6-way pressure-independent zone valve · BACnet points list

Belimo 6-way PI zone valve (C6..QP..+BAC) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

This 6-way zone valve switches one coil between a heating and a cooling circuit and limits flow in each sequence. A single setpoint AO 1 covers both: 0-33 % runs sequence 1 from Vmax1 down to zero, 67-100 % runs sequence 2 from zero up to Vmax2, and the middle is a dead band. It reports position, calculated flow, the active sequence and an actuator status. It is a different product from the 6-way EPIV.

This page lists 20 BACnet objects for the Belimo 6-way PI zone valve (C6..QP..+BAC) — 6 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Belimo’s documentation hosted by Tameson, not by Belimo itself, so treat it as unofficial.

Manufacturer
Belimo
Model
6-way PI zone valve (C6..QP..+BAC)
Equipment
6-way pressure-independent zone valve
Equipment type
Valves & actuators
BACnet objects
20 (6 writable)
Transport
BACnet MS/TP
Firmware
6-Way-PIQCV V1.0
Default device instance
1
Also known as
C6..QP(T)-..+BAC, C615QP-B+BAC, C615QP-D+BAC, C615QP-F+BAC, C620QPT-G+BAC, 6-Way-PIQCV, 6-way PI zone valve, Belimo 6-way PIQCV
Source document
BACnet PICS 6-way PI zone valve (C6..QP..-..+BAC) · rev. 2023-05 (unofficial copy, hosted by Tameson)
Download CSV 20 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.

BMS integration notes: Belimo 6-way PI zone valve (C6..QP..+BAC)

Integration in brief

Write MV 122 SpSource = Bus, set Vmax1 and Vmax2 once, then command AO 1 using the split range (0-33 % sequence 1, 67-100 % sequence 2). Read MI 1 for the active sequence, AI 19 for flow and BI 101 for alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1SpRelSingle setpoint for both heating/cooling sequencesCommand
MV 122SpSourceMust be Bus for AO 1 to take effectWrite
MI 1ActSequenceShows which sequence is activeRead
AI 19AbsFlow_UnitSelCalculated flowRead
AI 1RelPosValve position feedbackRead
BI 101SummaryStatusOverall OK / not OK alarmRead

Enable & remote start

Write MV 122 SpSource = 2 (Bus). With Analog (the default) the valve follows the 0-10 V signal on wire 3.

Network setup

Watch out for

Belimo 6-way PI zone valve (C6..QP..+BAC) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

20 of 20 shown
Type
Binary
Access
Show
Belimo 6-way PI zone valve (C6..QP..+BAC) BACnet Points List
DescriptionStates
AImin1RelPosCombined relative position (0-33 % seq 1, 67-100 % seq 2)%Read
AI5SpAnalog_VAnalog setpoint when SpSource is AnalogVRead
AI10RelFlowFlow relative to the active Vmax%Read
AI13AbsFlow_gpmCalculated flowgpmRead
AI15AbsFlow_lhCalculated flowl/hRead
AImin19AbsFlow_UnitSelCalculated flow in the unit set by MV 121Read
AI109SpAbsFlow_UnitSelFlow setpoint in the unit set by MV 121Read
AOmin1SpRelSetpoint: 0-33 % seq 1 Vmax1 to 0, 67-100 % seq 2 0 to Vmax2%Command
AV99Vmax1Maximum flow limit, sequence 1 (% of Vnom)%Write
AV100Vmax2Maximum flow limit, sequence 2 (% of Vnom)%Write
AV102Vnom_gpmNominal flowgpmRead
AV115Vnom_lhNominal flowl/hRead
AV119Vnom_UnitSelNominal flow in the unit set by MV 121Read
BImin101SummaryStatusSummary of MI 106ReadInactive=OK, Active=Not OK
MImin1ActSequenceActive sequenceRead1=Sequence 1, 2=Sequence 2, 3=Dead Band
MI106StatusActuatorActuator status (6-way and 2-way valve)Read1=OK, 2=Actuator cannot move, 3=Gear disengaged, 4=No communication to 2-way valve
MO1OverrideOverride the setpoint with fixed positionsCommand1=None, 2=Sequence 1 open, 3=Sequence 2 open, 4=Close, 5=Sequence 1 Vmax, 6=Sequence 2 Vmax
MV100ControlModeControl modeRead1=-, 2=FlowCtrl
MV121UnitSelFlowFlow unit for AI 19 and AI 109Write1=m3/s, 2=m3/h, 3=l/s, 4=l/min, 5=l/h, 6=gpm, 7=cfm
MVmin122SpSourceSetpoint sourceWrite1=Analog, 2=Bus
Object ID lookup: Belimo 6-way PI zone valve point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 6-way PI zone valve (C6..QP..+BAC) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo 6-way PI zone valve (C6..QP..+BAC)

How many BACnet points does the Belimo 6-way PI zone valve (C6..QP..+BAC) have?

This list has 20 BACnet objects: 7 analog inputs, 1 analog output, 5 analog values, 1 binary input, 2 multi-state inputs, 1 multi-state output, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo 6-way PI zone valve (C6..QP..+BAC) BACnet points are writable?

6 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo 6-way PI zone valve (C6..QP..+BAC) BACnet documentation?

Belimo does not publish it on its own website. This list comes from BACnet PICS 6-way PI zone valve (C6..QP..-..+BAC), revision 2023-05, a copy hosted by Tameson at https://storage.tameson.com/asset/Products/Manuals/EN/v2w7s_md99_belimo_bacnet_interface-description_6way-pi-zone-valve_en.pdf. Ask Belimo or its representative for the current revision.

What are the minimum BACnet points to integrate the Belimo 6-way PI zone valve (C6..QP..+BAC)?

Start with AO 1 SpRel (Single setpoint for both heating/cooling sequences); MV 122 SpSource (Must be Bus for AO 1 to take effect); MI 1 ActSequence (Shows which sequence is active); AI 19 AbsFlow_UnitSel (Calculated flow); AI 1 RelPos (Valve position feedback); BI 101 SummaryStatus (Overall OK / not OK alarm).

How do I enable BMS control of the Belimo 6-way PI zone valve (C6..QP..+BAC)?

Write MV 122 SpSource = 2 (Bus). With Analog (the default) the valve follows the 0-10 V signal on wire 3.

How do I check these points on the real 6-way PI zone valve (C6..QP..+BAC)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: BACnet PICS 6-way PI zone valve (C6..QP..-..+BAC) · rev. 2023-05. Object names, instances and units are reproduced as published; descriptions are our own.