Pressure-independent control valve with energy meter · BACnet points list
Belimo Energy Valve V3 BACnet points list
Updated 6 November 2026
The Energy Valve V3 is a pressure-independent characterized control valve with a flow sensor and two temperature sensors, so it reports flow, delta T, power and heating/cooling energy. It talks BACnet MS/TP or BACnet IP. AO 1 is a % setpoint read as position, flow or power depending on ControlMode (MV 100); the setpoint only follows the bus when SpSource (MV 122) is Bus.
This page lists 62 BACnet objects for the Belimo Energy Valve V3 — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.
- Manufacturer
- Belimo
- Model
- Energy Valve V3
- Equipment
- Pressure-independent control valve with energy meter
- Equipment type
- Valves & actuators
- BACnet objects
- 62 (17 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Application 03.02-0000, firmware 12.25
- Default device instance
- 1
- Also known as
- Energy Valve, EV..R+BAC, EV..R+KBAC, EV..R3+BAC, EV..F+BAC, EV..F+KBAC, Belimo Energy Valve 3
- Source document
- BACnet interface description, Energy Valve V3 · rev. 2026-07
Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.
BMS integration notes: Belimo Energy Valve V3
Set MV 122 SpSource to Bus, pick the control mode in MV 100 (flow control by default) and the flow or power limits, then command AO 1 SpRel. Read flow, temperatures, delta T, power and energy, and watch BI 101 SummaryStatus and AI 100 ErrorState for faults.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 1 | SpRel | Setpoint: position, flow or power per control mode | Command |
| MV 122 | SpSource | Must be Bus for AO 1 to take effect | Write |
| MV 100 | ControlMode | Position, flow or power control | Write |
| AI 11 | AbsFlow_lmin | Measured flow, l/min | Read |
| AI 22 | DeltaT_K | Coil delta T, K | Read |
| AI 30 | AbsPower_kW | Thermal power, kW | Read |
| AI 31 | E_Cooling_kWh | Cooling energy meter, kWh | Read |
| AI 32 | E_Heating_kWh | Heating energy meter, kWh | Read |
| BI 101 | SummaryStatus | Overall OK / not OK | Read |
| AI 100 | ErrorState | Bit-coded error flags | Read |
Enable & remote start
Write MV 122 SpSource = 2 (Bus); the default Analog (1) follows the 0-10 V signal on wire 3. MO 1 Override can force close, open, nominal or max flow/power or motor stop and falls back to None after 2 hours.
Network setup
- Default device instance 1 (writable, 0-4194302).
- MS/TP: baud 9600-76800, default 38400; address 0-127, default 1; max 32 nodes without repeater; 120 ohm terminator.
- BACnet IP: UDP port 47808 by default; foreign device registration supported.
- Configure through the valve's built-in web server.
Watch out for
- Writable objects with instance 90 or above are stored persistently and should not be written cyclically.
- While air bubbles are detected the valve runs in position control regardless of MV 100.
- Max 5 active COV subscriptions, lifetime up to 12 hours.
Belimo Energy Valve V3 BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | RelPos | Relative position | % | Read | |
| AI | 2 | AbsPos | Absolute position | ° | Read | |
| AI | 5 | SpAnalog_V | Analog setpoint | V | Read | |
| AI | 10 | RelFlow | Relative flow | % | Read | |
| AImin | 11 | AbsFlow_lmin | Absolute flow | l/min | Read | |
| AI | 12 | AbsFlow_m3h | Absolute flow | m³/h | Read | |
| AI | 13 | AbsFlow_gpm | Absolute flow | gpm | Read | |
| AI | 14 | AbsFlow_ls | Absolute flow | l/s | Read | |
| AI | 15 | AbsFlow_lh | Absolute flow | l/h | Read | |
| AI | 20 | T1_C | Temperature 1 (remote sensor) | °C | Read | |
| AI | 21 | T2_C | Temperature 2 (embedded sensor) | °C | Read | |
| AImin | 22 | DeltaT_K | Delta T | K | Read | |
| AI | 25 | T1_F | Temperature 1 (remote sensor) | °F | Read | |
| AI | 26 | T2_F | Temperature 2 (embedded sensor) | °F | Read | |
| AI | 27 | DeltaT_F | Delta T | °F | Read | |
| AImin | 30 | AbsPower_kW | Power | kW | Read | |
| AImin | 31 | E_Cooling_kWh | Cooling energy | kWh | Read | |
| AImin | 32 | E_Heating_kWh | Heating energy | kWh | Read | |
| AI | 33 | E_Cooling_MJ | Cooling energy | MJ | Read | |
| AI | 34 | E_Heating_MJ | Heating energy | MJ | Read | |
| AI | 35 | AbsPower_kBTUh | Power | kBTU/h | Read | |
| AI | 36 | E_Cooling_kBTU | Cooling energy | kBTU | Read | |
| AI | 37 | E_Heating_kBTU | Heating energy | kBTU | Read | |
| AI | 40 | RelPower | Relative power | % | Read | |
| AI | 45 | AbsPower_ton | Power | ton | Read | |
| AI | 46 | E_Cooling_tonh | Cooling energy | ton·h | Read | |
| AI | 47 | E_Heating_tonh | Heating energy | ton·h | Read | |
| AI | 60 | GlycolConcentration | Glycol concentration, measured or web-server override | % | Read | |
| AImin | 100 | ErrorState | Bit-coded error flags (see notes) | Read | ||
| AI | 111 | SpAbsFlow_lmin | Absolute flow setpoint | l/min | Read | |
| AI | 112 | SpAbsFlow_m3h | Absolute flow setpoint | m³/h | Read | |
| AI | 113 | SpAbsFlow_gpm | Absolute flow setpoint | gpm | Read | |
| AI | 114 | SpAbsFlow_ls | Absolute flow setpoint | l/s | Read | |
| AI | 115 | SpAbsFlow_lh | Absolute flow setpoint | l/h | Read | |
| AOmin | 1 | SpRel | Setpoint: position, flow or power per ControlMode | % | Command | |
| AV | 90 | V'max_lmin | Maximum flow limit | l/min | Write | |
| AV | 91 | V'max_gpm | Maximum flow limit | gpm | Write | |
| AV | 95 | P'max_kW | Maximum power limit | kW | Write | |
| AV | 96 | P'max_kBTUh | Maximum power limit | kBTU/h | Write | |
| AV | 100 | V'max | Maximum flow limit (30-100 %) | % | Write | |
| AV | 101 | V'nom_lmin | Nominal volume flow | l/min | Write | |
| AV | 102 | V'nom_gpm | Nominal volume flow | gpm | Write | |
| AV | 103 | SpDeltaT_K | Delta T setpoint (default 10 K) | K | Write | |
| AV | 104 | SpDeltaT_F | Delta T setpoint (default 18 °F) | °F | Write | |
| AV | 105 | P'max | Maximum power limit (0.5-100 %) | % | Write | |
| AV | 106 | P'nom_kW | Nominal power | kW | Read | |
| AV | 107 | P'nom_kBTUh | Nominal power | kBTU/h | Read | |
| AV | 108 | SpFlow_DeltaT lmin | Flow setpoint at delta T | l/min | Write | |
| AV | 109 | SpFlow_DeltaT gpm | Flow setpoint at delta T | gpm | Write | |
| BI | 1 | SpPosReached | Setpoint position reached | Read | 1=No, 2=Yes | |
| BImin | 101 | SummaryStatus | Summary of MI 103 to MI 107 | Read | 1=OK, 2=Not OK | |
| BV | 100 | RstErrCount | Reset error counters | Read | 1=None, 2=Reset | |
| MI | 102 | DeltaT_MgrStatus | Delta T manager status | Read | 1=Not selected, 2=Standby, 3=Active, 4=Scaling standby, 5=Scaling active | |
| MI | 103 | StatusSensor | Flow and temperature sensor status | Read | 1=OK, 2=Flow sensor not OK, 3=T1 not OK, 4=T2 not OK | |
| MI | 104 | StatusFlow | Flow status | Read | 1=OK, 2=Reverse flow detected, 3=Flow not reached, 4=Flow in closed position | |
| MI | 105 | StatusMedia | Media status | Read | 1=OK, 2=Airbubbles, 3=Freeze warning | |
| MI | 106 | StatusActuator | Actuator status | Read | 1=OK, 2=Actuator cannot move, 3=Gear disengaged | |
| MI | 107 | StatusPower | Power control status | Read | 1=OK, 2=Power not reached | |
| MO | 1 | Override | Override control; returns to None after 2 hours | Command | 1=None, 2=Close, 3=Open, 4=V'nom, 5=V'max, 6=MotStop, 7=P'nom, 8=P'max | |
| MVmin | 100 | ControlMode | How the setpoint is read (default Flow control) | Write | 1=Position Control, 2=Flow Control, 3=Power Control | |
| MV | 101 | DeltaT_Limitation | Delta T manager mode (default Disabled) | Write | 1=Disabled, 2=dT-Manager, 3=dT-Manager scaling | |
| MVmin | 122 | SpSource | Setpoint source: analog 0-10 V or bus AO 1 | Write | 1=Analog, 2=Bus |
No points match these filters.
Object ID lookup: Belimo Energy Valve V3 point IDs by name
AI1RelPosAI2AbsPosAI5SpAnalog_VAI10RelFlowAI11AbsFlow_lminAI12AbsFlow_m3hAI13AbsFlow_gpmAI14AbsFlow_lsAI15AbsFlow_lhAI20T1_CAI21T2_CAI22DeltaT_KAI25T1_FAI26T2_FAI27DeltaT_FAI30AbsPower_kWAI31E_Cooling_kWhAI32E_Heating_kWhAI33E_Cooling_MJAI34E_Heating_MJAI35AbsPower_kBTUhAI36E_Cooling_kBTUAI37E_Heating_kBTUAI40RelPowerAI45AbsPower_tonAI46E_Cooling_tonhAI47E_Heating_tonhAI60GlycolConcentrationAI100ErrorStateAI111SpAbsFlow_lminAI112SpAbsFlow_m3hAI113SpAbsFlow_gpmAI114SpAbsFlow_lsAI115SpAbsFlow_lhAO1SpRelAV90V'max_lminAV91V'max_gpmAV95P'max_kWAV96P'max_kBTUhAV100V'maxAV101V'nom_lminAV102V'nom_gpmAV103SpDeltaT_KAV104SpDeltaT_FAV105P'maxAV106P'nom_kWAV107P'nom_kBTUhAV108SpFlow_DeltaT lminAV109SpFlow_DeltaT gpmBI1SpPosReachedBI101SummaryStatusBV100RstErrCountMI102DeltaT_MgrStatusMI103StatusSensorMI104StatusFlowMI105StatusMediaMI106StatusActuatorMI107StatusPowerMO1OverrideMV100ControlModeMV101DeltaT_LimitationMV122SpSource
Integration notes
- This is the older V3 object map; Energy Valve V4 uses a different, larger list.
- Flow, power and energy are each published in several units (l/min, m³/h, gpm, l/s, l/h; kW, kBTU/h, ton; kWh, MJ, kBTU, ton·h).
- AI 100 ErrorState bits: 0 sensor T1, 1 sensor T2, 2 flow sensor, 3 actuator cannot move, 4 flow with closed valve, 5 air bubbles, 6 flow not reached, 7 power not realized, 8 gear disengaged, 9 reverse flow, 10 MP communication faulty, 11 freeze warning.
- Value ranges may be limited further by the valve size (DN); see the product datasheet.
- Binary objects print state texts as 1/2 (No/Yes, OK/Not OK, None/Reset); kept as printed. BV 100 is printed with read access.
- Names printed with superscripts are written out here (AbsFlow_m3h for 'AbsFlow_m³h', V'max for V' with subscript max).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Energy Valve V3 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Belimo Energy Valve V3
How many BACnet points does the Belimo Energy Valve V3 have?
This list has 62 BACnet objects: 34 analog inputs, 1 analog output, 14 analog values, 2 binary inputs, 1 binary value, 6 multi-state inputs, 1 multi-state output, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Belimo Energy Valve V3 BACnet points are writable?
17 of the 62 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Belimo Energy Valve V3 BACnet documentation?
The source is BACnet interface description, Energy Valve V3, revision 2026-07, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_Energy-Valve_V3_en-gb.pdf.
What are the minimum BACnet points to integrate the Belimo Energy Valve V3?
Start with AO 1 SpRel (Setpoint: position, flow or power per control mode); MV 122 SpSource (Must be Bus for AO 1 to take effect); MV 100 ControlMode (Position, flow or power control); AI 11 AbsFlow_lmin (Measured flow, l/min); AI 22 DeltaT_K (Coil delta T, K); AI 30 AbsPower_kW (Thermal power, kW); AI 31 E_Cooling_kWh (Cooling energy meter, kWh); AI 32 E_Heating_kWh (Heating energy meter, kWh); BI 101 SummaryStatus (Overall OK / not OK); AI 100 ErrorState (Bit-coded error flags).
How do I enable BMS control of the Belimo Energy Valve V3?
Write MV 122 SpSource = 2 (Bus); the default Analog (1) follows the 0-10 V signal on wire 3. MO 1 Override can force close, open, nominal or max flow/power or motor stop and falls back to None after 2 hours.
How do I check these points on the real Energy Valve V3?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Belimo BACnet points lists
- Pressure-independent control valve
Belimo 2-way EPIV V4
Belimo 2-way electronic pressure-independent valves (EPIV) version 4.2, DN 15 to 50, BACnet models EP..R2+(K)BAC.
Also known as: EPIV, EP..R2+BAC, EP..R2+KBAC, Electronic Pressure Independent Valve, 2-way EPIV DN 15-50 - Ultrasonic liquid flow sensor
Belimo 22PF Flow Sensor
Belimo 22PF-.. ultrasonic flow sensors for water and glycol pipes, interface version 4.3.0.
Also known as: 22PF, 22PF-.., Belimo ultrasonic flow sensor, Flow Sensor 22PF - 6-way pressure-independent control valve
Belimo 6-way EPIV
Belimo 6-way EPIV (EP..R-R6+BAC) used to switch and control a single coil between heating and cooling sequences.
Also known as: EP..R-R6+BAC, 6-way EPIV, 6-way characterised control valve, Belimo 6-way valve - Damper and valve actuator
Belimo Air/Water Actuators (BACnet MS/TP)
Belimo general-purpose damper and valve actuators with the BACnet MS/TP interface (rotary, linear and fail-safe types).
Also known as: Belimo air/water actuator, Belimo AirWater BACnet, ..M(C)24A, ..R24A, ..V(K)24A, ..F24A, ..RF24A - Duct / outdoor sensors (temperature, humidity, CO2, VOC, differential pressure)
Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet
Belimo BACnet MS/TP sensors: 22DTH duct temperature/humidity, 22UTH outdoor temperature/humidity, 22DTM duct CO2/VOC and 22ADP differential pressure/airflow sensors.
Also known as: 22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.., 22DTH-16M, 22DTH-56M, 22UTH-160X, 22UTH-560X, 22DTM-16, 22DTM-56, 22ADP-164, 22ADP-164L, 22ADP-56Q, 22ADP-56QB, 22ADP-564L, 22ADP-566L - Pressure-independent control valve with energy meter
Belimo Energy Valve V4
Belimo Energy Valve version 4, DN 15 to 50, BACnet models EV..R2+(K)BAC, EV..R2+MID and EV..R3+BAC.
Also known as: Energy Valve, EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Belimo Energy Valve 4 - Fire and smoke damper actuator test module
Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module
Belimo FSKN120-BAC and FSKN24-BAC remote test modules for spring-return fire and combination fire/smoke damper actuators (FSTF, FSLF, FSNF, FSAFB, FSAF*A) in containment applications.
Also known as: FSKN120-BAC, FSKN24-BAC, FSKN, Belimo FSKN BACnet - Valve actuator (Ethernet, IoT)
Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)
Belimo IoT product range valve actuators VLM/VLR, VNM/VNR, VSM/VSR and VGM/VGR 24A-LP1 with Ethernet and BACnet IP.
Also known as: VLM24A-LP1, VLR24A-LP1, VNM24A-LP1, VNR24A-LP1, VSM24A-LP1, VSR24A-LP1, VGM24A-LP1, VGR24A-LP1, Belimo IoT Product Range - Butterfly valve actuator
Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo JR rotary actuators for butterfly valves in the BACnet MS/TP version (JR..A-BAC-..).
Also known as: JR actuator, JR..A-BAC-.., Belimo JR BACnet, JR/QR - Butterfly valve actuator
Belimo PR..-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo PR rotary actuators for butterfly valves in the BACnet MS/TP version (PR..-BAC-..).
Also known as: PR..-BAC-.., Belimo PR actuator, PR BACnet - Room sensor / operating unit
Belimo Room Operating Unit 22RT-5U00
Belimo 22RT...-5U00... room operating units with virtual or ePaper touch display, measuring temperature, humidity and CO2.
Also known as: 22RT, 22RT…-5U00…, Room Operating Unit, ROU, 22RTM-5U00, Belimo room sensor BACnet - Thermal (BTU) energy meter
Belimo Thermal Energy Meter V4
Belimo Thermal Energy Meters version 4, DN 15 to 50 (22PE..-1U.., including MID-certified 22PEM models).
Also known as: TEM, Thermal Energy Meter, 22PE-1U, 22PEM-1UC, 22PE…-1U.., Belimo energy meter - VAV compact controller (actuator with flow sensor)
Belimo VAV-Compact
Belimo VAV-Compact volumetric flow controllers with the BACnet/Modbus interface (..MV-D3-MOD and ..HV24A-MOD).
Also known as: VAV-Compact MOD, ..MV-D3-MOD, ..HV24A-MOD, LMV-D3-MOD, NMV-D3-MOD, SMV-D3-MOD, LHV24A-MOD - VAV / CAV / pressure controller
Belimo VAV-Universal VRU
Belimo VAV-Universal controllers VRU-D3-BAC, VRU-M1-BAC and VRU-M1R-BAC used for VAV/CAV airflow, duct pressure and room pressure control.
Also known as: VAV-Universal, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-..-BAC - VAV zone controller / actuator
Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)
Belimo ZoneEase VAV actuators LMV-BAC-.. and NMV-BAC-.. with the built-in zone control applications, application software ZoneEase 1.7.
Also known as: ZoneEase VAV, LMV-BAC-.., NMV-BAC-.., Belimo ZoneEase
Source: BACnet interface description, Energy Valve V3 · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.