Fire and smoke damper actuator test module · BACnet points list

Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module BACnet points list

Updated 6 November 2026

Short answer

The FSKN-BAC sits in the power feed of a fire or fire/smoke damper actuator and lets a BMS run a remote damper test. A test opens its relay so the damper springs closed, and the end switches are checked to prove the stroke; the result and the damper position are read over BACnet MS/TP (the same board also speaks Modbus RTU, chosen with DIP switch 6).

This page lists 9 BACnet objects for the Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
FSKN120-BAC / FSKN24-BAC fire and smoke damper test module
Equipment
Fire and smoke damper actuator test module
Equipment type
Valves & actuators
BACnet objects
9 (2 writable)
Transport
BACnet MS/TP
Firmware
Application 1.0.4
Also known as
FSKN120-BAC, FSKN24-BAC, FSKN, Belimo FSKN BACnet
Source document
FSKN120-BAC & FSKN24-BAC BACnet and Modbus protocol guide · AB_13004 · rev. 2025-10
Download CSV 9 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.

BMS integration notes: Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module

Integration in brief

Set DIP switch 6 ON for BACnet, set baud and MAC with the DIP switches, then write 3 (Test) to MV 120 to run a damper test. Read AI 1 position and BI 101 summary status for the result, and write 4 (Reset) to MV 120 to clear latched status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 120CommandWrite 3 = Test to stroke the damper, 4 = ResetWrite
AI 1RelPosDamper position: 0, 50 or 100 %Read
MI 100InternalActivityShows a test is runningRead
BI 101SummaryStatusTest or device fault summaryRead

Enable & remote start

Writing 3 (Test) to MV 120 opens the module's relay so the damper springs closed; the position switches prove it. The value returns to None (1) by itself.

Network setup

Watch out for

Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

9 of 9 shown
Type
Binary
Access
Show
Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module BACnet Points List
DescriptionStates
AImin1RelPosDamper position from the position switches (0, 50 or 100 %)%Read
AI2AbsPosAbsolute position (0, 45 or 90°)°Read
AV121OffsetDeviceIDDevice instance offset; instance = offset + MAC (default 1000)Write
BImin101SummaryStatusSummary of MI 106, MI 110 and MI 111Read0=OK, 1=Not OK
MImin100InternalActivityTest running, started by busRead1=None, 2=Test
MI106StatusActuatorActuator status (needs reset)Read1=OK, 2=Actuator cannot move
MI110StatusDeviceDevice status (needs reset)Read1=OK, 2=-, 3=InternalError
MI111StatusTrippingDuct temperature sensor (BAE) status (needs reset)Read1=OK, 2=-, 3=Temperature Sensor triggered
MVmin120CommandStart a damper test or reset status; returns to NoneWrite1=None, 2=-, 3=Test, 4=Reset
Object ID lookup: Belimo FSKN-BAC Damper Test Module point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FSKN120-BAC / FSKN24-BAC fire and smoke damper test module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module

How many BACnet points does the Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module have?

This list has 9 BACnet objects: 2 analog inputs, 1 analog value, 1 binary input, 4 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module BACnet points are writable?

2 of the 9 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module BACnet documentation?

The source is FSKN120-BAC & FSKN24-BAC BACnet and Modbus protocol guide (AB_13004), revision 2025-10, published free by Belimo at https://www.belimo.com/mam/americas/technical_documents/Tools/belimo_FSKN120_FSKN24_BACnet_Modbus_guide_en-us.pdf.

What are the minimum BACnet points to integrate the Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module?

Start with MV 120 Command (Write 3 = Test to stroke the damper, 4 = Reset); AI 1 RelPos (Damper position: 0, 50 or 100 %); MI 100 InternalActivity (Shows a test is running); BI 101 SummaryStatus (Test or device fault summary).

How do I enable BMS control of the Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module?

Writing 3 (Test) to MV 120 opens the module's relay so the damper springs closed; the position switches prove it. The value returns to None (1) by itself.

How do I check these points on the real FSKN120-BAC / FSKN24-BAC fire and smoke damper test module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: FSKN120-BAC & FSKN24-BAC BACnet and Modbus protocol guide · AB_13004 · rev. 2025-10. Object names, instances and units are reproduced as published; descriptions are our own.