Pressure-independent control valve · BACnet points list

Belimo 2-way EPIV V4 BACnet points list

Updated 28 October 2026

Short answer

The 2-way EPIV is a characterized control valve with a built-in ultrasonic flow sensor that holds flow regardless of system pressure. Over BACnet it takes a relative setpoint on AO 1 that means either position or flow, and reports position, flow, accumulated volume, flow-body temperature, glycol content and status. The document lists BACnet MS/TP and BACnet IP settings.

This page lists 36 BACnet objects for the Belimo 2-way EPIV V4 — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
2-way EPIV V4
Equipment
Pressure-independent control valve
Equipment type
Valves & actuators
BACnet objects
36 (15 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Application EPIV 4.2
Default device instance
1
Also known as
EPIV, EP..R2+BAC, EP..R2+KBAC, Electronic Pressure Independent Valve, 2-way EPIV DN 15-50
Source document
BACnet Interface Description, 2-way EPIV, DN 15…50 (Version 4.2) · rev. 2025-09 / V4.2
Download CSV 36 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Belimo 2-way EPIV V4

Integration in brief

Write MV 122 SpSource to Bus, pick position or flow control in MV 100, set the flow limits, then command AO 1 SpRel. Monitor AV 19 flow and AI 1 position, and use the MV 103-106 status objects and AV 140 ErrorState for alarms. If a bus fail action is set, keep rewriting AO 1 or MV 1 within the watchdog time.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1SpRelPosition or flow setpoint from the BMSCommand
MV 122SpSourceMust be Bus for AO 1 to take effectWrite
AV 19AbsFlow_UnitSelMeasured flowRead
AI 1RelPosValve position feedbackRead
AV 140ErrorStateBit-coded fault and warning flagsRead

Enable & remote start

Write MV 122 SpSource = 2 (Bus); otherwise the valve follows the 0.5-10 V signal on wire 3 and AO 1 is overridden.

Heartbeat & communication loss

AV 130 BusWatchdog sets 5-3600 s (default 120 s). If neither AO 1 nor MV 1 is rewritten within that time, the valve moves to the MV 130 BusFailAction (default None; options Open, Close, Max, Min, Stop) and sets bit 15 in AV 140.

Network setup

Watch out for

Belimo 2-way EPIV V4 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

36 of 36 shown
Type
Multi-stateOther
Access
Show
Belimo 2-way EPIV V4 BACnet Points List
DescriptionStates
AOmin1SpRelRelative setpoint: position or flow%Command
AI6SpAnalogAnalog setpoint when setpoint source is analog%Read
AImin1RelPosRelative valve position%Read
AV2AbsPosAbsolute valve position°Read
MVmin122SpSourceSetpoint source: analog wire 3 or bus AO 1Write1=Analog, 2=Bus
MV100ControlModeHow the setpoint is interpretedWrite1=Position Control, 2=Flow Control
MV1OverrideOverride control of the setpointWrite1=None, 2=Open valve, 3=Close valve, 4=Minimum, 5=–, 6=Maximum, 7=Nominal, 8=–, 9=–, 10=–, 11=Motor Stop
MV120CommandStart service/test function; returns to NoneWrite1=None, 2=–, 3=Synchronization
MV130BusFailActionAction when bus watchdog expiresWrite1=None, 2=Open, 3=Close, 4=Max, 5=Min, 6=–, 7=Stop
AV130BusWatchdogBus watchdog timeout (5-3600, default 120)sWrite
BV99BusTermination120 Ω bus termination enabledRead0=Disabled, 1=Enabled
MV106StatusActuatorActuator statusRead1=OK, 2=Actuator cannot move, 3=Gear train disengaged, 4=No communication to actuator
AV17SpAbsFlow_UnitSelActive absolute flow setpointm³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Read
AV10RelFlowFlow relative to maximum flow limit%Read
AVmin19AbsFlow_UnitSelMeasured absolute flowm³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Read
AV90VminMinimum flow limit%Write
AV93Vmin_UnitSelMinimum flow limitm³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Write
AV94VmaxMaximum flow limit (25-100% of nominal)%Write
AV97Vmax_UnitSelMaximum flow limitm³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Write
AV100Vnom_UnitSelNominal flow of the valvem³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Read
MV123UnitSelFlowEngineering unit for flow objectsWrite1=m³/s, 2=m³/h, 3=l/s, 4=l/min, 5=l/h, 6=gpm, 7=cfm
AV52Volume_UnitSelAccumulated volumem³, l, gal or cf (MV 126)Read
PIV50VolumePIV_UnitSelAccumulated volume as integerMV 126 unitRead
MV126UnitSelVolumeEngineering unit for volume objectsWrite1=m³, 2=Litre, 3=Gallon, 4=Cubic foot
MV103StatusSensorFlow and temperature sensor statusRead1=OK, 2=Flow measurement error, 3=Flowbody temperature not OK, 4=–, 5=Communication to flow sensor interrupted
MV104StatusFlowFlow statusRead1=OK, 2=Actual flow exceeds nominal flow, 3=Flow with closed valve, 4=Flow setpoint cannot be reached, 5=Reverse flow
MV105StatusMediaMedium statusRead1=OK, 2=Glycol detected, 3=Freeze warning
AV60GlycolConcentrationGlycol concentration%Read
PIV201MeterSerialNo_Part1Flow meter serial number, first digitsRead
PIV202MeterSerialNo_Part2Flow meter serial number, last digitsRead
AI23T_UnitSelFlow body temperature°C, K or °F (MV 127)Read
AI20Sens1Active_VoltSensor 1 input as voltage (active sensor)VRead
BI20Sens1SwitchSensor 1 as switch inputRead0=Inactive, 1=Active
MV127UnitSelTemperatureEngineering unit for temperatureWrite1=°C, 2=K, 3=°F
MV220Sens1TypeSensor 1 input type (bus setpoint only)Write1=None, 2=Active volt, 3=–, 4=–, 5=Switch
AVmin140ErrorStateBit-coded error and warning flagsReadBit 0=No communication to actuator, 1=Gear train disengaged, 2=Actuator cannot move, 3=Reverse flow, 4=Flow setpoint not reached, 5=Flow with closed valve, 6=Flow actual exceeds flow nominal, 7=Flow measurement error, 9=Flowbody temperature error, 10=Communication to sensor interrupted, 11=Freeze warning, 12=Glycol detected, 15=Bus watchdog triggered

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 2-way EPIV V4 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo 2-way EPIV V4

How many BACnet points does the Belimo 2-way EPIV V4 have?

This list has 36 BACnet objects: 4 analog inputs, 1 analog output, 13 analog values, 1 binary input, 1 binary value, 13 multi-state values, 3 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo 2-way EPIV V4 BACnet points are writable?

15 of the 36 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo 2-way EPIV V4 BACnet documentation?

The source is BACnet Interface Description, 2-way EPIV, DN 15…50 (Version 4.2), revision 2025-09 / V4.2, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_2way-EPIV_V4_2_en-gb.pdf.

What are the minimum BACnet points to integrate the Belimo 2-way EPIV V4?

Start with AO 1 SpRel (Position or flow setpoint from the BMS); MV 122 SpSource (Must be Bus for AO 1 to take effect); AV 19 AbsFlow_UnitSel (Measured flow); AI 1 RelPos (Valve position feedback); AV 140 ErrorState (Bit-coded fault and warning flags).

How do I enable BMS control of the Belimo 2-way EPIV V4?

Write MV 122 SpSource = 2 (Bus); otherwise the valve follows the 0.5-10 V signal on wire 3 and AO 1 is overridden.

Does the Belimo 2-way EPIV V4 need a BACnet heartbeat or have a communication timeout?

AV 130 BusWatchdog sets 5-3600 s (default 120 s). If neither AO 1 nor MV 1 is rewritten within that time, the valve moves to the MV 130 BusFailAction (default None; options Open, Close, Max, Min, Stop) and sets bit 15 in AV 140.

How do I check these points on the real 2-way EPIV V4?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: BACnet Interface Description, 2-way EPIV, DN 15…50 (Version 4.2) · rev. 2025-09 / V4.2. Object names, instances and units are reproduced as published; descriptions are our own.