Pressure-independent control valve with energy meter · BACnet points list

Belimo Energy Valve V4 BACnet points list

Updated 28 October 2026

Short answer

The Energy Valve V4 is a pressure-independent characterized control valve with an ultrasonic flow sensor and two temperature sensors, so it reports flow, delta T, power and heating/cooling energy. It speaks BACnet MS/TP and BACnet IP (including foreign-device registration). The setpoint on AO 1 means position, flow, power or differential pressure depending on the control mode in MV 100, and the engineering units of most analog objects follow selectable unit objects.

This page lists 68 BACnet objects for the Belimo Energy Valve V4 — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
Energy Valve V4
Equipment
Pressure-independent control valve with energy meter
Equipment type
Valves & actuators
BACnet objects
68 (27 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Application 04.01.0000, firmware 14.10.0002 (interface description V4.2.0)
Default device instance
1
Also known as
Energy Valve, EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Belimo Energy Valve 4
Source document
BACnet Interface Description, Energy Valve DN 15...50 (Version 4) · rev. 2024-09 / V4.2.0
Download CSV 68 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Belimo Energy Valve V4

Integration in brief

Set MV 122 SpSource to Bus, choose the control mode in MV 100 and the flow and power limits, then command AO 1 SpRel from the BMS. Read flow, temperatures, delta T, power and energy for monitoring, and watch MV 99 SummaryStatus and AV 140 ErrorState for faults. If you enable a bus fail action, the BMS must keep rewriting the setpoint inside the watchdog time.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1SpRelSetpoint: position, flow, power or dp per control modeCommand
MV 122SpSourceMust be Bus for AO 1 to take effectWrite
AV 19AbsFlow_UnitSelMeasured flowRead
AV 22DeltaT_UnitSelCoil delta TRead
AV 46HeatingPower_UnitSelHeating power delivered; units set by MV 124Read
AV 45CoolingPower_UnitSelCooling power delivered; units set by MV 124Read
AV 47CoolingEnergy_UnitSelCooling energy meterRead
AV 48HeatingEnergy_UnitSelHeating energy meterRead
MV 99SummaryStatusOverall OK / warning / not OKRead
AV 140ErrorStateBit-coded fault and warning flagsRead

Enable & remote start

Write MV 122 SpSource = 2 (Bus) so the valve follows AO 1 SpRel instead of the 0-10 V signal on wire 3. MV 1 Override can force open, close, min, max, nominal or motor stop.

Heartbeat & communication loss

AV 130 BusWatchdog sets a timeout of 5-3600 s (default 120 s). If no write arrives within that time, the valve runs the action in MV 130 BusFailAction (default None; options Open, Close, Max, Min, Stop) and sets the bus watchdog bit in AV 140. With a fail action set, the BMS must keep rewriting the setpoint.

Network setup

Watch out for

Belimo Energy Valve V4 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

68 of 68 shown
Type
Multi-stateOther
Access
Show
Belimo Energy Valve V4 BACnet Points List
DescriptionStates
AI1RelPosRelative valve position%Read
AI6SpAnalogAnalog setpoint when setpoint source is analog%Read
AI20Sens1Active_VoltSensor 1 input as voltage (active sensor)VRead
AI21Sens1Passive_OhmSensor 1 input as resistance (passive sensor)ΩRead
AI22T1_UnitSelRemote temperature T1°C, K or °F (MV 127)Read
AI23T2_UnitSelFlow body temperature T2°C, K or °F (MV 127)Read
AOmin1SpRelRelative setpoint: position, flow or power%Command
AV2AbsPosAbsolute valve position°Read
AV10RelFlowFlow relative to maximum flow limit%Read
AV17SpAbsFlow_UnitSelActive absolute flow setpointm³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Read
AVmin19AbsFlow_UnitSelMeasured absolute flowm³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Read
AV20Sens1Temp_UnitSelSensor 1 as temperature (passive sensor)°C, K or °F (MV 127)Read
AVmin22DeltaT_UnitSelDelta T between T1 and T2°C, K or °F (MV 128)Read
AV40RelPowerPower relative to maximum power limit%Read
AVmin45CoolingPower_UnitSelCooling powerW, kW, MW, BTU/h, kBTU/h or ton (MV 124)Read
AVmin46HeatingPower_UnitSelHeating powerW, kW, MW, BTU/h, kBTU/h or ton (MV 124)Read
AVmin47CoolingEnergy_UnitSelCooling energy meterJ, kJ, MJ, GJ, Wh, kWh, MWh, BTU, kBTU or ton-h (MV 125)Read
AVmin48HeatingEnergy_UnitSelHeating energy meterJ, kJ, MJ, GJ, Wh, kWh, MWh, BTU, kBTU or ton-h (MV 125)Read
AV52Volume_UnitSelAccumulated volumem³, l, gal or cf (MV 126)Read
AV55AbsDiffPressureMeasured differential water pressurePa, bar, psi, mbar or kPa (MV 131)Read
AV56RelDiffPressureDifferential pressure relative to max dp setpoint%Read
AV60GlycolConcentrationGlycol concentration, measured or override value%Read
AV90VminMinimum flow limit%Write
AV93Vmin_UnitSelMinimum flow limitm³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Write
AV94VmaxMaximum flow limit (25-100% of nominal)%Write
AV97Vmax_UnitSelMaximum flow limitm³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Write
AV100Vnom_UnitSelNominal flow of the valvem³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Read
AV110PmaxMaximum power limit%Write
AV113Pmax_UnitSelMaximum power limitW, kW, MW, BTU/h, kBTU/h or ton (MV 124)Write
AV116Pnom_UnitSelNominal powerW, kW, MW, BTU/h, kBTU/h or ton (MV 124)Read
AV120SpDeltaT_UnitSelDelta T setpoint for dT-Manager°C, K or °F (MV 128)Write
AV127SpAbsFlowDeltaT_UnitSelFlow setpoint at delta Tm³/s, m³/h, l/s, l/min, l/h, gpm or cfm (MV 123)Write
AV130BusWatchdogBus watchdog timeout (5-3600, default 120)sWrite
AV135AbsDiffPressureDifferential water pressure setpointPa, bar, psi, mbar or kPa (MV 131)Write
AV136NomDiffPressureNominal differential pressure setpointPa, bar, psi, mbar or kPa (MV 131)Read
AVmin140ErrorStateBit-coded error and warning flagsReadBit 0=No communication to actuator, 1=Gear train disengaged, 2=Actuator cannot move, 3=Reverse flow, 4=Flow setpoint not reached, 5=Flow with closed valve, 6=Flow actual exceeds flow nominal, 7=Flow measurement error, 8=Remote temperature error, 9=Flowbody temperature error, 10=Communication to sensor interrupted, 11=Freeze warning, 12=Glycol detected, 13=Power setpoint not reached, 14=Device end of life reached, 15=Bus watchdog triggered, 16=No differential pressure detected, 17=Differential pressure setpoint can not be reached, 18=Minimum position applied
BI20Sens1SwitchSensor 1 as switch inputRead0=Inactive, 1=Active
BV99BusTermination120 Ω bus termination enabledRead0=Disabled, 1=Enabled
MV1OverrideOverride control of the setpointCommand1=None, 2=Open Valve, 3=Close Valve, 4=Minimum, 5=–, 6=Maximum, 7=Nominal, 8=–, 9=–, 10=–, 11=Motor stop
MVmin99SummaryStatusSummary of all status objectsRead1=OK, 2=Warning, 3=Not OK
MV100ControlModeHow the setpoint is interpretedWrite1=Position control, 2=Flow control, 3=Power control, 4=Differential pressure control
MV101DeltaT_LimitationDelta T manager modeWrite1=Disabled, 2=dT-Manager, 3=dT-Manager scaling
MV102StatusDeltaTMgrDelta T manager statusRead1=Not selected, 2=Standby, 3=Active, 4=Scaling standby, 5=Scaling active
MV103StatusSensorFlow and temperature sensor statusRead1=OK, 2=Flow measurement error, 3=Flowbody temperature not OK, 4=Remote temperature not OK, 5=Communication to flow sensor interrupted
MV104StatusFlowFlow statusRead1=OK, 2=Actual flow exceeds nominal flow, 3=Flow with closed valve, 4=Flow setpoint cannot be reached, 5=Reverse flow
MV105StatusMediaMedium statusRead1=OK, 2=Glycol detected, 3=Freeze warning
MV106StatusActuatorActuator statusRead1=OK, 2=Actuator cannot move, 3=Gear train disengaged, 4=No communication to actuator
MV107StatusPowerPower control statusRead1=OK, 2=Power not reached
MV120CommandStart service/test function; returns to NoneWrite1=None, 2=–, 3=Synchronization
MVmin122SpSourceSetpoint source: analog wire 3 or bus AO 1Write1=Analog, 2=Bus
MV123UnitSelFlowEngineering unit for flow objectsWrite1=m³/s, 2=m³/h, 3=l/s, 4=l/min, 5=l/h, 6=gpm, 7=cfm
MV124UnitSelPowerEngineering unit for power objectsWrite1=W, 2=kW, 3=MW, 4=BTU/h, 5=kBTU/h, 6=ton
MV125UnitSelEnergyEngineering unit for energy objectsWrite1=J, 2=kJ, 3=MJ, 4=GJ, 5=Wh, 6=kWh, 7=MWh, 8=BTU, 9=kBTU, 10=tonh
MV126UnitSelVolumeEngineering unit for volume objectsWrite1=m³, 2=Litre, 3=Gallon, 4=Cubic foot
MV127UnitSelTemperatureEngineering unit for temperature sensorsWrite1=°C, 2=K, 3=°F
MV128UnitSelDeltaTEngineering unit for delta TWrite1=°C, 2=K, 3=°F
MV130BusFailActionAction when bus watchdog expiresWrite1=None, 2=Open, 3=Close, 4=Max, 5=Min, 6=–, 7=Stop
MV131UnitSelPressureDifferenceEngineering unit for differential pressureWrite1=Pa, 2=bar, 3=psi, 4=mbar, 5=kPa
MV140DiffPressureSensorStatusDifferential pressure sensor statusRead1=OK, 2=Differential pressure not detected
MV141DiffPressureControlStatusDifferential pressure control statusRead1=OK, 2=Differential pressure setpoint cannot be reached, 3=Minimum position applied
MV200SelectMeterRegistersCertified (MID) or lifetime meter registerWrite1=Certified meter register, 2=Lifetime meter register
MV220Sens1TypeSensor 1 input type (bus setpoint only)Write1=None, 2=Active volt, 3=–, 4=Passive, 5=Switch
MV221Sens1TempTypeSensor 1 passive element typeWrite1=None, 2=PT1000, 3=Ni1000EU, 4=–, 5=–, 6=–, 7=–, 8=NTC10k2, 9=NTC10k3
PIV31CoolingEnergyPIV_UnitSelCooling energy meter as integerMV 125 unitRead
PIV32HeatingEnergyPIV_UnitSelHeating energy meter as integerMV 125 unitRead
PIV50VolumePIV_UnitSelAccumulated volume as integerMV 126 unitRead
PIV201MeterSerialNo_Part1Energy meter serial number, first digitsRead
PIV202MeterSerialNo_Part2Energy meter serial number, last digitsRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Energy Valve V4 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo Energy Valve V4

How many BACnet points does the Belimo Energy Valve V4 have?

This list has 68 BACnet objects: 6 analog inputs, 1 analog output, 29 analog values, 1 binary input, 1 binary value, 25 multi-state values, 5 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo Energy Valve V4 BACnet points are writable?

27 of the 68 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo Energy Valve V4 BACnet documentation?

The source is BACnet Interface Description, Energy Valve DN 15...50 (Version 4), revision 2024-09 / V4.2.0, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_Energy-Valve_V4_2_en-gb.pdf.

What are the minimum BACnet points to integrate the Belimo Energy Valve V4?

Start with AO 1 SpRel (Setpoint: position, flow, power or dp per control mode); MV 122 SpSource (Must be Bus for AO 1 to take effect); AV 19 AbsFlow_UnitSel (Measured flow); AV 22 DeltaT_UnitSel (Coil delta T); AV 46 HeatingPower_UnitSel (Heating power delivered; units set by MV 124); AV 45 CoolingPower_UnitSel (Cooling power delivered; units set by MV 124); AV 47 CoolingEnergy_UnitSel (Cooling energy meter); AV 48 HeatingEnergy_UnitSel (Heating energy meter); MV 99 SummaryStatus (Overall OK / warning / not OK); AV 140 ErrorState (Bit-coded fault and warning flags).

How do I enable BMS control of the Belimo Energy Valve V4?

Write MV 122 SpSource = 2 (Bus) so the valve follows AO 1 SpRel instead of the 0-10 V signal on wire 3. MV 1 Override can force open, close, min, max, nominal or motor stop.

Does the Belimo Energy Valve V4 need a BACnet heartbeat or have a communication timeout?

AV 130 BusWatchdog sets a timeout of 5-3600 s (default 120 s). If no write arrives within that time, the valve runs the action in MV 130 BusFailAction (default None; options Open, Close, Max, Min, Stop) and sets the bus watchdog bit in AV 140. With a fail action set, the BMS must keep rewriting the setpoint.

How do I check these points on the real Energy Valve V4?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: BACnet Interface Description, Energy Valve DN 15...50 (Version 4) · rev. 2024-09 / V4.2.0. Object names, instances and units are reproduced as published; descriptions are our own.