Duct / outdoor sensors (temperature, humidity, CO2, VOC, differential pressure) · BACnet points list

Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet BACnet points list

Updated 28 October 2026

Short answer

This family of Belimo sensors shares one BACnet MS/TP object map. AI 0-11 carry the measured values (temperature, humidity, derived absolute humidity, enthalpy and dew point, CO2, VOC, differential pressure and fan airflow), and AV objects hold offsets, output scaling limits, channel assignment, fan k-factors, device settings and the optional LCD. Only the values the particular model measures are in service; the rest show Out of Service.

This page lists 81 BACnet objects for the Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet — 69 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet
Equipment
Duct / outdoor sensors (temperature, humidity, CO2, VOC, differential pressure)
Equipment type
Thermostats, sensors & meters
BACnet objects
81 (69 writable)
Transport
BACnet MS/TP
Firmware
2.3
Also known as
22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.., 22DTH-16M, 22DTH-56M, 22UTH-160X, 22UTH-560X, 22DTM-16, 22DTM-56, 22ADP-164, 22ADP-164L, 22ADP-56Q, 22ADP-56QB, 22ADP-564L, 22ADP-566L
Source document
BACnet Interface Description, Belimo Sensors 22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.. · rev. 2024-03 / V4.2
Download CSV 81 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet

Integration in brief

Set the MS/TP MAC address and baud rate on the RS-485 module's DIP switches, then read the AI objects the model supports. Offsets, limits and the SI/Imperial choice are configuration AVs to set once. For 22ADP fan airflow, set the fan manufacturer and k-factor first.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 0Value temperatureTemperature (22DTH / 22UTH / 22DTM)Read
AI 1Value relative humidityRelative humidity (22DTH / 22UTH)Read
AI 5Value CO2CO2 (22DTM)Read
AI 8Differential pressure 1Differential pressure (22ADP)Read
AI 9Volumetric flow 1Fan airflow (22ADP)Read
AI 4Value dew pointCalculated dew point (22DTH / 22UTH)Read

Network setup

Watch out for

Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

81 of 81 shown
Type
Access
Show
Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet BACnet Points List
DescriptionStates
AImin0Value temperatureMeasured temperature°C / °FRead
AImin1Value relative humidityMeasured relative humidity%RHRead
AI2Value absolute humidityCalculated absolute humidityg/m³ / gr/ft³Read
AI3Value enthalpyCalculated enthalpykJ/kg / BTU/lbRead
AImin4Value dew pointCalculated dew point°C / °FRead
AImin5Value CO2Measured CO2ppmRead
AI6Value VOCMeasured VOC%Read
AI7Value CO2 VOC MixCombined CO2/VOC air quality value%Read
AImin8Differential pressure 1Differential pressure, sensor S1 (22ADP)Pa / inWCRead
AImin9Volumetric flow 1Fan airflow from dp S1 and k-factor (22ADP)m³/h or m³/s / cfmRead
AI10Differential pressure 2Differential pressure, sensor S2 (dual ADP only)Pa / inWCRead
AI11Volumetric flow 2Fan airflow from dp S2 (dual ADP only)m³/h or m³/s / cfmRead
AV0Offset temperatureTemperature offset, -3 to +3 °C°C / °FWrite
AV1Offset relative humidityHumidity offset, -5 to +5 %RH%RHWrite
AV2Offset CO2CO2 offset, -150 to +150 ppmppmWrite
AV3Offset VOCVOC offset, -15 to +15 %%Write
AV4Offset differential pressure 1dp S1 offset, -50 to +50 Pa (inWC in 1/1000)Pa / inWCWrite
AV5Offset differential pressure 2dp S2 offset (dual ADP only)Pa / inWCWrite
AV6Lower limit temperatureLower limit / 0 V scaling for temperature°C / °FWrite
AV7Upper limit temperatureUpper limit / 10 V scaling for temperature°C / °FWrite
AV8Lower limit relative humidityLower limit / 0 V scaling for relative humidity%RHWrite
AV9Upper limit relative humidityUpper limit / 10 V scaling for relative humidity%RHWrite
AV10Lower limit absolute humidityLower limit / 0 V scaling for absolute humidityg/m³ / gr/ft³Write
AV11Upper limit absolute humidityUpper limit / 10 V scaling for absolute humidityg/m³ / gr/ft³Write
AV12Lower limit enthalpyLower limit / 0 V scaling for enthalpykJ/kg / BTU/lbWrite
AV13Upper limit enthalpyUpper limit / 10 V scaling for enthalpykJ/kg / BTU/lbWrite
AV14Lower limit dew pointLower limit / 0 V scaling for dew point°C / °FWrite
AV15Upper limit dew pointUpper limit / 10 V scaling for dew point°C / °FWrite
AV16Lower limit CO2Lower limit / 0 V scaling for CO2ppmWrite
AV17Upper limit CO2Upper limit / 10 V scaling for CO2ppmWrite
AV18Lower limit VOCLower limit / 0 V scaling for VOC%Write
AV19Upper limit VOCUpper limit / 10 V scaling for VOC%Write
AV20Lower limit CO2 VOC MixLower limit / 0 V scaling for CO2 VOC Mix%Write
AV21Upper limit CO2 VOC MixUpper limit / 10 V scaling for CO2 VOC Mix%Write
AV22Lower limit volumetric flow 1Lower limit for airflow 1 (printed as AI[22])m³/h or m³/s / cfmWrite
AV23Upper limit volumetric flow 1Upper limit for airflow 1 (printed as AI[23])m³/h or m³/s / cfmWrite
AV24Lower limit volumetric flow 2Lower limit for airflow 2, dual ADP (printed as AI[24])m³/h or m³/s / cfmWrite
AV25Upper limit volumetric flow 2Upper limit for airflow 2, dual ADP (printed as AI[25])m³/h or m³/s / cfmWrite
AV26Channel temperatureOutput/LCD channel for temperature (0=unused, 1-4)Write
AV27Channel relative humidityOutput/LCD channel for relative humidity (0=unused, 1-4)Write
AV28Channel absolute humidityOutput/LCD channel for absolute humidity (0=unused, 1-4)Write
AV29Channel enthalpyOutput/LCD channel for enthalpy (0=unused, 1-4)Write
AV30Channel dew pointOutput/LCD channel for dew point (0=unused, 1-4)Write
AV31Channel CO2Output/LCD channel for CO2 (0=unused, 1-4)Write
AV32Channel VOCOutput/LCD channel for VOC (0=unused, 1-4)Write
AV33Channel CO2 VOC MixOutput/LCD channel for CO2 VOC Mix (0=unused, 1-4)Write
AV34Channel differential pressure 1Output/LCD channel for differential pressure 1 (0=unused, 1-4)Write
AV35Channel volumetric flow 1Output/LCD channel for volumetric flow 1 (0=unused, 1-4)Write
AV36Channel differential pressure 2Output/LCD channel for differential pressure 2 (0=unused, 1-4)Write
AV37Channel volumetric flow 2Output/LCD channel for volumetric flow 2 (0=unused, 1-4)Write
AV38Selection of the unitary systemSI or Imperial units (22ADP: set by DIP 6)Write1=SI, 2=Imperial
AV39Height above sea levelInstallation altitude, always in metresmWrite
AV40Input k-factor volumetric flow 1Fan k-factor x10 for airflow 1Write
AV41Selection of the fan manufacturer 1Fan maker formula for airflow 1Write0=Rosenberg/Comefri/Gebhart/Nicotra/Ziehl-Abegg, 1=EBM-Papst/AIR-CONCEPTS, 2=Fläkt-Woods
AV42Input k-factor volumetric flow 2Fan k-factor x10 for airflow 2 (dual ADP)Write
AV43Selection of the fan manufacturer 2Fan maker formula for airflow 2 (dual ADP)Write0=Rosenberg/Comefri/Gebhart/Nicotra/Ziehl-Abegg, 1=EBM-Papst/AIR-CONCEPTS, 2=Fläkt-Woods
AV44Response time for volumetric flow 1Airflow 1 response time, 4-30 ssWrite
AV45Response time for volumetric flow 2Airflow 2 response time (dual ADP)sWrite
AV85Zeroing differential pressure 1Start zero calibration of dp S1Write0=No zeroing, 1=Start zeroing
AV86Zeroing differential pressure 2Start zero calibration of dp S2 (dual ADP)Write0=No zeroing, 1=Start zeroing
AV46Offset device IDDevice ID = this offset + MAC addressWrite
AV47Unconfirmed COVEnable unsubscribed COV broadcastsWrite0=Disabled, 1=Enabled
AV48Minimum output voltageMinimum voltage of the 0-10 V outputsVWrite
AV49Operating hoursOperating hours counterhWrite
AV50Maintenance timeMaintenance countdown in hourshWrite
AV52Enable LCDTurn the optional display on/offWrite0=Disabled, 1=Enabled
AV53Brightness LCDDisplay brightness%Write
AV54Rotation LCDDisplay rotationWrite0=0°, 1=90°, 2=180°, 3=270°
AV55Enable LCD traffic light functionColour backlight by valueWrite0=Disabled, 1=Enabled
AV56Enable symbol maintenance on LCDShow maintenance symbol when AV 50 expiresWrite0=Disabled, 1=Enabled
AV57Enable symbol maintenance on LCDSecond maintenance-symbol object, same text as AV 56Write0=Disabled, 1=Enabled
AV58Enable LCD channel 1Show channel 1 on the displayWrite0=Disabled, 1=Enabled
AV59Enable LCD channel 2Show channel 2 on the displayWrite0=Disabled, 1=Enabled
AV60Enable LCD channel 3Show channel 3 on the displayWrite0=Disabled, 1=Enabled
AV61Enable LCD channel 4Show channel 4 on the displayWrite0=Disabled, 1=Enabled
AV62Channel assignment for traffic light functionWhich channel object (AV 26-35) drives the coloursWrite
AV63Traffic light function color range 1Backlight colour for range 1Write0=Off, 1=Green, 2=Yellow, 3=Red, 4=Blue, 5=Magenta, 6=Cyan, 7=White
AV64Traffic light function color range 2Backlight colour for range 2Write0=Off, 1=Green, 2=Yellow, 3=Red, 4=Blue, 5=Magenta, 6=Cyan, 7=White
AV65Traffic light function color range 3Backlight colour for range 3Write0=Off, 1=Green, 2=Yellow, 3=Red, 4=Blue, 5=Magenta, 6=Cyan, 7=White
AV66Setting for threshold range 1 | 2Threshold between colour ranges 1 and 2Write
AV67Setting for threshold range 2 | 3Threshold between colour ranges 2 and 3Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet

How many BACnet points does the Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet have?

This list has 81 BACnet objects: 12 analog inputs, 69 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet BACnet points are writable?

69 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet BACnet documentation?

The source is BACnet Interface Description, Belimo Sensors 22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.., revision 2024-03 / V4.2, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_Sensors_V4_1_en-gb.pdf.

What are the minimum BACnet points to integrate the Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet?

Start with AI 0 Value temperature (Temperature (22DTH / 22UTH / 22DTM)); AI 1 Value relative humidity (Relative humidity (22DTH / 22UTH)); AI 5 Value CO2 (CO2 (22DTM)); AI 8 Differential pressure 1 (Differential pressure (22ADP)); AI 9 Volumetric flow 1 (Fan airflow (22ADP)); AI 4 Value dew point (Calculated dew point (22DTH / 22UTH)).

How do I check these points on the real Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: BACnet Interface Description, Belimo Sensors 22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.. · rev. 2024-03 / V4.2. Object names, instances and units are reproduced as published; descriptions are our own.