Damper and valve actuator · BACnet points list

Belimo Air/Water Actuators (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

Belimo's air/water actuators with a communication interface can run on BACnet MS/TP. The BMS writes a % setpoint to AO 1, scaled between Min and Max, and reads position and status; one extra sensor input (active, passive temperature or switch) can be read over the bus. The setpoint can also come from a 0-10 V signal, chosen with SpSource (MV 122).

This page lists 20 BACnet objects for the Belimo Air/Water Actuators (BACnet MS/TP) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
Air/Water Actuators (BACnet MS/TP)
Equipment
Damper and valve actuator
Equipment type
Valves & actuators
BACnet objects
20 (10 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
1
Also known as
Belimo air/water actuator, Belimo AirWater BACnet, ..M(C)24A, ..R24A, ..V(K)24A, ..F24A, ..RF24A
Source document
BACnet interface description, Air/water actuators · V3.08 · rev. 2026-05
Download CSV 20 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.

BMS integration notes: Belimo Air/Water Actuators (BACnet MS/TP)

Integration in brief

Set MV 122 SpSource to Bus and command AO 1 SpRel. Read AI 1 position and BI 101 summary status. If a bus watchdog is set in AV 130, keep writing AO 1 (or MO 1) within that time.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1SpRelActuator setpoint, % (between Min and Max)Command
MV 122SpSourceMust be Bus for AO 1 to take effectWrite
AI 1RelPosPosition feedbackRead
BI 101SummaryStatusOverall OK / not OK alarmRead

Enable & remote start

MV 122 SpSource selects the setpoint: Analog (1, default) follows the 0-10 V signal on wire 3; Bus (2) uses AO 1. MO 1 Override can force Open, Close, Min, Mid, Max or fast open/close.

Heartbeat & communication loss

AV 130 Bus Watchdog (0-3600 s, default 0 = off). When set, each write to AO 1 or MO 1 restarts the timer; on timeout the AO 1 priority array is cleared, the relinquish default applies, and MI 110 shows Bus Watchdog triggered. With SpSource = Analog only MO 1 writes are tracked.

Network setup

Watch out for

Belimo Air/Water Actuators (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

20 of 20 shown
Type
Binary
Access
Show
Belimo Air/Water Actuators (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1RelPosRelative position%Read
AI2AbsPosAbsolute position (degrees rotary, mm linear)Read
AI6SpAnalogAnalog setpoint when SpSource is Analog%Read
AI20Sens1AnalogSensor 1 value when Sens1Type is Active (V, ohm, °C or °F)Read
AOmin1SpRelBus setpoint, scaled between Min and Max%Command
AV97MinMinimum setpoint (at most Max - 30 %)%Write
AV98MaxMaximum setpoint (at least Min + 30 %)%Write
AV130Bus WatchdogBus watchdog timeout, 0 = offsWrite
AV131Fail-Safe Bridging TimeBridging time on power failure (fail-safe models)sWrite
AV132Fail-Safe PositionFail-safe position (fail-safe models)%Write
BI20Sens1SwitchSensor 1 as switch inputReadInactive, Active
BI99BusTermination120 ohm bus termination enabledReadInactive, Active
BImin101SummaryStatusSummary of MI 106 and MI 110ReadInactive=OK, Active=Not OK
MI100InternalActivityInternal test or adaption runningRead1=None, 2=Test, 3=Adaption
MI106StatusActuatorActuator statusRead1=OK, 2=Actuator cannot move, 3=Gear train disengaged, 4=Mechanical travel increased
MI110StatusDeviceDevice status, incl. bus watchdogRead1=OK, 2=Bus Watchdog triggered
MO1OverrideOverride the setpoint with fixed positionsCommand1=None, 2=Open, 3=Close, 4=Min_Vmin, 5=Mid_Vmid, 6=Max_Vmax, 7=Fast open, 8=Fast close
MV120CommandService command: adaption, test or status resetWrite1=None, 2=Adaption, 3=Test, 4=Reset
MVmin122SpSourceSetpoint source: analog 0-10 V or bus AO 1Write1=Analog, 2=Bus
MV220Sens1TypeSensor 1 typeWrite1=None, 2=Active / hybrid, 3=Passive_1K, 4=Passive_20K, 5=Switch, 6=PT1000_C, 7=NI1000_C, 8=NTC10K2_C, 9=PT1000_F, 10=NI1000_F, 11=NTC10K2_F
Object ID lookup: Belimo Air/Water Actuators point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Air/Water Actuators (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo Air/Water Actuators (BACnet MS/TP)

How many BACnet points does the Belimo Air/Water Actuators (BACnet MS/TP) have?

This list has 20 BACnet objects: 4 analog inputs, 1 analog output, 5 analog values, 3 binary inputs, 3 multi-state inputs, 1 multi-state output, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo Air/Water Actuators (BACnet MS/TP) BACnet points are writable?

10 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo Air/Water Actuators (BACnet MS/TP) BACnet documentation?

The source is BACnet interface description, Air/water actuators (V3.08), revision 2026-05, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_AirWater_V3_8_en-gb.pdf.

What are the minimum BACnet points to integrate the Belimo Air/Water Actuators (BACnet MS/TP)?

Start with AO 1 SpRel (Actuator setpoint, % (between Min and Max)); MV 122 SpSource (Must be Bus for AO 1 to take effect); AI 1 RelPos (Position feedback); BI 101 SummaryStatus (Overall OK / not OK alarm).

How do I enable BMS control of the Belimo Air/Water Actuators (BACnet MS/TP)?

MV 122 SpSource selects the setpoint: Analog (1, default) follows the 0-10 V signal on wire 3; Bus (2) uses AO 1. MO 1 Override can force Open, Close, Min, Mid, Max or fast open/close.

Does the Belimo Air/Water Actuators (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

AV 130 Bus Watchdog (0-3600 s, default 0 = off). When set, each write to AO 1 or MO 1 restarts the timer; on timeout the AO 1 priority array is cleared, the relinquish default applies, and MI 110 shows Bus Watchdog triggered. With SpSource = Analog only MO 1 writes are tracked.

How do I check these points on the real Air/Water Actuators (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: BACnet interface description, Air/water actuators · V3.08 · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.