Pressure-independent control valve with energy meter · BACnet points list

Belimo Energy Valve V3 BACnet points list

Updated 6 November 2026

Short answer

The Energy Valve V3 is a pressure-independent characterized control valve with a flow sensor and two temperature sensors, so it reports flow, delta T, power and heating/cooling energy. It talks BACnet MS/TP or BACnet IP. AO 1 is a % setpoint read as position, flow or power depending on ControlMode (MV 100); the setpoint only follows the bus when SpSource (MV 122) is Bus.

This page lists 62 BACnet objects for the Belimo Energy Valve V3 — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
Energy Valve V3
Equipment
Pressure-independent control valve with energy meter
Equipment type
Valves & actuators
BACnet objects
62 (17 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Application 03.02-0000, firmware 12.25
Default device instance
1
Also known as
Energy Valve, EV..R+BAC, EV..R+KBAC, EV..R3+BAC, EV..F+BAC, EV..F+KBAC, Belimo Energy Valve 3
Source document
BACnet interface description, Energy Valve V3 · rev. 2026-07
Download CSV 62 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.

BMS integration notes: Belimo Energy Valve V3

Integration in brief

Set MV 122 SpSource to Bus, pick the control mode in MV 100 (flow control by default) and the flow or power limits, then command AO 1 SpRel. Read flow, temperatures, delta T, power and energy, and watch BI 101 SummaryStatus and AI 100 ErrorState for faults.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1SpRelSetpoint: position, flow or power per control modeCommand
MV 122SpSourceMust be Bus for AO 1 to take effectWrite
MV 100ControlModePosition, flow or power controlWrite
AI 11AbsFlow_lminMeasured flow, l/minRead
AI 22DeltaT_KCoil delta T, KRead
AI 30AbsPower_kWThermal power, kWRead
AI 31E_Cooling_kWhCooling energy meter, kWhRead
AI 32E_Heating_kWhHeating energy meter, kWhRead
BI 101SummaryStatusOverall OK / not OKRead
AI 100ErrorStateBit-coded error flagsRead

Enable & remote start

Write MV 122 SpSource = 2 (Bus); the default Analog (1) follows the 0-10 V signal on wire 3. MO 1 Override can force close, open, nominal or max flow/power or motor stop and falls back to None after 2 hours.

Network setup

Watch out for

Belimo Energy Valve V3 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

62 of 62 shown
Type
Access
Show
Belimo Energy Valve V3 BACnet Points List
DescriptionStates
AI1RelPosRelative position%Read
AI2AbsPosAbsolute position°Read
AI5SpAnalog_VAnalog setpointVRead
AI10RelFlowRelative flow%Read
AImin11AbsFlow_lminAbsolute flowl/minRead
AI12AbsFlow_m3hAbsolute flowm³/hRead
AI13AbsFlow_gpmAbsolute flowgpmRead
AI14AbsFlow_lsAbsolute flowl/sRead
AI15AbsFlow_lhAbsolute flowl/hRead
AI20T1_CTemperature 1 (remote sensor)°CRead
AI21T2_CTemperature 2 (embedded sensor)°CRead
AImin22DeltaT_KDelta TKRead
AI25T1_FTemperature 1 (remote sensor)°FRead
AI26T2_FTemperature 2 (embedded sensor)°FRead
AI27DeltaT_FDelta T°FRead
AImin30AbsPower_kWPowerkWRead
AImin31E_Cooling_kWhCooling energykWhRead
AImin32E_Heating_kWhHeating energykWhRead
AI33E_Cooling_MJCooling energyMJRead
AI34E_Heating_MJHeating energyMJRead
AI35AbsPower_kBTUhPowerkBTU/hRead
AI36E_Cooling_kBTUCooling energykBTURead
AI37E_Heating_kBTUHeating energykBTURead
AI40RelPowerRelative power%Read
AI45AbsPower_tonPowertonRead
AI46E_Cooling_tonhCooling energyton·hRead
AI47E_Heating_tonhHeating energyton·hRead
AI60GlycolConcentrationGlycol concentration, measured or web-server override%Read
AImin100ErrorStateBit-coded error flags (see notes)Read
AI111SpAbsFlow_lminAbsolute flow setpointl/minRead
AI112SpAbsFlow_m3hAbsolute flow setpointm³/hRead
AI113SpAbsFlow_gpmAbsolute flow setpointgpmRead
AI114SpAbsFlow_lsAbsolute flow setpointl/sRead
AI115SpAbsFlow_lhAbsolute flow setpointl/hRead
AOmin1SpRelSetpoint: position, flow or power per ControlMode%Command
AV90V'max_lminMaximum flow limitl/minWrite
AV91V'max_gpmMaximum flow limitgpmWrite
AV95P'max_kWMaximum power limitkWWrite
AV96P'max_kBTUhMaximum power limitkBTU/hWrite
AV100V'maxMaximum flow limit (30-100 %)%Write
AV101V'nom_lminNominal volume flowl/minWrite
AV102V'nom_gpmNominal volume flowgpmWrite
AV103SpDeltaT_KDelta T setpoint (default 10 K)KWrite
AV104SpDeltaT_FDelta T setpoint (default 18 °F)°FWrite
AV105P'maxMaximum power limit (0.5-100 %)%Write
AV106P'nom_kWNominal powerkWRead
AV107P'nom_kBTUhNominal powerkBTU/hRead
AV108SpFlow_DeltaT lminFlow setpoint at delta Tl/minWrite
AV109SpFlow_DeltaT gpmFlow setpoint at delta TgpmWrite
BI1SpPosReachedSetpoint position reachedRead1=No, 2=Yes
BImin101SummaryStatusSummary of MI 103 to MI 107Read1=OK, 2=Not OK
BV100RstErrCountReset error countersRead1=None, 2=Reset
MI102DeltaT_MgrStatusDelta T manager statusRead1=Not selected, 2=Standby, 3=Active, 4=Scaling standby, 5=Scaling active
MI103StatusSensorFlow and temperature sensor statusRead1=OK, 2=Flow sensor not OK, 3=T1 not OK, 4=T2 not OK
MI104StatusFlowFlow statusRead1=OK, 2=Reverse flow detected, 3=Flow not reached, 4=Flow in closed position
MI105StatusMediaMedia statusRead1=OK, 2=Airbubbles, 3=Freeze warning
MI106StatusActuatorActuator statusRead1=OK, 2=Actuator cannot move, 3=Gear disengaged
MI107StatusPowerPower control statusRead1=OK, 2=Power not reached
MO1OverrideOverride control; returns to None after 2 hoursCommand1=None, 2=Close, 3=Open, 4=V'nom, 5=V'max, 6=MotStop, 7=P'nom, 8=P'max
MVmin100ControlModeHow the setpoint is read (default Flow control)Write1=Position Control, 2=Flow Control, 3=Power Control
MV101DeltaT_LimitationDelta T manager mode (default Disabled)Write1=Disabled, 2=dT-Manager, 3=dT-Manager scaling
MVmin122SpSourceSetpoint source: analog 0-10 V or bus AO 1Write1=Analog, 2=Bus
Object ID lookup: Belimo Energy Valve V3 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Energy Valve V3 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo Energy Valve V3

How many BACnet points does the Belimo Energy Valve V3 have?

This list has 62 BACnet objects: 34 analog inputs, 1 analog output, 14 analog values, 2 binary inputs, 1 binary value, 6 multi-state inputs, 1 multi-state output, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo Energy Valve V3 BACnet points are writable?

17 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo Energy Valve V3 BACnet documentation?

The source is BACnet interface description, Energy Valve V3, revision 2026-07, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_Energy-Valve_V3_en-gb.pdf.

What are the minimum BACnet points to integrate the Belimo Energy Valve V3?

Start with AO 1 SpRel (Setpoint: position, flow or power per control mode); MV 122 SpSource (Must be Bus for AO 1 to take effect); MV 100 ControlMode (Position, flow or power control); AI 11 AbsFlow_lmin (Measured flow, l/min); AI 22 DeltaT_K (Coil delta T, K); AI 30 AbsPower_kW (Thermal power, kW); AI 31 E_Cooling_kWh (Cooling energy meter, kWh); AI 32 E_Heating_kWh (Heating energy meter, kWh); BI 101 SummaryStatus (Overall OK / not OK); AI 100 ErrorState (Bit-coded error flags).

How do I enable BMS control of the Belimo Energy Valve V3?

Write MV 122 SpSource = 2 (Bus); the default Analog (1) follows the 0-10 V signal on wire 3. MO 1 Override can force close, open, nominal or max flow/power or motor stop and falls back to None after 2 hours.

How do I check these points on the real Energy Valve V3?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: BACnet interface description, Energy Valve V3 · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.