VAV zone controller / actuator · BACnet points list

Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

ZoneEase VAV is a VAV damper actuator with a built-in differential pressure sensor and zone control applications (cooling, changeover, electric or hydronic reheat, parallel or series fan, CO2 and plain VAV). It runs on BACnet MS/TP. The BMS mostly sets the system mode, room setpoint, airflow limits and the heating/cooling changeover, and reads room temperature, airflow and status.

This page lists 97 BACnet objects for the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) — 58 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
ZoneEase VAV zone control actuator (BACnet MS/TP)
Equipment
VAV zone controller / actuator
Equipment type
Valves & actuators
BACnet objects
97 (58 writable)
Transport
BACnet MS/TP
Firmware
Application ZoneEase 1.7
Default device instance
1
Also known as
ZoneEase VAV, LMV-BAC-.., NMV-BAC-.., Belimo ZoneEase
Source document
BACnet Interface description, ZoneEase VAV (VAV zone control actuator) · V1.7 · rev. 2025-05
Download CSV 97 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.

BMS integration notes: Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)

Integration in brief

Pick the application in MV 2 during commissioning, then run the zone from the BMS with MV 1 SystemMode, AV 108 room setpoint and BV 1 changeover (where the application uses it). Read room temperature, airflow and damper position, and watch the status MIs. If a bus fail action is set, keep writing within the watchdog time.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1SystemModeOff / Active / Eco / BoostWrite
AV 108SpRmT_CRoom temperature setpoint, °CWrite
BV 1BMS ChangeoverHeating or cooling air from the AHUWrite
AI 20RmT_CRoom temperature, °CRead
AI 12AbsAirFlow_m3hMeasured airflow, m³/hRead
AI 1RelPosDmpDamper position, %Read
MI 101StatusSystemSystem health: sensor and config faultsRead
MI 106StatusActuatorActuator status and errorsRead

Enable & remote start

MV 1 SystemMode switches the zone between Off, Active, Eco and Boost. In the VAV application (#9 in MV 2) the BMS sets the airflow directly with AV 102-104. MO 1 Override can force the damper or a fixed airflow, temperature or CO2 setpoint (types 8-13 use AO 10).

Heartbeat & communication loss

AV 130 BusWatchdog, 5-3600 s, default 120 s. If no write arrives within the timeout the actuator runs MV 130 BusFailAction (default None).

Sensors & values from the BMS

BV 1 BMS Changeover tells the zone whether the AHU supplies cool or warm air (all applications except #2, #8 and #9). Room temperature, humidity and CO2 come from the connected room operating unit or analog input, not from the BMS.

Network setup

Watch out for

Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

97 of 97 shown
Type
Access
Show
Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1RelPosDmpRelative damper position%Read
AI2AbsPosDmpAbsolute damper position°Read
AI3RelativeHumdityRoom relative humidity%Read
AI7RelPosValveReheat valve position (none for on/off valve)%Read
AI10RelAirFlowRelative airflow, based on V'nom%Read
AImin12AbsAirFlow_m3hAbsolute airflowm³/hRead
AI13AbsAirFlow_cfmAbsolute airflowcfmRead
AI15RelPosDmpSecSecondary damper position%Read
AI16RelAirFlowSecSecondary damper relative airflow%Read
AI19AbsAirFlow_UnitSelAbsolute airflow in the unit set by MV 121Read
AImin20RmT_CRoom temperature°CRead
AI21RmT_FRoom temperature°FRead
AI23RmT_UnitSelRoom temperature in the unit set by MV 128Read
AI29DeltaP_PaDifferential pressurePaRead
AI61CO2ConcentrationCO2 concentrationppmRead
AI110SpAbsAirFlow_UnitSelAirflow setpoint in the unit set by MV 121Read
AO10OverrideValueOverride setpoint used when MO 1 is 8-13Write
AV1BoostModeTimeBoost mode time (default 100)minWrite
AV2EcoModeHeatSpShiftEco mode heating setpoint shift (default 4)°CWrite
AV3EcoModeCoolSpShiftEco mode cooling setpoint shift (default 4)°CWrite
AV20SpRelAirFlowSecSetpoint sent to the secondary damper%Read
AV31TempCtrlPBandTemperature loop P-band (default 2)Write
AV32TempCtrlTnTemperature loop integral time (default 600)sWrite
AV33DeadbandTempTemperature loop deadband (default 1)°CWrite
AV34CO2CtrlPBandCO2 loop P-band (CO2 app only)Write
AV35CO2CtrlTnCO2 loop integral time (CO2 app only)sWrite
AV36DeadbandCO2CO2 loop deadband (CO2 app only)ppmWrite
AV80HysteresisFanParallel fan hysteresis%Write
AV81HysteresisElHeater1Electric heater 1 hysteresis%Write
AV82HysteresisElHeater2Electric heater 2 hysteresis%Write
AV83AggregateStartElectric reheat start value (default 10)%Write
AV84SpRmTHL_CHigh limit of room setpoint at the room unit°CWrite
AV85SpRmTLL_CLow limit of room setpoint at the room unit°CWrite
AV86Vmin_m3hMinimum airflowm³/hWrite
AV87VmaxC_m3hMaximum cooling airflowm³/hWrite
AV88Vmin_UnitSelMinimum airflow in the unit set by MV 121Write
AV89VmaxC_UnitSelMaximum cooling airflow in the unit set by MV 121Write
AV90Vmin_cfmMinimum airflowcfmWrite
AV91VmaxC_cfmMaximum cooling airflowcfmWrite
AV93VmaxH_m3/hMaximum heating airflowm³/hWrite
AV94VmaxH_UnitSelMaximum heating airflow in the unit set by MV 121Write
AV95VmaxH_cfmMaximum heating airflowcfmWrite
AV102SpAbsVAVAirFlow_m3hAirflow setpoint (VAV application #9 only)m³/hWrite
AV103SpAbsVAVAirFlow_cfmAirflow setpoint (VAV application #9 only)cfmWrite
AV104SpAbsVAVAirFlow_UnitSelAirflow setpoint in MV 121 unit (VAV app #9 only)Write
AVmin108SpRmT_CRoom temperature setpoint (default 22)°CWrite
AV109SpRmT_FRoom temperature setpoint°FWrite
AV110SpRmT_UnitSelRoom temperature setpoint in the unit set by MV 128Write
AV111SpCO2CO2 setpoint (CO2 app only)ppmWrite
AV112Vnom_m3hNominal airflowm³/hRead
AV113Vnom_cfmNominal airflowcfmRead
AV115AirQualityGoodLimitCO2 limit for good air quality LED (default 1000)ppmWrite
AV116AirQualityMediumLimitCO2 limit for moderate air quality LED (default 1500)ppmWrite
AV117FlowGainSecSecondary damper airflow gainWrite
AV119Vnom_UnitSelNominal airflow in the unit set by MV 121Read
AV120VnomSec_m3hSecondary damper nominal airflowm³/hRead
AV121VnomSec_UnitSelSecondary damper nominal airflow, MV 121 unitRead
AV122VmaxSec_m3hSecondary damper maximum airflowm³/hRead
AV123VmaxSec_UnitSelSecondary damper maximum airflow, MV 121 unitRead
AV124VminSec_m3hSecondary damper minimum airflowm³/hRead
AV125VminSec_UnitSelSecondary damper minimum airflow, MV 121 unitRead
AV128SetFlowCutOffPressureValueDifferential pressure zero-point cut-offPaWrite
AV130BusWatchdogBus watchdog timeout (5-3600 s, default 120)sWrite
AV200TrunkNoCloudMS/TP trunk number for the cloud twinWrite
BI4FrostModeStateFrost mode stateRead0=Inactive, 1=Active
BI5DigitalInputStatusRoom unit digital inputRead0=Inactive, 1=Active
BI6HighCutStateReheat safety (high cut) stateRead0=Inactive, 1=Active
BI10Heater1StateElectric heater 1 / on-off valve stateRead0=Off, 1=On
BI11Heater2StateElectric heater 2 stateRead0=Off, 1=On
BI12FanStateFan stateRead0=Off, 1=On
BI15RmOccupStatePresence sensor stateRead0=Not occupied, 1=Occupied
BVmin1BMS ChangeoverHeating/cooling air supplied, written by the BMSWrite0=Cooling, 1=Heating
BV2RUOpRightsRoom unit operating rights (default enabled)Write0=Room unit access disabled, 1=Room unit access enabled
BV3OpStateSecSecondary damper setpoint reachedRead0=Setpoint not reached, 1=Setpoint reached
BV10SyncPosDamper synchronization positionWrite0=0% (damper closed), 1=100% (damper open)
BV11SyncStartStart synchronizationWrite0=No sync., 1=Start sync.
BV13OccupSensEnEnable occupancy sensor (toggles Active/Eco)Write0=Disabled, 1=Enabled
BV21OffModeDmpPosDamper position in Off modeWrite0=Damper closed, 1=Damper controlled to V'min
BV111ColorSchemeRoom unit display colorsWrite0=Black on white, 1=White on black
BV117EnFlowCutOffSuppress creep flow with closed damperWrite0=Disabled, 1=Enabled
BV125ShowAirQualityIndicationAir quality LED on the room unitWrite0=Disabled, 1=Enabled
BV127ROUDisplaySensorValuesShow sensor values on the room unitWrite0=Invisible, 1=Visible
BV128EnSecEnable secondary damperWrite0=Disabled, 1=Enabled
MImin101StatusSystemHealth of the standalone VAV systemRead1=System OK, 2=Invalid application, 3=Room temp. sensor broken, 4=Room temp. out of range, 5=Deadband temp. not reached, 6=AI sensor error, 7=AI sensor value out of range, 8=Deadband CO2 not reached, 9=V'min invalid, 10=CtrlRefVal
MImin106StatusActuatorActuator statusRead1=Actuator OK, 2=Adaptation in progress, 3=Sync. in progress, 4=Motor stop, 5=Actuator setpoint position cannot be reached (error), 6=Flow with closed damper position, 7=Actuator setpoint position cannot be reached (warning)
MI108StatusMPBusMP-Bus and connected device statusRead1=MP-Bus OK, 2=MP-Bus not alive, 3=MP-Bus room unit/ceiling unit not alive, 4=MP-Bus I/O module not alive, 5=MP-Bus reheat valve not alive, 6=MP-Bus secondary damper not alive
MI109StatusPressureDifferential pressure sensor and duct pressure statusRead1=Pressure OK, 2=dp sensor broken, 3=dp sensor out of range, 4=dp sensor connected incorrectly or back flow detected, 5=Insufficient pressure
MO1OverrideOverride control; types 8-13 use AO 10Write1=None, 2=Open damper, 3=Close damper, 4=Airflow V'max, 5=Airflow V'min, 6=Airflow V'nom, 7=MotorStop, 8=Pos. damper in %, 9=Airflow in %, 10=Airflow in m³/h, 11=-, 12=Temp. SP in °C, 13=CO2 SP in ppm
MVmin1SystemModeSystem mode (default Active)Write1=Off, 2=Active, 3=Eco, 4=Boost
MV2ApplicationSelVAV zone application selectionWrite1=none, 2=c, 3=c/h, 4=c+el-rh1, 5=c+el-rh2, 6=c+on/off-rh, 7=c+mod-rh, 8=CO2, 9=VAV, 10=c+p-f, 11=c+p-f+el-rh1, 12=c+p-f+el-rh2, 13=c+p-f+on/off-rh, 14=c+p-f+mod-rh, 15=c+s-f, 16=c/h+s-f, 17=c+s-f+el-rh1, 18=c+s-f+el-rh2, 19=c+s-f+on/off-rh, 20=c+s-f+mod-rh
MV3PowerOnModeAction at power-on (default Synchronization)Write1=No action, 2=Synchronization, 3=Adaptation
MV4RUDisplaySetRoom unit display setting (22RT-A00.. units)Read1=Room temp. and setpoint display, 2=Setpoint display only, 3=Room temperature only
MV5ReheatEnWhen reheat is allowed (default heating only)Write1=Always allowed, 2=Allowed in heating mode only, 3=Allowed in cooling mode only, 4=Never allowed
MV6CtrlRefValReference values for VAV controlWrite1=Temperature only, 2=Temperature and CO2 analog input, 3=Temperature and CO2 room operating unit
MV121UnitSelAirFlowAirflow unit for the _UnitSel objectsWrite1=m³/h, 2=l/s, 3=cfm
MV128UnitSelTempTemperature unit for the _UnitSel objectsWrite1=K, 2=°C, 3=°F
MV130BusFailActionAction when the bus watchdog expiresWrite1=None, 2=Open, 3=Close, 4=Max, 5=Min, 6=-, 7=Stop
Object ID lookup: Belimo ZoneEase VAV point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ZoneEase VAV zone control actuator (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)

How many BACnet points does the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) have?

This list has 97 BACnet objects: 16 analog inputs, 1 analog output, 47 analog values, 7 binary inputs, 12 binary values, 4 multi-state inputs, 1 multi-state output, 9 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) BACnet points are writable?

58 of the 97 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) BACnet documentation?

The source is BACnet Interface description, ZoneEase VAV (VAV zone control actuator) (V1.7), revision 2025-05, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_ZoneEase-VAV_V1_7_en-gb.pdf.

What are the minimum BACnet points to integrate the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)?

Start with MV 1 SystemMode (Off / Active / Eco / Boost); AV 108 SpRmT_C (Room temperature setpoint, °C); BV 1 BMS Changeover (Heating or cooling air from the AHU); AI 20 RmT_C (Room temperature, °C); AI 12 AbsAirFlow_m3h (Measured airflow, m³/h); AI 1 RelPosDmp (Damper position, %); MI 101 StatusSystem (System health: sensor and config faults); MI 106 StatusActuator (Actuator status and errors).

How do I enable BMS control of the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)?

MV 1 SystemMode switches the zone between Off, Active, Eco and Boost. In the VAV application (#9 in MV 2) the BMS sets the airflow directly with AV 102-104. MO 1 Override can force the damper or a fixed airflow, temperature or CO2 setpoint (types 8-13 use AO 10).

Does the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

AV 130 BusWatchdog, 5-3600 s, default 120 s. If no write arrives within the timeout the actuator runs MV 130 BusFailAction (default None).

Can the BMS supply sensor values to the Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)?

BV 1 BMS Changeover tells the zone whether the AHU supplies cool or warm air (all applications except #2, #8 and #9). Room temperature, humidity and CO2 come from the connected room operating unit or analog input, not from the BMS.

How do I check these points on the real ZoneEase VAV zone control actuator (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: BACnet Interface description, ZoneEase VAV (VAV zone control actuator) · V1.7 · rev. 2025-05. Object names, instances and units are reproduced as published; descriptions are our own.