Valve actuator (Ethernet, IoT) · BACnet points list
Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) BACnet points list
Updated 28 October 2026
These Belimo valve actuators have an Ethernet port with a web server and BACnet IP. The BMS writes a 0-100 % setpoint to AO 1 and reads position, two sensor inputs and status. The setpoint can instead come from an analog signal on S1, chosen with SpSource.
This page lists 13 BACnet objects for the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.
- Manufacturer
- Belimo
- Model
- IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)
- Equipment
- Valve actuator (Ethernet, IoT)
- Equipment type
- Valves & actuators
- BACnet objects
- 13 (5 writable)
- Transport
- BACnet IP
- Firmware
- 12.25 (application 3.01-0000)
- Also known as
- VLM24A-LP1, VLR24A-LP1, VNM24A-LP1, VNR24A-LP1, VSM24A-LP1, VSR24A-LP1, VGM24A-LP1, VGR24A-LP1, Belimo IoT Product Range
BMS integration notes: Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)
Set MV 122 SpSource to Bus and command AO 1 SpRel over BACnet IP. Read AI 1 position and BI 101 summary status. Sensor types are set over BACnet but must be confirmed on the web server.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 1 | SpRel | Valve setpoint, 0-100 % | Command |
| MV 122 | SpSource | Must be Bus for AO 1 to take effect | Write |
| AI 1 | RelPos | Valve position feedback | Read |
| BI 101 | SummaryStatus | Overall OK / not OK alarm | Read |
Enable & remote start
MV 122 SpSource selects the setpoint: Bus uses AO 1, Analog uses the (0)2-10 V signal on S1 while BACnet stays available for monitoring. Analog setpoint needs Sensortype 1 = Active, confirmed on the web server. MO 1 Override can force Open, Close or MotStop.
Network setup
- BACnet IP (Annex J), with foreign device registration supported.
- Device instance, object name and location are writable; no default instance is stated.
Watch out for
- Out-of-range analog writes are clamped to the range limits without an error.
- Writes to read-only analog value objects are overwritten by the application without an error.
- Max 5 active COV subscriptions, lifetime up to 8 hours.
- No segmentation support.
Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AOmin | 1 | SpRel | Bus setpoint, relative to position | % | Command | |
| MO | 1 | Override | Override control | Command | 1=None, 2=Open, 3=Close, 4=MotStop | |
| AImin | 1 | RelPos | Relative position | % | Read | |
| AI | 2 | AbsPos | Absolute position | ° | Read | |
| AI | 6 | SpAnalog | Analog setpoint | % | Read | |
| AI | 20 | S1 | Sensor 1 raw value (0/1, ohm or mV by type) | Read | ||
| AI | 21 | S2 | Sensor 2 raw value (0/1, ohm or mV by type) | Read | ||
| BImin | 101 | SummaryStatus | Summary of MI 103 and MI 106 | Read | 0=OK, 1=Not OK | |
| MI | 103 | StatusSensor | Passive sensor status | Read | 1=OK, 2=S1 not OK, 3=S2 not OK | |
| MI | 106 | StatusActuator | Actuator status | Read | 1=OK, 2=Actuator cannot move, 3=Gear disengaged | |
| MVmin | 122 | SpSource | Setpoint source: analog on S1 or bus AO 1 | Write | 1=Analog, 2=Bus | |
| MV | 220 | Sensortype 1 | Sensor 1 type (confirm on web server) | Write | 1=None, 2=Switch, 3=Passive, 4=Active | |
| MV | 221 | Sensortype 2 | Sensor 2 type (confirm on web server) | Write | 1=None, 2=Switch, 3=Passive, 4=Active |
No points match these filters.
Integration notes
- The PICS lists state texts without numbers; numbers here follow the printed order, starting at 1.
- Sensor type changes made over BACnet must be confirmed on the actuator web server.
- Sensor values are raw: 0/1 for a switch, ohm for a passive sensor, mV for an active sensor.
- Foreign device registration is supported for BACnet IP across subnets.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)
How many BACnet points does the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) have?
This list has 13 BACnet objects: 5 analog inputs, 1 analog output, 1 binary input, 2 multi-state inputs, 1 multi-state output, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) BACnet points are writable?
5 of the 13 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP) BACnet documentation?
The source is Protocol Implementation Conformance Statement IoT Product Range (T5-PICS IoT Product Range v1.0), revision 2017-10, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_IoT_product_range_en-gb.pdf.
What are the minimum BACnet points to integrate the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)?
Start with AO 1 SpRel (Valve setpoint, 0-100 %); MV 122 SpSource (Must be Bus for AO 1 to take effect); AI 1 RelPos (Valve position feedback); BI 101 SummaryStatus (Overall OK / not OK alarm).
How do I enable BMS control of the Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)?
MV 122 SpSource selects the setpoint: Bus uses AO 1, Analog uses the (0)2-10 V signal on S1 while BACnet stays available for monitoring. Analog setpoint needs Sensortype 1 = Active, confirmed on the web server. MO 1 Override can force Open, Close or MotStop.
How do I check these points on the real IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Belimo BACnet points lists
- Pressure-independent control valve
Belimo 2-way EPIV V4
Belimo 2-way electronic pressure-independent valves (EPIV) version 4.2, DN 15 to 50, BACnet models EP..R2+(K)BAC.
Also known as: EPIV, EP..R2+BAC, EP..R2+KBAC, Electronic Pressure Independent Valve, 2-way EPIV DN 15-50 - Ultrasonic liquid flow sensor
Belimo 22PF Flow Sensor
Belimo 22PF-.. ultrasonic flow sensors for water and glycol pipes, interface version 4.3.0.
Also known as: 22PF, 22PF-.., Belimo ultrasonic flow sensor, Flow Sensor 22PF - 6-way pressure-independent control valve
Belimo 6-way EPIV
Belimo 6-way EPIV (EP..R-R6+BAC) used to switch and control a single coil between heating and cooling sequences.
Also known as: EP..R-R6+BAC, 6-way EPIV, 6-way characterised control valve, Belimo 6-way valve - Duct / outdoor sensors (temperature, humidity, CO2, VOC, differential pressure)
Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet
Belimo BACnet MS/TP sensors: 22DTH duct temperature/humidity, 22UTH outdoor temperature/humidity, 22DTM duct CO2/VOC and 22ADP differential pressure/airflow sensors.
Also known as: 22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.., 22DTH-16M, 22DTH-56M, 22UTH-160X, 22UTH-560X, 22DTM-16, 22DTM-56, 22ADP-164, 22ADP-164L, 22ADP-56Q, 22ADP-56QB, 22ADP-564L, 22ADP-566L - Pressure-independent control valve with energy meter
Belimo Energy Valve V4
Belimo Energy Valve version 4, DN 15 to 50, BACnet models EV..R2+(K)BAC, EV..R2+MID and EV..R3+BAC.
Also known as: Energy Valve, EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Belimo Energy Valve 4 - Butterfly valve actuator
Belimo PR..-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo PR rotary actuators for butterfly valves in the BACnet MS/TP version (PR..-BAC-..).
Also known as: PR..-BAC-.., Belimo PR actuator, PR BACnet - Room sensor / operating unit
Belimo Room Operating Unit 22RT-5U00
Belimo 22RT...-5U00... room operating units with virtual or ePaper touch display, measuring temperature, humidity and CO2.
Also known as: 22RT, 22RT…-5U00…, Room Operating Unit, ROU, 22RTM-5U00, Belimo room sensor BACnet - Thermal (BTU) energy meter
Belimo Thermal Energy Meter V4
Belimo Thermal Energy Meters version 4, DN 15 to 50 (22PE..-1U.., including MID-certified 22PEM models).
Also known as: TEM, Thermal Energy Meter, 22PE-1U, 22PEM-1UC, 22PE…-1U.., Belimo energy meter - VAV compact controller (actuator with flow sensor)
Belimo VAV-Compact
Belimo VAV-Compact volumetric flow controllers with the BACnet/Modbus interface (..MV-D3-MOD and ..HV24A-MOD).
Also known as: VAV-Compact MOD, ..MV-D3-MOD, ..HV24A-MOD, LMV-D3-MOD, NMV-D3-MOD, SMV-D3-MOD, LHV24A-MOD - VAV / CAV / pressure controller
Belimo VAV-Universal VRU
Belimo VAV-Universal controllers VRU-D3-BAC, VRU-M1-BAC and VRU-M1R-BAC used for VAV/CAV airflow, duct pressure and room pressure control.
Also known as: VAV-Universal, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-..-BAC
Source: Protocol Implementation Conformance Statement IoT Product Range · T5-PICS IoT Product Range v1.0 · rev. 2017-10. Object names, instances and units are reproduced as published; descriptions are our own.