a BACnet MS/TP device that reports temperatures, humidity, enthalpy, CO2, damper position, run times, thermostat and relay states, operating mode and the active alarm. The BMS can send occupancy, heating and cooling commands, feed network sensor values, and adjust setpoints and changeover limits.
This page lists 71 BACnet objects for the Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM) — 32 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Belimo’s documentation hosted by ZOT Supply, not by Belimo itself, so treat it as unofficial.
- Manufacturer
- Belimo
- Model
- ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM)
- Equipment
- Rooftop unit economizer controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 71 (32 writable)
- Transport
- BACnet MS/TP
- Firmware
- Application 02.01.1003, firmware 08.04.0000
- Also known as
- ZIP Economizer, ECON-ZIP-BASE, ECON-ZIP-COM, ECON-ZIP-EM, Belimo economizer controller BACnet, ZIP Economizer BACnet
- Source document
- ZIP Economizer Installation and Operation Manual, BACnet Object Descriptions · rev. Tech.Doc 03/21 (unofficial copy, hosted by ZOT Supply)
Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.
BMS integration notes: Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM)
Select BACnet Active in the Com Interface menu and set baud, device ID and MS/TP address. Command occupancy and the Y1/Y2/W1 calls through MO 1-5, or let the thermostat drive them, and read MI 1 operating mode, AI 1 damper position, SAT/OAT and BI 1 / MI 2 for alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MO 1 | OccupancyCommand | Occupancy (fan): 1 enabled, 2 disabled | Command |
| MO 4 | Y1Command | Stage 1 cooling call | Command |
| MO 5 | Y2Command | Stage 2 cooling call | Command |
| MO 3 | W1Command | Heating call | Command |
| AV 2 | SpFreeCoolSAT | Free cooling supply air setpoint | Write |
| MI 1 | OperationMode | Operating mode (free cooling, DCV, etc.) | Read |
| AI 1 | RelPosDmpFb | Damper position feedback, % | Read |
| AI 2 | SAT | Supply air temperature | Read |
| AI 3 | OAT | Outdoor air temperature | Read |
| MI 2 | CurrentAlarm | Most recent active alarm | Read |
Enable & remote start
Set Com Interface to BACnet Active (default is MP Active); the ECON-ZIP-COM module is required.
Heartbeat & communication loss
AV 18 BusWatchdog sets a bus timeout of 0-3600 s (0 = off, the default). When it trips, the commandable objects fall back to their relinquish defaults.
Sensors & values from the BMS
AO 1-5 accept CO2, outdoor and return humidity and temperature from the network; they read 8888 (no value) until written.
Network setup
- Com Interface menu: BACnet Active, then baud (9600-115200), BACnet Device ID and MS/TP address.
- At least one SAT and one OAT sensor and one compressor are needed for economizer operation.
- Attached devices are auto-detected; their settings appear once detected.
Watch out for
- MO commands relinquish (value 3) to hand control back to the thermostat inputs.
- PurgeCommand works only with BV 1 PurgeOperationEn active.
- Remote damper override needs BV 3 RemoteDmpOverrideEn active.
Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | RelPosDmpFb | Damper position feedback | % | Read | |
| AImin | 2 | SAT | Supply air temperature | °F | Read | |
| AImin | 3 | OAT | Outdoor air temperature | °F | Read | |
| AI | 4 | OAH | Outdoor air humidity | %RH | Read | |
| AI | 5 | OAE | Outdoor air enthalpy | Btu/lb | Read | |
| AI | 6 | RAT | Return air temperature | °F | Read | |
| AI | 7 | RAH | Return air humidity | %RH | Read | |
| AI | 8 | RAE | Return air enthalpy | Btu/lb | Read | |
| AI | 9 | CO2Concentration | CO2 concentration | ppm | Read | |
| AI | 10 | SpDmpPos | Damper position output | % | Read | |
| AI | 11 | RunTimeCompressor1 | Run time, compressor 1 | h | Read | |
| AI | 12 | RunTimeCompressor2 | Run time, compressor 2 | h | Read | |
| AI | 13 | RunTimeEcon | Run time, free cooling | h | Read | |
| AI | 14 | RunTimeMechanical | Run time, mechanical cooling | h | Read | |
| AI | 15 | RunTimeDCV | Run time, demand control ventilation | h | Read | |
| AI | 16 | RunTimeIntegrated | Run time, integrated cooling | h | Read | |
| AI | 17 | RunTimeVentilation | Run time, ventilation | h | Read | |
| AI | 18 | RunTimeHeating | Run time, heating | h | Read | |
| AI | 19 | RunTimeUnoccupied | Run time, unoccupied | h | Read | |
| AI | 20 | RunTimeFreezeProtection | Run time, freeze protection | h | Read | |
| AI | 21 | DeviceProductionDate | Production date | Read | ||
| AO | 1 | CO2Network | CO2 value from the network, 250-2200 | ppm | Command | |
| AO | 2 | OAHNetwork | Outdoor air humidity from the network, 5-100 | %RH | Command | |
| AO | 3 | OATNetwork | Outdoor air temperature from the network, -50 to 160 | °F | Command | |
| AO | 4 | RAHNetwork | Return or space humidity from the network, 5-100 | %RH | Command | |
| AO | 5 | RATNetwork | Return or space temperature from the network, -50 to 160 | °F | Command | |
| AO | 6 | RemoteDmpOverridePos | Damper override position; disables FC, VENT, DCV, Purge | % | Command | |
| AV | 1 | SpCO2PPM | Zone CO2 setpoint, 500-2000 | ppm | Write | |
| AVmin | 2 | SpFreeCoolSAT | Free cooling SAT setpoint, 45-70 (default 55) | °F | Write | |
| AV | 3 | VentMin | Ventilation minimum damper position | % | Write | |
| AV | 4 | LowSpeedVentMin | Ventilation minimum damper position at low fan speed | % | Write | |
| AV | 5 | DCVMin | DCV minimum damper position | % | Write | |
| AV | 6 | LowSpeedDCVMin | DCV minimum damper position at low fan speed | % | Write | |
| AV | 7 | ExhFanOn | Damper position that enables the exhaust fan | % | Write | |
| AV | 8 | LowSpeedExhFanOn | Exhaust fan enable damper position at low fan speed | % | Write | |
| AV | 9 | PurgeDmpPos | Purge mode damper position | % | Write | |
| AV | 10 | DrybulbHighLimit | High limit, single dry bulb changeover, 60-80 | °F | Write | |
| AV | 11 | EnthHighLimit | Enthalpy high limit, single enthalpy, 25-30 | Btu/lb | Write | |
| AV | 12 | DiffEnthHighLimit | Enthalpy high limit, differential enthalpy, 25-30 | Btu/lb | Write | |
| AV | 13 | DiffDrybulbHighLimit | Temperature high limit, differential dry bulb, 60-80 | °F | Write | |
| AV | 14 | EnthTempHighLimit | Temperature high limit, single enthalpy, 60-80 | °F | Write | |
| AV | 15 | DiffEnthTempHighLimit | Temperature high limit, differential enthalpy, 60-80 | °F | Write | |
| AV | 16 | LowOATCompLockoutLimit | Lowest OAT for compressor operation (LCLO), 40-65 | °F | Write | |
| AV | 17 | ZIPCode | ZIP code; sets high limits for the climate zone | Write | ||
| AV | 18 | BusWatchdog | Bus watchdog timeout, 0-3600, 0 = off | s | Write | |
| BI | 1 | AlarmState | Alarm state | Read | Active/Inactive | |
| BI | 2 | G | Occupancy (fan) state | Read | Active/Inactive | |
| BI | 3 | Y1 | Stage 1 cooling request | Read | Active/Inactive | |
| BI | 4 | Y2 | Stage 2 cooling request | Read | Active/Inactive | |
| BI | 5 | W1 | Stage 1 heating request | Read | Active/Inactive | |
| BI | 6 | Compressor1State | CC1 relay state | Read | Active/Inactive | |
| BI | 7 | Compressor2State | CC2 relay state | Read | Active/Inactive | |
| BI | 8 | ExhFanState | Exhaust fan relay state | Read | Active/Inactive | |
| BI | 9 | SATLowLimState | Compressor disabled, SAT too low | Read | Active/Inactive | |
| BI | 10 | LowOATCompLockoutState | Low ambient compressor lockout (LCLO) | Read | Active/Inactive | |
| BI | 11 | PurgeState | Purge requested (PurgeCommand or AUX2) | Read | Active/Inactive | |
| BI | 12 | FanSpeedState | Indoor fan speed | Read | Active/Inactive | |
| BV | 1 | PurgeOperationEn | Enable purge operation (default Inactive) | Write | Active/Inactive | |
| BV | 2 | SatY2LimitEn | Enable default SAT Y2 limit (default Active) | Write | Active/Inactive | |
| BV | 3 | RemoteDmpOverrideEn | Enable remote damper override (default Inactive) | Write | Active/Inactive | |
| MImin | 1 | OperationMode | Current operating mode | Read | 1=Virgin, 2=Auto, 3=Manual, 4=Factory Test, 5=Acceptance Tests, 6=Free Cooling, 7=Integrated Cooling, 8=Mechanical Cooling, 9=DCV, 10=Ventilation, 11=Heating, 12=Unoccupied, 13=Purge, 14=Freeze Protection, 15=Brownout, 16=PCB Test, 17=Recovery, 18=Damper Scaling | |
| MImin | 2 | CurrentAlarm | Most recent active alarm | Read | 1=OAT_OR, 2=OAT_ND, 3=OAH_OR, 4=OAH_ND, 5=OAHDT, 6=OAH, 7=RAT_OR1, 8=RAT_ND1, 9=RAT_OR2, 10=RAT_ND2, 11=RAH_OR, 12=RAH_ND, 13=RHnoOAH, 14=RHnoRAT, 15=SAT_OR, 16=SAT_ND, 17=Y2noY1, 18=SAT_Er1, 19=SAT_Er2, 20=Dmp_Pos, 21=SAT_Er3, 22=Dmp_Stk, 23=EM_ND, 24=EF_ND, 25=CC1_ND, 26=CC2_ND, 27=IF_ND, 28=CO2_ND, 29=CO2_OR, 30=W1 and Y1, 31=No_Alm | |
| MI | 3 | CompressorQuantity | Compressors detected or selected | Read | 1=Auto, 2=1 compressor, 3=2 compressors, 4=undefined | |
| MI | 4 | ClimateZone | Climate zone from the ZIP code | Read | 1-19=US zones 1A-8 (without California), 20-35=California zones 1-16, 36=Canada | |
| MI | 5 | StatusCompressor1 | Compressor 1 status | Read | 1=Available, 2=off SAT ok, 3=off checking SAT, 4=off Econ Potential, 5=off DXLL, 6=off LCLO | |
| MI | 6 | StatusCompressor2 | Compressor 2 status | Read | 1=Available, 2=off SAT ok, 3=off checking SAT, 4=off Econ Potential, 5=off DXLL, 6=off LCLO | |
| MOmin | 1 | OccupancyCommand | Occupancy (fan) command | Command | 1=Enabled, 2=Disabled, 3=Relinquished | |
| MO | 2 | PurgeCommand | Purge request (when PurgeOperationEn is on) | Command | 1=Enabled, 2=Disabled, 3=Relinquished | |
| MOmin | 3 | W1Command | Heating command | Command | 1=Enabled, 2=Disabled, 3=Relinquished | |
| MOmin | 4 | Y1Command | Stage 1 cooling command | Command | 1=Enabled, 2=Disabled, 3=Relinquished | |
| MOmin | 5 | Y2Command | Stage 2 cooling command | Command | 1=Enabled, 2=Disabled, 3=Relinquished |
No points match these filters.
Object ID lookup: Belimo ZIP Economizer point IDs by name
AI1RelPosDmpFbAI2SATAI3OATAI4OAHAI5OAEAI6RATAI7RAHAI8RAEAI9CO2ConcentrationAI10SpDmpPosAI11RunTimeCompressor1AI12RunTimeCompressor2AI13RunTimeEconAI14RunTimeMechanicalAI15RunTimeDCVAI16RunTimeIntegratedAI17RunTimeVentilationAI18RunTimeHeatingAI19RunTimeUnoccupiedAI20RunTimeFreezeProtectionAI21DeviceProductionDateAO1CO2NetworkAO2OAHNetworkAO3OATNetworkAO4RAHNetworkAO5RATNetworkAO6RemoteDmpOverridePosAV1SpCO2PPMAV2SpFreeCoolSATAV3VentMinAV4LowSpeedVentMinAV5DCVMinAV6LowSpeedDCVMinAV7ExhFanOnAV8LowSpeedExhFanOnAV9PurgeDmpPosAV10DrybulbHighLimitAV11EnthHighLimitAV12DiffEnthHighLimitAV13DiffDrybulbHighLimitAV14EnthTempHighLimitAV15DiffEnthTempHighLimitAV16LowOATCompLockoutLimitAV17ZIPCodeAV18BusWatchdogBI1AlarmStateBI2GBI3Y1BI4Y2BI5W1BI6Compressor1StateBI7Compressor2StateBI8ExhFanStateBI9SATLowLimStateBI10LowOATCompLockoutStateBI11PurgeStateBI12FanSpeedStateBV1PurgeOperationEnBV2SatY2LimitEnBV3RemoteDmpOverrideEnMI1OperationModeMI2CurrentAlarmMI3CompressorQuantityMI4ClimateZoneMI5StatusCompressor1MI6StatusCompressor2MO1OccupancyCommandMO2PurgeCommandMO3W1CommandMO4Y1CommandMO5Y2Command
Integration notes
- Many objects need optional parts: the Energy Module (ECON-ZIP-EM) for DCV, exhaust fan, 2-speed fan, purge and remote override; humidity sensors for the enthalpy objects.
- Network sensor AOs (AO 1-5) default to 8888, meaning no value.
- Writing AO 6 RemoteDmpOverridePos disables free cooling, ventilation, DCV and purge.
- High limits marked as climate-zone dependent default from the ZIP code in AV 17.
- MI 4 lists 36 zones in the definition table although the value range is printed as 1-34.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM)
How many BACnet points does the Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM) have?
This list has 71 BACnet objects: 21 analog inputs, 6 analog outputs, 18 analog values, 12 binary inputs, 3 binary values, 6 multi-state inputs, 5 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM) BACnet points are writable?
32 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM) BACnet documentation?
Belimo does not publish it on its own website. This list comes from ZIP Economizer Installation and Operation Manual, BACnet Object Descriptions, revision Tech.Doc 03/21, a copy hosted by ZOT Supply at https://www.zotsupply.com/content/PDFs/Belimo/Economizer/belimo_zip-economizer_operations-manual_en-us.pdf. Ask Belimo or its representative for the current revision.
What are the minimum BACnet points to integrate the Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM)?
Start with MO 1 OccupancyCommand (Occupancy (fan): 1 enabled, 2 disabled); MO 4 Y1Command (Stage 1 cooling call); MO 5 Y2Command (Stage 2 cooling call); MO 3 W1Command (Heating call); AV 2 SpFreeCoolSAT (Free cooling supply air setpoint); MI 1 OperationMode (Operating mode (free cooling, DCV, etc.)); AI 1 RelPosDmpFb (Damper position feedback, %); AI 2 SAT (Supply air temperature); AI 3 OAT (Outdoor air temperature); MI 2 CurrentAlarm (Most recent active alarm).
How do I enable BMS control of the Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM)?
Set Com Interface to BACnet Active (default is MP Active); the ECON-ZIP-COM module is required.
Does the Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM) need a BACnet heartbeat or have a communication timeout?
AV 18 BusWatchdog sets a bus timeout of 0-3600 s (0 = off, the default). When it trips, the commandable objects fall back to their relinquish defaults.
Can the BMS supply sensor values to the Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM)?
AO 1-5 accept CO2, outdoor and return humidity and temperature from the network; they read 8888 (no value) until written.
How do I check these points on the real ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Belimo BACnet points lists
- Pressure-independent control valve
Belimo 2-way EPIV V4
Belimo 2-way electronic pressure-independent valves (EPIV) version 4.2, DN 15 to 50, BACnet models EP..R2+(K)BAC.
Also known as: EPIV, EP..R2+BAC, EP..R2+KBAC, Electronic Pressure Independent Valve, 2-way EPIV DN 15-50 - Ultrasonic liquid flow sensor
Belimo 22PF Flow Sensor
Belimo 22PF-.. ultrasonic flow sensors for water and glycol pipes, interface version 4.3.0.
Also known as: 22PF, 22PF-.., Belimo ultrasonic flow sensor, Flow Sensor 22PF - 6-way pressure-independent control valve
Belimo 6-way EPIV
Belimo 6-way EPIV (EP..R-R6+BAC) used to switch and control a single coil between heating and cooling sequences.
Also known as: EP..R-R6+BAC, 6-way EPIV, 6-way characterised control valve, Belimo 6-way valve - 6-way pressure-independent zone valve
Belimo 6-way PI zone valve (C6..QP..+BAC)
Belimo 6-way pressure-independent zone valves C615QP-B/D/F+BAC and C620QPT-G+BAC, application 6-Way-PIQCV V1.0, on BACnet MS/TP.
Also known as: C6..QP(T)-..+BAC, C615QP-B+BAC, C615QP-D+BAC, C615QP-F+BAC, C620QPT-G+BAC, 6-Way-PIQCV, 6-way PI zone valve, Belimo 6-way PIQCV - Damper and valve actuator
Belimo Air/Water Actuators (BACnet MS/TP)
Belimo general-purpose damper and valve actuators with the BACnet MS/TP interface (rotary, linear and fail-safe types).
Also known as: Belimo air/water actuator, Belimo AirWater BACnet, ..M(C)24A, ..R24A, ..V(K)24A, ..F24A, ..RF24A - Fire damper actuator interface
Belimo BKN230-24-MOD fire damper communication and power unit
Belimo BKN230-24-MOD unit that powers and networks one motorised fire damper actuator (BF24..-ST, BFN24..-ST, BFL24..-ST).
Also known as: BKN230-24-MOD, BKN230-24-MOD-BAC, BKN230, Belimo BKN230 BACnet, Schako BKN230, 71589-00002 - Zone valve actuator
Belimo CQ24A-BAC CQ zone rotary actuator
Belimo CQ24A-BAC rotary actuator for CQ zone valves, BACnet MS/TP application version 01.05.0001.
Also known as: CQ24A-BAC, CQ Zone Rotary Actuator, Belimo CQ BACnet, ZoneTight CQ actuator - Duct / outdoor sensors (temperature, humidity, CO2, VOC, differential pressure)
Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet
Belimo BACnet MS/TP sensors: 22DTH duct temperature/humidity, 22UTH outdoor temperature/humidity, 22DTM duct CO2/VOC and 22ADP differential pressure/airflow sensors.
Also known as: 22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.., 22DTH-16M, 22DTH-56M, 22UTH-160X, 22UTH-560X, 22DTM-16, 22DTM-56, 22ADP-164, 22ADP-164L, 22ADP-56Q, 22ADP-56QB, 22ADP-564L, 22ADP-566L - Pressure-independent control valve with energy meter
Belimo Energy Valve V3
Belimo Energy Valve generation 3 (EV..R+(K)BAC, EV..R3+BAC, EV..F+(K)BAC), the installed base before Energy Valve V4.
Also known as: Energy Valve, EV..R+BAC, EV..R+KBAC, EV..R3+BAC, EV..F+BAC, EV..F+KBAC, Belimo Energy Valve 3 - Pressure-independent control valve with energy meter
Belimo Energy Valve V4
Belimo Energy Valve version 4, DN 15 to 50, BACnet models EV..R2+(K)BAC, EV..R2+MID and EV..R3+BAC.
Also known as: Energy Valve, EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Belimo Energy Valve 4 - Fire and smoke damper actuator test module
Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module
Belimo FSKN120-BAC and FSKN24-BAC remote test modules for spring-return fire and combination fire/smoke damper actuators (FSTF, FSLF, FSNF, FSAFB, FSAF*A) in containment applications.
Also known as: FSKN120-BAC, FSKN24-BAC, FSKN, Belimo FSKN BACnet - Gas detection sensor / monitor
Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others)
Belimo 22G..-5A and 22G..-5B wall gas monitors (CO, NO2, CO2, NH3, refrigerant and other gases) with CAN bus and BACnet MS/TP.
Also known as: 22G, 22G02-5A, 22G02-5B, 22G14-5A, 22G14-5B, 22G0214-5A, 22G0214-5B, Belimo gas monitor BACnet, Belimo CO monitor - Valve actuator (Ethernet, IoT)
Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)
Belimo IoT product range valve actuators VLM/VLR, VNM/VNR, VSM/VSR and VGM/VGR 24A-LP1 with Ethernet and BACnet IP.
Also known as: VLM24A-LP1, VLR24A-LP1, VNM24A-LP1, VNR24A-LP1, VSM24A-LP1, VSR24A-LP1, VGM24A-LP1, VGR24A-LP1, Belimo IoT Product Range - Butterfly valve actuator
Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo JR rotary actuators for butterfly valves in the BACnet MS/TP version (JR..A-BAC-..).
Also known as: JR actuator, JR..A-BAC-.., Belimo JR BACnet, JR/QR - Butterfly valve actuator
Belimo PR..-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo PR rotary actuators for butterfly valves in the BACnet MS/TP version (PR..-BAC-..).
Also known as: PR..-BAC-.., Belimo PR actuator, PR BACnet - Room sensor / operating unit
Belimo Room Operating Unit 22RT-5U00
Belimo 22RT...-5U00... room operating units with virtual or ePaper touch display, measuring temperature, humidity and CO2.
Also known as: 22RT, 22RT…-5U00…, Room Operating Unit, ROU, 22RTM-5U00, Belimo room sensor BACnet - Thermal (BTU) energy meter
Belimo Thermal Energy Meter V4
Belimo Thermal Energy Meters version 4, DN 15 to 50 (22PE..-1U.., including MID-certified 22PEM models).
Also known as: TEM, Thermal Energy Meter, 22PE-1U, 22PEM-1UC, 22PE…-1U.., Belimo energy meter - VAV compact controller (actuator with flow sensor)
Belimo VAV-Compact
Belimo VAV-Compact volumetric flow controllers with the BACnet/Modbus interface (..MV-D3-MOD and ..HV24A-MOD).
Also known as: VAV-Compact MOD, ..MV-D3-MOD, ..HV24A-MOD, LMV-D3-MOD, NMV-D3-MOD, SMV-D3-MOD, LHV24A-MOD - VAV / CAV / pressure controller
Belimo VAV-Universal VRU
Belimo VAV-Universal controllers VRU-D3-BAC, VRU-M1-BAC and VRU-M1R-BAC used for VAV/CAV airflow, duct pressure and room pressure control.
Also known as: VAV-Universal, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-..-BAC - VAV zone controller / actuator
Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)
Belimo ZoneEase VAV actuators LMV-BAC-.. and NMV-BAC-.. with the built-in zone control applications, application software ZoneEase 1.7.
Also known as: ZoneEase VAV, LMV-BAC-.., NMV-BAC-.., Belimo ZoneEase
Source: ZIP Economizer Installation and Operation Manual, BACnet Object Descriptions · rev. Tech.Doc 03/21. Object names, instances and units are reproduced as published; descriptions are our own.