- ZoneEase VAV zone control actuator (BACnet MS/TP)
VAV zone controller / actuator · BACnet points list
Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) BACnet points list
Updated 6 November 2026
ZoneEase VAV is a VAV damper actuator with a built-in differential pressure sensor and zone control applications (cooling, changeover, electric or hydronic reheat, parallel or series fan, CO2 and plain VAV). It runs on BACnet MS/TP. The BMS mostly sets the system mode, room setpoint, airflow limits and the heating/cooling changeover, and reads room temperature, airflow and status.
This page lists 97 BACnet objects for the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.
- Manufacturer
- Belimo
- Model
- ZoneEase VAV zone control actuator (BACnet MS/TP)
- Equipment
- VAV zone controller / actuator
- Equipment type
- Valves & actuators
- BACnet objects
- 97 (58 writable)
- Transport
- BACnet MS/TP
- Firmware
- Application ZoneEase 1.7
- Default device instance
- 1
- Also known as
- ZoneEase VAV, LMV-BAC-.., NMV-BAC-.., Belimo ZoneEase
Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.
BMS integration notes: Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)
Pick the application in MV 2 during commissioning, then run the zone from the BMS with MV 1 SystemMode, AV 108 room setpoint and BV 1 changeover (where the application uses it). Read room temperature, airflow and damper position, and watch the status MIs. If a bus fail action is set, keep writing within the watchdog time.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | SystemMode | Off / Active / Eco / Boost | Write |
| AV 108 | SpRmT_C | Room temperature setpoint, °C | Write |
| BV 1 | BMS Changeover | Heating or cooling air from the AHU | Write |
| AI 20 | RmT_C | Room temperature, °C | Read |
| AI 12 | AbsAirFlow_m3h | Measured airflow, m³/h | Read |
| AI 1 | RelPosDmp | Damper position, % | Read |
| MI 101 | StatusSystem | System health: sensor and config faults | Read |
| MI 106 | StatusActuator | Actuator status and errors | Read |
Enable & remote start
MV 1 SystemMode switches the zone between Off, Active, Eco and Boost. In the VAV application (#9 in MV 2) the BMS sets the airflow directly with AV 102-104. MO 1 Override can force the damper or a fixed airflow, temperature or CO2 setpoint (types 8-13 use AO 10).
Heartbeat & communication loss
AV 130 BusWatchdog, 5-3600 s, default 120 s. If no write arrives within the timeout the actuator runs MV 130 BusFailAction (default None).
Sensors & values from the BMS
BV 1 BMS Changeover tells the zone whether the AHU supplies cool or warm air (all applications except #2, #8 and #9). Room temperature, humidity and CO2 come from the connected room operating unit or analog input, not from the BMS.
Network setup
- MS/TP only: baud 9600-115200, default 38400; address 0-127, default 1; max 32 nodes without repeater.
- Device instance 0-4194302, default 1.
- Configure with the Belimo ZoneEase VAV app (Android).
- AV 200 TrunkNoCloud records the MS/TP trunk for the cloud twin and helps spot MAC collisions.
Watch out for
- Persistent writable objects (limits, tuning, configuration) should not be written cyclically.
- Airflow and temperature objects come in several unit versions; map one set and stick to it.
- Max 5 active COV subscriptions, lifetime up to 8 hours.
Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | RelPosDmp | Relative damper position | % | Read | |
| AI | 2 | AbsPosDmp | Absolute damper position | ° | Read | |
| AI | 3 | RelativeHumdity | Room relative humidity | % | Read | |
| AI | 7 | RelPosValve | Reheat valve position (none for on/off valve) | % | Read | |
| AI | 10 | RelAirFlow | Relative airflow, based on V'nom | % | Read | |
| AImin | 12 | AbsAirFlow_m3h | Absolute airflow | m³/h | Read | |
| AI | 13 | AbsAirFlow_cfm | Absolute airflow | cfm | Read | |
| AI | 15 | RelPosDmpSec | Secondary damper position | % | Read | |
| AI | 16 | RelAirFlowSec | Secondary damper relative airflow | % | Read | |
| AI | 19 | AbsAirFlow_UnitSel | Absolute airflow in the unit set by MV 121 | Read | ||
| AImin | 20 | RmT_C | Room temperature | °C | Read | |
| AI | 21 | RmT_F | Room temperature | °F | Read | |
| AI | 23 | RmT_UnitSel | Room temperature in the unit set by MV 128 | Read | ||
| AI | 29 | DeltaP_Pa | Differential pressure | Pa | Read | |
| AI | 61 | CO2Concentration | CO2 concentration | ppm | Read | |
| AI | 110 | SpAbsAirFlow_UnitSel | Airflow setpoint in the unit set by MV 121 | Read | ||
| AO | 10 | OverrideValue | Override setpoint used when MO 1 is 8-13 | Write | ||
| AV | 1 | BoostModeTime | Boost mode time (default 100) | min | Write | |
| AV | 2 | EcoModeHeatSpShift | Eco mode heating setpoint shift (default 4) | °C | Write | |
| AV | 3 | EcoModeCoolSpShift | Eco mode cooling setpoint shift (default 4) | °C | Write | |
| AV | 20 | SpRelAirFlowSec | Setpoint sent to the secondary damper | % | Read | |
| AV | 31 | TempCtrlPBand | Temperature loop P-band (default 2) | Write | ||
| AV | 32 | TempCtrlTn | Temperature loop integral time (default 600) | s | Write | |
| AV | 33 | DeadbandTemp | Temperature loop deadband (default 1) | °C | Write | |
| AV | 34 | CO2CtrlPBand | CO2 loop P-band (CO2 app only) | Write | ||
| AV | 35 | CO2CtrlTn | CO2 loop integral time (CO2 app only) | s | Write | |
| AV | 36 | DeadbandCO2 | CO2 loop deadband (CO2 app only) | ppm | Write | |
| AV | 80 | HysteresisFan | Parallel fan hysteresis | % | Write | |
| AV | 81 | HysteresisElHeater1 | Electric heater 1 hysteresis | % | Write | |
| AV | 82 | HysteresisElHeater2 | Electric heater 2 hysteresis | % | Write | |
| AV | 83 | AggregateStart | Electric reheat start value (default 10) | % | Write | |
| AV | 84 | SpRmTHL_C | High limit of room setpoint at the room unit | °C | Write | |
| AV | 85 | SpRmTLL_C | Low limit of room setpoint at the room unit | °C | Write | |
| AV | 86 | Vmin_m3h | Minimum airflow | m³/h | Write | |
| AV | 87 | VmaxC_m3h | Maximum cooling airflow | m³/h | Write | |
| AV | 88 | Vmin_UnitSel | Minimum airflow in the unit set by MV 121 | Write | ||
| AV | 89 | VmaxC_UnitSel | Maximum cooling airflow in the unit set by MV 121 | Write | ||
| AV | 90 | Vmin_cfm | Minimum airflow | cfm | Write | |
| AV | 91 | VmaxC_cfm | Maximum cooling airflow | cfm | Write | |
| AV | 93 | VmaxH_m3/h | Maximum heating airflow | m³/h | Write | |
| AV | 94 | VmaxH_UnitSel | Maximum heating airflow in the unit set by MV 121 | Write | ||
| AV | 95 | VmaxH_cfm | Maximum heating airflow | cfm | Write | |
| AV | 102 | SpAbsVAVAirFlow_m3h | Airflow setpoint (VAV application #9 only) | m³/h | Write | |
| AV | 103 | SpAbsVAVAirFlow_cfm | Airflow setpoint (VAV application #9 only) | cfm | Write | |
| AV | 104 | SpAbsVAVAirFlow_UnitSel | Airflow setpoint in MV 121 unit (VAV app #9 only) | Write | ||
| AVmin | 108 | SpRmT_C | Room temperature setpoint (default 22) | °C | Write | |
| AV | 109 | SpRmT_F | Room temperature setpoint | °F | Write | |
| AV | 110 | SpRmT_UnitSel | Room temperature setpoint in the unit set by MV 128 | Write | ||
| AV | 111 | SpCO2 | CO2 setpoint (CO2 app only) | ppm | Write | |
| AV | 112 | Vnom_m3h | Nominal airflow | m³/h | Read | |
| AV | 113 | Vnom_cfm | Nominal airflow | cfm | Read | |
| AV | 115 | AirQualityGoodLimit | CO2 limit for good air quality LED (default 1000) | ppm | Write | |
| AV | 116 | AirQualityMediumLimit | CO2 limit for moderate air quality LED (default 1500) | ppm | Write | |
| AV | 117 | FlowGainSec | Secondary damper airflow gain | Write | ||
| AV | 119 | Vnom_UnitSel | Nominal airflow in the unit set by MV 121 | Read | ||
| AV | 120 | VnomSec_m3h | Secondary damper nominal airflow | m³/h | Read | |
| AV | 121 | VnomSec_UnitSel | Secondary damper nominal airflow, MV 121 unit | Read | ||
| AV | 122 | VmaxSec_m3h | Secondary damper maximum airflow | m³/h | Read | |
| AV | 123 | VmaxSec_UnitSel | Secondary damper maximum airflow, MV 121 unit | Read | ||
| AV | 124 | VminSec_m3h | Secondary damper minimum airflow | m³/h | Read | |
| AV | 125 | VminSec_UnitSel | Secondary damper minimum airflow, MV 121 unit | Read | ||
| AV | 128 | SetFlowCutOffPressureValue | Differential pressure zero-point cut-off | Pa | Write | |
| AV | 130 | BusWatchdog | Bus watchdog timeout (5-3600 s, default 120) | s | Write | |
| AV | 200 | TrunkNoCloud | MS/TP trunk number for the cloud twin | Write | ||
| BI | 4 | FrostModeState | Frost mode state | Read | 0=Inactive, 1=Active | |
| BI | 5 | DigitalInputStatus | Room unit digital input | Read | 0=Inactive, 1=Active | |
| BI | 6 | HighCutState | Reheat safety (high cut) state | Read | 0=Inactive, 1=Active | |
| BI | 10 | Heater1State | Electric heater 1 / on-off valve state | Read | 0=Off, 1=On | |
| BI | 11 | Heater2State | Electric heater 2 state | Read | 0=Off, 1=On | |
| BI | 12 | FanState | Fan state | Read | 0=Off, 1=On | |
| BI | 15 | RmOccupState | Presence sensor state | Read | 0=Not occupied, 1=Occupied | |
| BVmin | 1 | BMS Changeover | Heating/cooling air supplied, written by the BMS | Write | 0=Cooling, 1=Heating | |
| BV | 2 | RUOpRights | Room unit operating rights (default enabled) | Write | 0=Room unit access disabled, 1=Room unit access enabled | |
| BV | 3 | OpStateSec | Secondary damper setpoint reached | Read | 0=Setpoint not reached, 1=Setpoint reached | |
| BV | 10 | SyncPos | Damper synchronization position | Write | 0=0% (damper closed), 1=100% (damper open) | |
| BV | 11 | SyncStart | Start synchronization | Write | 0=No sync., 1=Start sync. | |
| BV | 13 | OccupSensEn | Enable occupancy sensor (toggles Active/Eco) | Write | 0=Disabled, 1=Enabled | |
| BV | 21 | OffModeDmpPos | Damper position in Off mode | Write | 0=Damper closed, 1=Damper controlled to V'min | |
| BV | 111 | ColorScheme | Room unit display colors | Write | 0=Black on white, 1=White on black | |
| BV | 117 | EnFlowCutOff | Suppress creep flow with closed damper | Write | 0=Disabled, 1=Enabled | |
| BV | 125 | ShowAirQualityIndication | Air quality LED on the room unit | Write | 0=Disabled, 1=Enabled | |
| BV | 127 | ROUDisplaySensorValues | Show sensor values on the room unit | Write | 0=Invisible, 1=Visible | |
| BV | 128 | EnSec | Enable secondary damper | Write | 0=Disabled, 1=Enabled | |
| MImin | 101 | StatusSystem | Health of the standalone VAV system | Read | 1=System OK, 2=Invalid application, 3=Room temp. sensor broken, 4=Room temp. out of range, 5=Deadband temp. not reached, 6=AI sensor error, 7=AI sensor value out of range, 8=Deadband CO2 not reached, 9=V'min invalid, 10=CtrlRefVal | |
| MImin | 106 | StatusActuator | Actuator status | Read | 1=Actuator OK, 2=Adaptation in progress, 3=Sync. in progress, 4=Motor stop, 5=Actuator setpoint position cannot be reached (error), 6=Flow with closed damper position, 7=Actuator setpoint position cannot be reached (warning) | |
| MI | 108 | StatusMPBus | MP-Bus and connected device status | Read | 1=MP-Bus OK, 2=MP-Bus not alive, 3=MP-Bus room unit/ceiling unit not alive, 4=MP-Bus I/O module not alive, 5=MP-Bus reheat valve not alive, 6=MP-Bus secondary damper not alive | |
| MI | 109 | StatusPressure | Differential pressure sensor and duct pressure status | Read | 1=Pressure OK, 2=dp sensor broken, 3=dp sensor out of range, 4=dp sensor connected incorrectly or back flow detected, 5=Insufficient pressure | |
| MO | 1 | Override | Override control; types 8-13 use AO 10 | Write | 1=None, 2=Open damper, 3=Close damper, 4=Airflow V'max, 5=Airflow V'min, 6=Airflow V'nom, 7=MotorStop, 8=Pos. damper in %, 9=Airflow in %, 10=Airflow in m³/h, 11=-, 12=Temp. SP in °C, 13=CO2 SP in ppm | |
| MVmin | 1 | SystemMode | System mode (default Active) | Write | 1=Off, 2=Active, 3=Eco, 4=Boost | |
| MV | 2 | ApplicationSel | VAV zone application selection | Write | 1=none, 2=c, 3=c/h, 4=c+el-rh1, 5=c+el-rh2, 6=c+on/off-rh, 7=c+mod-rh, 8=CO2, 9=VAV, 10=c+p-f, 11=c+p-f+el-rh1, 12=c+p-f+el-rh2, 13=c+p-f+on/off-rh, 14=c+p-f+mod-rh, 15=c+s-f, 16=c/h+s-f, 17=c+s-f+el-rh1, 18=c+s-f+el-rh2, 19=c+s-f+on/off-rh, 20=c+s-f+mod-rh | |
| MV | 3 | PowerOnMode | Action at power-on (default Synchronization) | Write | 1=No action, 2=Synchronization, 3=Adaptation | |
| MV | 4 | RUDisplaySet | Room unit display setting (22RT-A00.. units) | Read | 1=Room temp. and setpoint display, 2=Setpoint display only, 3=Room temperature only | |
| MV | 5 | ReheatEn | When reheat is allowed (default heating only) | Write | 1=Always allowed, 2=Allowed in heating mode only, 3=Allowed in cooling mode only, 4=Never allowed | |
| MV | 6 | CtrlRefVal | Reference values for VAV control | Write | 1=Temperature only, 2=Temperature and CO2 analog input, 3=Temperature and CO2 room operating unit | |
| MV | 121 | UnitSelAirFlow | Airflow unit for the _UnitSel objects | Write | 1=m³/h, 2=l/s, 3=cfm | |
| MV | 128 | UnitSelTemp | Temperature unit for the _UnitSel objects | Write | 1=K, 2=°C, 3=°F | |
| MV | 130 | BusFailAction | Action when the bus watchdog expires | Write | 1=None, 2=Open, 3=Close, 4=Max, 5=Min, 6=-, 7=Stop |
No points match these filters.
Object ID lookup: Belimo ZoneEase VAV point IDs by name
AI1RelPosDmpAI2AbsPosDmpAI3RelativeHumdityAI7RelPosValveAI10RelAirFlowAI12AbsAirFlow_m3hAI13AbsAirFlow_cfmAI15RelPosDmpSecAI16RelAirFlowSecAI19AbsAirFlow_UnitSelAI20RmT_CAI21RmT_FAI23RmT_UnitSelAI29DeltaP_PaAI61CO2ConcentrationAI110SpAbsAirFlow_UnitSelAO10OverrideValueAV1BoostModeTimeAV2EcoModeHeatSpShiftAV3EcoModeCoolSpShiftAV20SpRelAirFlowSecAV31TempCtrlPBandAV32TempCtrlTnAV33DeadbandTempAV34CO2CtrlPBandAV35CO2CtrlTnAV36DeadbandCO2AV80HysteresisFanAV81HysteresisElHeater1AV82HysteresisElHeater2AV83AggregateStartAV84SpRmTHL_CAV85SpRmTLL_CAV86Vmin_m3hAV87VmaxC_m3hAV88Vmin_UnitSelAV89VmaxC_UnitSelAV90Vmin_cfmAV91VmaxC_cfmAV93VmaxH_m3/hAV94VmaxH_UnitSelAV95VmaxH_cfmAV102SpAbsVAVAirFlow_m3hAV103SpAbsVAVAirFlow_cfmAV104SpAbsVAVAirFlow_UnitSelAV108SpRmT_CAV109SpRmT_FAV110SpRmT_UnitSelAV111SpCO2AV112Vnom_m3hAV113Vnom_cfmAV115AirQualityGoodLimitAV116AirQualityMediumLimitAV117FlowGainSecAV119Vnom_UnitSelAV120VnomSec_m3hAV121VnomSec_UnitSelAV122VmaxSec_m3hAV123VmaxSec_UnitSelAV124VminSec_m3hAV125VminSec_UnitSelAV128SetFlowCutOffPressureValueAV130BusWatchdogAV200TrunkNoCloudBI4FrostModeStateBI5DigitalInputStatusBI6HighCutStateBI10Heater1StateBI11Heater2StateBI12FanStateBI15RmOccupStateBV1BMS ChangeoverBV2RUOpRightsBV3OpStateSecBV10SyncPosBV11SyncStartBV13OccupSensEnBV21OffModeDmpPosBV111ColorSchemeBV117EnFlowCutOffBV125ShowAirQualityIndicationBV127ROUDisplaySensorValuesBV128EnSecMI101StatusSystemMI106StatusActuatorMI108StatusMPBusMI109StatusPressureMO1OverrideMV1SystemModeMV2ApplicationSelMV3PowerOnModeMV4RUDisplaySetMV5ReheatEnMV6CtrlRefValMV121UnitSelAirFlowMV128UnitSelTempMV130BusFailAction
Integration notes
- The interface description lists every object twice (alphabetical, then grouped); the alphabetical list (pdf pp5-11) was used.
- Multi-state state numbers are as printed in the guide.
- Many values exist in several units (m³/h, cfm, °C, °F) plus a _UnitSel copy that follows MV 121 / MV 128.
- Which objects are used depends on the application chosen in MV 2; CO2 and VAV-only objects are marked in the descriptions.
- MI 101 is printed W in the alphabetical list and R in the grouped list; listed as R. MV 4 has no access mark and is listed as R.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ZoneEase VAV zone control actuator (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)
How many BACnet points does the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) have?
This list has 97 BACnet objects: 16 analog inputs, 1 analog output, 47 analog values, 7 binary inputs, 12 binary values, 4 multi-state inputs, 1 multi-state output, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) BACnet points are writable?
58 of the 97 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) BACnet documentation?
The source is BACnet Interface description, ZoneEase VAV (VAV zone control actuator) (V1.7), revision 2025-05, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_ZoneEase-VAV_V1_7_en-gb.pdf.
What are the minimum BACnet points to integrate the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)?
Start with MV 1 SystemMode (Off / Active / Eco / Boost); AV 108 SpRmT_C (Room temperature setpoint, °C); BV 1 BMS Changeover (Heating or cooling air from the AHU); AI 20 RmT_C (Room temperature, °C); AI 12 AbsAirFlow_m3h (Measured airflow, m³/h); AI 1 RelPosDmp (Damper position, %); MI 101 StatusSystem (System health: sensor and config faults); MI 106 StatusActuator (Actuator status and errors).
How do I enable BMS control of the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)?
MV 1 SystemMode switches the zone between Off, Active, Eco and Boost. In the VAV application (#9 in MV 2) the BMS sets the airflow directly with AV 102-104. MO 1 Override can force the damper or a fixed airflow, temperature or CO2 setpoint (types 8-13 use AO 10).
Does the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?
AV 130 BusWatchdog, 5-3600 s, default 120 s. If no write arrives within the timeout the actuator runs MV 130 BusFailAction (default None).
Can the BMS supply sensor values to the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)?
BV 1 BMS Changeover tells the zone whether the AHU supplies cool or warm air (all applications except #2, #8 and #9). Room temperature, humidity and CO2 come from the connected room operating unit or analog input, not from the BMS.
How do I check these points on the real ZoneEase VAV zone control actuator (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Belimo BACnet points lists
- Pressure-independent control valve
Belimo 2-way EPIV V4
Belimo 2-way electronic pressure-independent valves (EPIV) version 4.2, DN 15 to 50, BACnet models EP..R2+(K)BAC.
Also known as: EPIV, EP..R2+BAC, EP..R2+KBAC, Electronic Pressure Independent Valve, 2-way EPIV DN 15-50 - Ultrasonic liquid flow sensor
Belimo 22PF Flow Sensor
Belimo 22PF-.. ultrasonic flow sensors for water and glycol pipes, interface version 4.3.0.
Also known as: 22PF, 22PF-.., Belimo ultrasonic flow sensor, Flow Sensor 22PF - 6-way pressure-independent control valve
Belimo 6-way EPIV
Belimo 6-way EPIV (EP..R-R6+BAC) used to switch and control a single coil between heating and cooling sequences.
Also known as: EP..R-R6+BAC, 6-way EPIV, 6-way characterised control valve, Belimo 6-way valve - Damper and valve actuator
Belimo Air/Water Actuators (BACnet MS/TP)
Belimo general-purpose damper and valve actuators with the BACnet MS/TP interface (rotary, linear and fail-safe types).
Also known as: Belimo air/water actuator, Belimo AirWater BACnet, ..M(C)24A, ..R24A, ..V(K)24A, ..F24A, ..RF24A - Duct / outdoor sensors (temperature, humidity, CO2, VOC, differential pressure)
Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet
Belimo BACnet MS/TP sensors: 22DTH duct temperature/humidity, 22UTH outdoor temperature/humidity, 22DTM duct CO2/VOC and 22ADP differential pressure/airflow sensors.
Also known as: 22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.., 22DTH-16M, 22DTH-56M, 22UTH-160X, 22UTH-560X, 22DTM-16, 22DTM-56, 22ADP-164, 22ADP-164L, 22ADP-56Q, 22ADP-56QB, 22ADP-564L, 22ADP-566L - Pressure-independent control valve with energy meter
Belimo Energy Valve V3
Belimo Energy Valve generation 3 (EV..R+(K)BAC, EV..R3+BAC, EV..F+(K)BAC), the installed base before Energy Valve V4.
Also known as: Energy Valve, EV..R+BAC, EV..R+KBAC, EV..R3+BAC, EV..F+BAC, EV..F+KBAC, Belimo Energy Valve 3 - Pressure-independent control valve with energy meter
Belimo Energy Valve V4
Belimo Energy Valve version 4, DN 15 to 50, BACnet models EV..R2+(K)BAC, EV..R2+MID and EV..R3+BAC.
Also known as: Energy Valve, EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Belimo Energy Valve 4 - Fire and smoke damper actuator test module
Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module
Belimo FSKN120-BAC and FSKN24-BAC remote test modules for spring-return fire and combination fire/smoke damper actuators (FSTF, FSLF, FSNF, FSAFB, FSAF*A) in containment applications.
Also known as: FSKN120-BAC, FSKN24-BAC, FSKN, Belimo FSKN BACnet - Valve actuator (Ethernet, IoT)
Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)
Belimo IoT product range valve actuators VLM/VLR, VNM/VNR, VSM/VSR and VGM/VGR 24A-LP1 with Ethernet and BACnet IP.
Also known as: VLM24A-LP1, VLR24A-LP1, VNM24A-LP1, VNR24A-LP1, VSM24A-LP1, VSR24A-LP1, VGM24A-LP1, VGR24A-LP1, Belimo IoT Product Range - Butterfly valve actuator
Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo JR rotary actuators for butterfly valves in the BACnet MS/TP version (JR..A-BAC-..).
Also known as: JR actuator, JR..A-BAC-.., Belimo JR BACnet, JR/QR - Butterfly valve actuator
Belimo PR..-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo PR rotary actuators for butterfly valves in the BACnet MS/TP version (PR..-BAC-..).
Also known as: PR..-BAC-.., Belimo PR actuator, PR BACnet - Room sensor / operating unit
Belimo Room Operating Unit 22RT-5U00
Belimo 22RT...-5U00... room operating units with virtual or ePaper touch display, measuring temperature, humidity and CO2.
Also known as: 22RT, 22RT…-5U00…, Room Operating Unit, ROU, 22RTM-5U00, Belimo room sensor BACnet - Thermal (BTU) energy meter
Belimo Thermal Energy Meter V4
Belimo Thermal Energy Meters version 4, DN 15 to 50 (22PE..-1U.., including MID-certified 22PEM models).
Also known as: TEM, Thermal Energy Meter, 22PE-1U, 22PEM-1UC, 22PE…-1U.., Belimo energy meter - VAV compact controller (actuator with flow sensor)
Belimo VAV-Compact
Belimo VAV-Compact volumetric flow controllers with the BACnet/Modbus interface (..MV-D3-MOD and ..HV24A-MOD).
Also known as: VAV-Compact MOD, ..MV-D3-MOD, ..HV24A-MOD, LMV-D3-MOD, NMV-D3-MOD, SMV-D3-MOD, LHV24A-MOD - VAV / CAV / pressure controller
Belimo VAV-Universal VRU
Belimo VAV-Universal controllers VRU-D3-BAC, VRU-M1-BAC and VRU-M1R-BAC used for VAV/CAV airflow, duct pressure and room pressure control.
Also known as: VAV-Universal, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-..-BAC
Source: BACnet Interface description, ZoneEase VAV (VAV zone control actuator) · V1.7 · rev. 2025-05. Object names, instances and units are reproduced as published; descriptions are our own.