 "manufacturer": "Belimo",
 "manufacturer_slug": "belimo",
 "model": "ZoneEase VAV zone control actuator (BACnet MS/TP)",
 "model_slug": "zoneease-vav",
 "short_model": "ZoneEase VAV",
 "aliases": [
  "ZoneEase VAV",
  "LMV-BAC-..",
  "NMV-BAC-..",
  "Belimo ZoneEase"
 ],
 "equipment_type": "VAV zone controller / actuator",
 "applies_to": "Belimo ZoneEase VAV actuators LMV-BAC-.. and NMV-BAC-.. with the built-in zone control applications, application software ZoneEase 1.7.",
 "summary": "ZoneEase VAV is a VAV damper actuator with a built-in differential pressure sensor and zone control applications (cooling, changeover, electric or hydronic reheat, parallel or series fan, CO2 and plain VAV). It runs on BACnet MS/TP. The BMS mostly sets the system mode, room setpoint, airflow limits and the heating/cooling changeover, and reads room temperature, airflow and status.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "Application ZoneEase 1.7",
 "default_device_instance": 1,
 "access_inferred": false,
 "notes": [
  "The interface description lists every object twice (alphabetical, then grouped); the alphabetical list (pdf pp5-11) was used.",
  "Multi-state state numbers are as printed in the guide.",
  "Many values exist in several units (m³/h, cfm, °C, °F) plus a _UnitSel copy that follows MV 121 / MV 128.",
  "Which objects are used depends on the application chosen in MV 2; CO2 and VAV-only objects are marked in the descriptions.",
  "MI 101 is printed W in the alphabetical list and R in the grouped list; listed as R. MV 4 has no access mark and is listed as R."
 ],
 "source": {
  "title": "BACnet Interface description, ZoneEase VAV (VAV zone control actuator)",
  "doc_number": "V1.7",
  "revision_date": "2025-05",
  "url": "https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_ZoneEase-VAV_V1_7_en-gb.pdf"
 },
 "integration": {
  "summary": "Pick the application in MV 2 during commissioning, then run the zone from the BMS with MV 1 SystemMode, AV 108 room setpoint and BV 1 changeover (where the application uses it). Read room temperature, airflow and damper position, and watch the status MIs. If a bus fail action is set, keep writing within the watchdog time.",
  "minimum_points": [
   {
    "ref": "MV 1",
    "name": "SystemMode",
    "why": "Off / Active / Eco / Boost"
   },
   {
    "ref": "AV 108",
    "name": "SpRmT_C",
    "why": "Room temperature setpoint, °C"
   },
   {
    "ref": "BV 1",
    "name": "BMS Changeover",
    "why": "Heating or cooling air from the AHU"
   },
   {
    "ref": "AI 20",
    "name": "RmT_C",
    "why": "Room temperature, °C"
   },
   {
    "ref": "AI 12",
    "name": "AbsAirFlow_m3h",
    "why": "Measured airflow, m³/h"
   },
   {
    "ref": "AI 1",
    "name": "RelPosDmp",
    "why": "Damper position, %"
   },
   {
    "ref": "MI 101",
    "name": "StatusSystem",
    "why": "System health: sensor and config faults"
   },
   {
    "ref": "MI 106",
    "name": "StatusActuator",
    "why": "Actuator status and errors"
   }
  ],
  "enable": "MV 1 SystemMode switches the zone between Off, Active, Eco and Boost. In the VAV application (#9 in MV 2) the BMS sets the airflow directly with AV 102-104. MO 1 Override can force the damper or a fixed airflow, temperature or CO2 setpoint (types 8-13 use AO 10).",
  "heartbeat": "AV 130 BusWatchdog, 5-3600 s, default 120 s. If no write arrives within the timeout the actuator runs MV 130 BusFailAction (default None).",
  "remote_sensors": "BV 1 BMS Changeover tells the zone whether the AHU supplies cool or warm air (all applications except #2, #8 and #9). Room temperature, humidity and CO2 come from the connected room operating unit or analog input, not from the BMS.",
  "setup": [
   "MS/TP only: baud 9600-115200, default 38400; address 0-127, default 1; max 32 nodes without repeater.",
   "Device instance 0-4194302, default 1.",
   "Configure with the Belimo ZoneEase VAV app (Android).",
   "AV 200 TrunkNoCloud records the MS/TP trunk for the cloud twin and helps spot MAC collisions."
  ],
  "gotchas": [
   "Persistent writable objects (limits, tuning, configuration) should not be written cyclically.",
   "Airflow and temperature objects come in several unit versions; map one set and stick to it.",
   "Max 5 active COV subscriptions, lifetime up to 8 hours."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "RelPosDmp",
   "description": "Relative damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "AbsPosDmp",
   "description": "Absolute damper position",
   "units": "°",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "RelativeHumdity",
   "description": "Room relative humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "RelPosValve",
   "description": "Reheat valve position (none for on/off valve)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "RelAirFlow",
   "description": "Relative airflow, based on V'nom",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "AbsAirFlow_m3h",
   "description": "Absolute airflow",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "AbsAirFlow_cfm",
   "description": "Absolute airflow",
   "units": "cfm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "RelPosDmpSec",
   "description": "Secondary damper position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "RelAirFlowSec",
   "description": "Secondary damper relative airflow",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "AbsAirFlow_UnitSel",
   "description": "Absolute airflow in the unit set by MV 121",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "RmT_C",
   "description": "Room temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "RmT_F",
   "description": "Room temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "RmT_UnitSel",
   "description": "Room temperature in the unit set by MV 128",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "DeltaP_Pa",
   "description": "Differential pressure",
   "units": "Pa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "CO2Concentration",
   "description": "CO2 concentration",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 110,
   "name": "SpAbsAirFlow_UnitSel",
   "description": "Airflow setpoint in the unit set by MV 121",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 10,
   "name": "OverrideValue",
   "description": "Override setpoint used when MO 1 is 8-13",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "BoostModeTime",
   "description": "Boost mode time (default 100)",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "EcoModeHeatSpShift",
   "description": "Eco mode heating setpoint shift (default 4)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "EcoModeCoolSpShift",
   "description": "Eco mode cooling setpoint shift (default 4)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "SpRelAirFlowSec",
   "description": "Setpoint sent to the secondary damper",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "TempCtrlPBand",
   "description": "Temperature loop P-band (default 2)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "TempCtrlTn",
   "description": "Temperature loop integral time (default 600)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "DeadbandTemp",
   "description": "Temperature loop deadband (default 1)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "CO2CtrlPBand",
   "description": "CO2 loop P-band (CO2 app only)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "CO2CtrlTn",
   "description": "CO2 loop integral time (CO2 app only)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "DeadbandCO2",
   "description": "CO2 loop deadband (CO2 app only)",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "HysteresisFan",
   "description": "Parallel fan hysteresis",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "HysteresisElHeater1",
   "description": "Electric heater 1 hysteresis",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "HysteresisElHeater2",
   "description": "Electric heater 2 hysteresis",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "AggregateStart",
   "description": "Electric reheat start value (default 10)",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "SpRmTHL_C",
   "description": "High limit of room setpoint at the room unit",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "SpRmTLL_C",
   "description": "Low limit of room setpoint at the room unit",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "Vmin_m3h",
   "description": "Minimum airflow",
   "units": "m³/h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "VmaxC_m3h",
   "description": "Maximum cooling airflow",
   "units": "m³/h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "Vmin_UnitSel",
   "description": "Minimum airflow in the unit set by MV 121",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "VmaxC_UnitSel",
   "description": "Maximum cooling airflow in the unit set by MV 121",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "Vmin_cfm",
   "description": "Minimum airflow",
   "units": "cfm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "VmaxC_cfm",
   "description": "Maximum cooling airflow",
   "units": "cfm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "VmaxH_m3/h",
   "description": "Maximum heating airflow",
   "units": "m³/h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "VmaxH_UnitSel",
   "description": "Maximum heating airflow in the unit set by MV 121",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "VmaxH_cfm",
   "description": "Maximum heating airflow",
   "units": "cfm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "SpAbsVAVAirFlow_m3h",
   "description": "Airflow setpoint (VAV application #9 only)",
   "units": "m³/h",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "SpAbsVAVAirFlow_cfm",
   "description": "Airflow setpoint (VAV application #9 only)",
   "units": "cfm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "SpAbsVAVAirFlow_UnitSel",
   "description": "Airflow setpoint in MV 121 unit (VAV app #9 only)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "SpRmT_C",
   "description": "Room temperature setpoint (default 22)",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "SpRmT_F",
   "description": "Room temperature setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "SpRmT_UnitSel",
   "description": "Room temperature setpoint in the unit set by MV 128",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "SpCO2",
   "description": "CO2 setpoint (CO2 app only)",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "Vnom_m3h",
   "description": "Nominal airflow",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "Vnom_cfm",
   "description": "Nominal airflow",
   "units": "cfm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "AirQualityGoodLimit",
   "description": "CO2 limit for good air quality LED (default 1000)",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "AirQualityMediumLimit",
   "description": "CO2 limit for moderate air quality LED (default 1500)",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "FlowGainSec",
   "description": "Secondary damper airflow gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "Vnom_UnitSel",
   "description": "Nominal airflow in the unit set by MV 121",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "VnomSec_m3h",
   "description": "Secondary damper nominal airflow",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "VnomSec_UnitSel",
   "description": "Secondary damper nominal airflow, MV 121 unit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "VmaxSec_m3h",
   "description": "Secondary damper maximum airflow",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "VmaxSec_UnitSel",
   "description": "Secondary damper maximum airflow, MV 121 unit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "VminSec_m3h",
   "description": "Secondary damper minimum airflow",
   "units": "m³/h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "VminSec_UnitSel",
   "description": "Secondary damper minimum airflow, MV 121 unit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "SetFlowCutOffPressureValue",
   "description": "Differential pressure zero-point cut-off",
   "units": "Pa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "BusWatchdog",
   "description": "Bus watchdog timeout (5-3600 s, default 120)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 200,
   "name": "TrunkNoCloud",
   "description": "MS/TP trunk number for the cloud twin",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "FrostModeState",
   "description": "Frost mode state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "DigitalInputStatus",
   "description": "Room unit digital input",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "HighCutState",
   "description": "Reheat safety (high cut) state",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "Heater1State",
   "description": "Electric heater 1 / on-off valve state",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "Heater2State",
   "description": "Electric heater 2 state",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 12,
   "name": "FanState",
   "description": "Fan state",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 15,
   "name": "RmOccupState",
   "description": "Presence sensor state",
   "units": "",
   "access": "R",
   "states": "0=Not occupied, 1=Occupied"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "BMS Changeover",
   "description": "Heating/cooling air supplied, written by the BMS",
   "units": "",
   "access": "W",
   "states": "0=Cooling, 1=Heating"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "RUOpRights",
   "description": "Room unit operating rights (default enabled)",
   "units": "",
   "access": "W",
   "states": "0=Room unit access disabled, 1=Room unit access enabled"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "OpStateSec",
   "description": "Secondary damper setpoint reached",
   "units": "",
   "access": "R",
   "states": "0=Setpoint not reached, 1=Setpoint reached"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "SyncPos",
   "description": "Damper synchronization position",
   "units": "",
   "access": "W",
   "states": "0=0% (damper closed), 1=100% (damper open)"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "SyncStart",
   "description": "Start synchronization",
   "units": "",
   "access": "W",
   "states": "0=No sync., 1=Start sync."
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "OccupSensEn",
   "description": "Enable occupancy sensor (toggles Active/Eco)",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "OffModeDmpPos",
   "description": "Damper position in Off mode",
   "units": "",
   "access": "W",
   "states": "0=Damper closed, 1=Damper controlled to V'min"
  },
  {
   "type": "BV",
   "instance": 111,
   "name": "ColorScheme",
   "description": "Room unit display colors",
   "units": "",
   "access": "W",
   "states": "0=Black on white, 1=White on black"
  },
  {
   "type": "BV",
   "instance": 117,
   "name": "EnFlowCutOff",
   "description": "Suppress creep flow with closed damper",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 125,
   "name": "ShowAirQualityIndication",
   "description": "Air quality LED on the room unit",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BV",
   "instance": 127,
   "name": "ROUDisplaySensorValues",
   "description": "Show sensor values on the room unit",
   "units": "",
   "access": "W",
   "states": "0=Invisible, 1=Visible"
  },
  {
   "type": "BV",
   "instance": 128,
   "name": "EnSec",
   "description": "Enable secondary damper",
   "units": "",
   "access": "W",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "MI",
   "instance": 101,
   "name": "StatusSystem",
   "description": "Health of the standalone VAV system",
   "units": "",
   "access": "R",
   "states": "1=System OK, 2=Invalid application, 3=Room temp. sensor broken, 4=Room temp. out of range, 5=Deadband temp. not reached, 6=AI sensor error, 7=AI sensor value out of range, 8=Deadband CO2 not reached, 9=V'min invalid, 10=CtrlRefVal"
  },
  {
   "type": "MI",
   "instance": 106,
   "name": "StatusActuator",
   "description": "Actuator status",
   "units": "",
   "access": "R",
   "states": "1=Actuator OK, 2=Adaptation in progress, 3=Sync. in progress, 4=Motor stop, 5=Actuator setpoint position cannot be reached (error), 6=Flow with closed damper position, 7=Actuator setpoint position cannot be reached (warning)"
  },
  {
   "type": "MI",
   "instance": 108,
   "name": "StatusMPBus",
   "description": "MP-Bus and connected device status",
   "units": "",
   "access": "R",
   "states": "1=MP-Bus OK, 2=MP-Bus not alive, 3=MP-Bus room unit/ceiling unit not alive, 4=MP-Bus I/O module not alive, 5=MP-Bus reheat valve not alive, 6=MP-Bus secondary damper not alive"
  },
  {
   "type": "MI",
   "instance": 109,
   "name": "StatusPressure",
   "description": "Differential pressure sensor and duct pressure status",
   "units": "",
   "access": "R",
   "states": "1=Pressure OK, 2=dp sensor broken, 3=dp sensor out of range, 4=dp sensor connected incorrectly or back flow detected, 5=Insufficient pressure"
  },
  {
   "type": "MO",
   "instance": 1,
   "name": "Override",
   "description": "Override control; types 8-13 use AO 10",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Open damper, 3=Close damper, 4=Airflow V'max, 5=Airflow V'min, 6=Airflow V'nom, 7=MotorStop, 8=Pos. damper in %, 9=Airflow in %, 10=Airflow in m³/h, 11=-, 12=Temp. SP in °C, 13=CO2 SP in ppm"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "SystemMode",
   "description": "System mode (default Active)",
   "units": "",
   "access": "W",
   "states": "1=Off, 2=Active, 3=Eco, 4=Boost"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "ApplicationSel",
   "description": "VAV zone application selection",
   "units": "",
   "access": "W",
   "states": "1=none, 2=c, 3=c/h, 4=c+el-rh1, 5=c+el-rh2, 6=c+on/off-rh, 7=c+mod-rh, 8=CO2, 9=VAV, 10=c+p-f, 11=c+p-f+el-rh1, 12=c+p-f+el-rh2, 13=c+p-f+on/off-rh, 14=c+p-f+mod-rh, 15=c+s-f, 16=c/h+s-f, 17=c+s-f+el-rh1, 18=c+s-f+el-rh2, 19=c+s-f+on/off-rh, 20=c+s-f+mod-rh"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "PowerOnMode",
   "description": "Action at power-on (default Synchronization)",
   "units": "",
   "access": "W",
   "states": "1=No action, 2=Synchronization, 3=Adaptation"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "RUDisplaySet",
   "description": "Room unit display setting (22RT-A00.. units)",
   "units": "",
   "access": "R",
   "states": "1=Room temp. and setpoint display, 2=Setpoint display only, 3=Room temperature only"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "ReheatEn",
   "description": "When reheat is allowed (default heating only)",
   "units": "",
   "access": "W",
   "states": "1=Always allowed, 2=Allowed in heating mode only, 3=Allowed in cooling mode only, 4=Never allowed"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "CtrlRefVal",
   "description": "Reference values for VAV control",
   "units": "",
   "access": "W",
   "states": "1=Temperature only, 2=Temperature and CO2 analog input, 3=Temperature and CO2 room operating unit"
  },
  {
   "type": "MV",
   "instance": 121,
   "name": "UnitSelAirFlow",
   "description": "Airflow unit for the _UnitSel objects",
   "units": "",
   "access": "W",
   "states": "1=m³/h, 2=l/s, 3=cfm"
  },
  {
   "type": "MV",
   "instance": 128,
   "name": "UnitSelTemp",
   "description": "Temperature unit for the _UnitSel objects",
   "units": "",
   "access": "W",
   "states": "1=K, 2=°C, 3=°F"
  },
  {
   "type": "MV",
   "instance": 130,
   "name": "BusFailAction",
   "description": "Action when the bus watchdog expires",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Open, 3=Close, 4=Max, 5=Min, 6=-, 7=Stop"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/belimo/zoneease-vav",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}