Valve actuator (Ethernet, IoT) · BACnet points list

Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) BACnet points list

Updated 28 October 2026

Short answer

These Belimo valve actuators have an Ethernet port with a web server and BACnet IP. The BMS writes a 0-100 % setpoint to AO 1 and reads position, two sensor inputs and status. The setpoint can instead come from an analog signal on S1, chosen with SpSource.

This page lists 13 BACnet objects for the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)
Equipment
Valve actuator (Ethernet, IoT)
Equipment type
Valves & actuators
BACnet objects
13 (5 writable)
Transport
BACnet IP
Firmware
12.25 (application 3.01-0000)
Also known as
VLM24A-LP1, VLR24A-LP1, VNM24A-LP1, VNR24A-LP1, VSM24A-LP1, VSR24A-LP1, VGM24A-LP1, VGR24A-LP1, Belimo IoT Product Range
Source document
Protocol Implementation Conformance Statement IoT Product Range · T5-PICS IoT Product Range v1.0 · rev. 2017-10
Download CSV 13 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)

Integration in brief

Set MV 122 SpSource to Bus and command AO 1 SpRel over BACnet IP. Read AI 1 position and BI 101 summary status. Sensor types are set over BACnet but must be confirmed on the web server.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1SpRelValve setpoint, 0-100 %Command
MV 122SpSourceMust be Bus for AO 1 to take effectWrite
AI 1RelPosValve position feedbackRead
BI 101SummaryStatusOverall OK / not OK alarmRead

Enable & remote start

MV 122 SpSource selects the setpoint: Bus uses AO 1, Analog uses the (0)2-10 V signal on S1 while BACnet stays available for monitoring. Analog setpoint needs Sensortype 1 = Active, confirmed on the web server. MO 1 Override can force Open, Close or MotStop.

Network setup

Watch out for

Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

13 of 13 shown
Type
Binary
Access
Show
Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) BACnet Points List
DescriptionStates
AOmin1SpRelBus setpoint, relative to position%Command
MO1OverrideOverride controlCommand1=None, 2=Open, 3=Close, 4=MotStop
AImin1RelPosRelative position%Read
AI2AbsPosAbsolute position°Read
AI6SpAnalogAnalog setpoint%Read
AI20S1Sensor 1 raw value (0/1, ohm or mV by type)Read
AI21S2Sensor 2 raw value (0/1, ohm or mV by type)Read
BImin101SummaryStatusSummary of MI 103 and MI 106Read0=OK, 1=Not OK
MI103StatusSensorPassive sensor statusRead1=OK, 2=S1 not OK, 3=S2 not OK
MI106StatusActuatorActuator statusRead1=OK, 2=Actuator cannot move, 3=Gear disengaged
MVmin122SpSourceSetpoint source: analog on S1 or bus AO 1Write1=Analog, 2=Bus
MV220Sensortype 1Sensor 1 type (confirm on web server)Write1=None, 2=Switch, 3=Passive, 4=Active
MV221Sensortype 2Sensor 2 type (confirm on web server)Write1=None, 2=Switch, 3=Passive, 4=Active

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)

How many BACnet points does the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) have?

This list has 13 BACnet objects: 5 analog inputs, 1 analog output, 1 binary input, 2 multi-state inputs, 1 multi-state output, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) BACnet points are writable?

5 of the 13 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) BACnet documentation?

The source is Protocol Implementation Conformance Statement IoT Product Range (T5-PICS IoT Product Range v1.0), revision 2017-10, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_IoT_product_range_en-gb.pdf.

What are the minimum BACnet points to integrate the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)?

Start with AO 1 SpRel (Valve setpoint, 0-100 %); MV 122 SpSource (Must be Bus for AO 1 to take effect); AI 1 RelPos (Valve position feedback); BI 101 SummaryStatus (Overall OK / not OK alarm).

How do I enable BMS control of the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)?

MV 122 SpSource selects the setpoint: Bus uses AO 1, Analog uses the (0)2-10 V signal on S1 while BACnet stays available for monitoring. Analog setpoint needs Sensortype 1 = Active, confirmed on the web server. MO 1 Override can force Open, Close or MotStop.

How do I check these points on the real IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: Protocol Implementation Conformance Statement IoT Product Range · T5-PICS IoT Product Range v1.0 · rev. 2017-10. Object names, instances and units are reproduced as published; descriptions are our own.