Room sensor / operating unit · BACnet points list

Belimo Room Operating Unit 22RT-5U00 BACnet points list

Updated 28 October 2026

Short answer

The 22RT room operating unit is a wall sensor with a configurable display that measures room temperature and, depending on model, humidity and CO2. Over BACnet MS/TP it reports the measured values and lets the BMS read and write the temperature and ventilation setpoints, set the building operation mode, and control what the display shows (icons, buttons, CO2 traffic light). The occupant's local adjustments come back as the same setpoint objects.

This page lists 44 BACnet objects for the Belimo Room Operating Unit 22RT-5U00 — 37 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
Room Operating Unit 22RT-5U00
Equipment
Room sensor / operating unit
Equipment type
Thermostats, sensors & meters
BACnet objects
44 (37 writable)
Transport
BACnet MS/TP
Firmware
ROUS1 V2.2 / V3.0
Default device instance
1
Also known as
22RT, 22RT…-5U00…, Room Operating Unit, ROU, 22RTM-5U00, Belimo room sensor BACnet
Source document
BACnet Interface Description, Room Operating Units 22RT...-5U00... · rev. 2023-04 / V2.2/V3.0
Download CSV 44 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Belimo Room Operating Unit 22RT-5U00

Integration in brief

Read AI 1 temperature (plus AI 2 humidity and AI 3 CO2 where fitted) and use AV 110 or the relative AV 111 as the zone setpoint, which the occupant can also change locally. Use MV 118 for comfort/eco/boost/off mode and AV 15 for the ventilation setpoint. Drive the heating/cooling and warning icons from the BMS if wanted.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 118OperationModeOff / comfort / eco / boostWrite
AV 110SetpointTemperatureZone setpoint (BMS or occupant)Write
AV 15VentilationSetpointVentilation setpoint, % (BMS or occupant)Write
AI 1TemperatureRoom temperatureRead
AI 2Relative_HumidityRoom humidityRead
AI 3Co2ValueRoom CO2Read

Enable & remote start

BV 110 EnLocalAdjustment allows or blocks occupant changes to setpoints, Eco, Boost and On/Off on the unit.

Heartbeat & communication loss

AV 130 BusWatchdog, 30-3600 s (default 120 s), is for monitoring only; the document gives no fail action.

Network setup

Watch out for

Belimo Room Operating Unit 22RT-5U00 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

44 of 44 shown
Type
Multi-state
Access
Show
Belimo Room Operating Unit 22RT-5U00 BACnet Points List
DescriptionStates
AImin1TemperatureRoom temperature°C, K or °F (MV 127)Read
AImin2Relative_HumidityRoom relative humidity%RHRead
AImin3Co2ValueRoom CO2 concentrationppmRead
AV12DewPointTemperatureRoom dew point°C, K or °F (MV 127)Read
AV100TemperatureOffsetRoom temperature offset, -15 to +15KWrite
AV101HumidityOffsetRelative humidity offset, -20 to +20%RHWrite
AV102Co2OffsetCO2 offset, -500 to +500ppmWrite
MV127UnitSelTemperatureTemperature unit used on the busWrite1=°C, 2=K, 3=°F
MV100UnitSelTemperatureDisplayTemperature unit shown on the displayWrite1=°C, 2=-, 3=°F
MV128UnitSelDeltaTUnit for relative setpoint AV 111Write1=°C, 2=K, 3=°F
AVmin110SetpointTemperatureRoom/zone temperature setpoint°C, K or °F (MV 127)Write
AV111SetpointRelTemperatureRelative setpoint shift from default°C, K or °F (MV 128)Write
MV103SetpointTypeAbsolute or relative setpoint on the displayWrite0=Absolute setpoint, 1=Relative setpoint
AV112SetpointTemperatureDefaultCentre of setpoint adjustment range (15-35)°CWrite
AV113AdjustmentRangeSetpointAllowed setpoint adjustment (0-5, e.g. 3 = ±3)KWrite
AVmin15VentilationSetpointRoom/zone ventilation setpoint%Write
MV10ManualAutomaticControlModeManual or automatic ventilation stagesWrite1=Manual ventilation stages control, 2=Automatic ventilation stages control
MV105VentControlModeVentilation control functionalityWrite1=Manual mode only, 2=Automatic or manual
MV106NumberVentilationStagesNumber of ventilation stages on displayWrite1=3 stages, 2=4 stages, 3=7 stages
BV110EnLocalAdjustmentAllow occupant adjustments on the unitWrite0=Disabled, 1=Enabled
BV111ColorSchemeDisplay colour schemeWrite0=Black on white, 1=White on black
BV112ShowTemperatureShow room temperature on displayWrite0=Invisible, 1=Visible
BV113ShowRelHumidityShow relative humidity on displayWrite0=Invisible, 1=Visible
BV114ShowCo2Show CO2 on displayWrite0=Invisible, 1=Visible
MV110TempDisplayModeWhat the large temperature field showsWrite1=Invisible, 2=Display actual room temperature, 3=Room temperature setpoint
BV115ShowVentilationStagesShow ventilation stages on displayWrite0=Invisible, 1=Visible
BV116ShowBoostButtonShow boost button on displayWrite0=Invisible, 1=Visible
MV111ModeEcoButtonEco button behaviourWrite1=Invisible, 2=Display status, 3=Selection eco mode on/off
MV112ModeOnOffButtonOn/off button behaviourWrite1=Invisible, 2=Display status, 3=Selection on/off
BV120ShowWarningIconShow warning icon (when MV 116 = 2)Write0=Invisible, 1=Visible
BV121ShowWindowIconShow window icon (when MV 117 = 2)Write0=Invisible, 1=Visible
MV115DispHeatCoolStHeating/cooling status icon from the BMSWrite1=None, 2=Heating, 3=Cooling
BV122ShowHeatingCoolingIconEnable heating/cooling iconsWrite0=Invisible, 1=Visible
MV116WarningIconFunctionWarning icon sourceWrite1=Invisible, 2=According to display warning icon, 3=According to device error status
MV117WindowIconFunctionWindow icon sourceWrite1=Invisible, 2=According to display window icon, 3=According to digital input
MVmin118OperationModeBuilding operation modeWrite1=Off/protection, 2=On/comfort, 3=Eco mode, 4=Boost mode
AV117BoostModeDurationBoost mode duration (60-3600)sWrite
BI10DigitalInputDigital input state (e.g. window contact)Read0=False, 1=True
AV130BusWatchdogBus watchdog timeout, monitoring only (default 120)sWrite
BV99BusTermination120 Ω bus termination enabledRead0=Disabled, 1=Enabled
MV119AirQualityStatusCO2 traffic-light statusRead1=Deactivated, 2=Ok, 3=Warning, 4=Alarm
BV125ShowAirQualityIndicationShow CO2 traffic lightWrite0=Disabled, 1=Enabled
AV115AirQualityGoodLimitCO2 threshold green/yellow (600-1249)ppmWrite
AV116AirQualityMediumLimitCO2 threshold yellow/red (1250-2000)ppmWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Room Operating Unit 22RT-5U00 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo Room Operating Unit 22RT-5U00

How many BACnet points does the Belimo Room Operating Unit 22RT-5U00 have?

This list has 44 BACnet objects: 3 analog inputs, 13 analog values, 1 binary input, 12 binary values, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo Room Operating Unit 22RT-5U00 BACnet points are writable?

37 of the 44 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo Room Operating Unit 22RT-5U00 BACnet documentation?

The source is BACnet Interface Description, Room Operating Units 22RT...-5U00..., revision 2023-04 / V2.2/V3.0, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/belimo_BACnet_Interface-description_room-sensors-am_en-us.pdf.

What are the minimum BACnet points to integrate the Belimo Room Operating Unit 22RT-5U00?

Start with MV 118 OperationMode (Off / comfort / eco / boost); AV 110 SetpointTemperature (Zone setpoint (BMS or occupant)); AV 15 VentilationSetpoint (Ventilation setpoint, % (BMS or occupant)); AI 1 Temperature (Room temperature); AI 2 Relative_Humidity (Room humidity); AI 3 Co2Value (Room CO2).

How do I enable BMS control of the Belimo Room Operating Unit 22RT-5U00?

BV 110 EnLocalAdjustment allows or blocks occupant changes to setpoints, Eco, Boost and On/Off on the unit.

Does the Belimo Room Operating Unit 22RT-5U00 need a BACnet heartbeat or have a communication timeout?

AV 130 BusWatchdog, 30-3600 s (default 120 s), is for monitoring only; the document gives no fail action.

How do I check these points on the real Room Operating Unit 22RT-5U00?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: BACnet Interface Description, Room Operating Units 22RT...-5U00... · rev. 2023-04 / V2.2/V3.0. Object names, instances and units are reproduced as published; descriptions are our own.