Easy BACnet
  1. Home
  2. BACnet points lists
  3. Belimo
  4. JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)

Butterfly valve actuator · BACnet points list

Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The JR..A-BAC-.. is a Belimo rotary actuator for butterfly valves with BACnet MS/TP on board. The BMS writes a % setpoint to AO 1 and reads position and status; two extra sensor inputs (0-10 V, passive temperature or switch) can be read over the bus. The setpoint can also come from a 0-10 V signal, chosen with SpSource (MV 122).

This page lists 26 BACnet objects for the Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Belimo’s own free documentation, linked below.

Manufacturer
Belimo
Model
JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Equipment
Butterfly valve actuator
Equipment type
Valves & actuators
BACnet objects
26 (13 writable)
Transport
BACnet MS/TP
Firmware
Application JR/QR 1.6.0001
Also known as
JR actuator, JR..A-BAC-.., Belimo JR BACnet, JR/QR
Source document
BACnet Interface Description, JR actuator (rotary actuator for butterfly valves) · V1.06 · rev. 2026-01
Download CSV 26 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.

BMS integration notes: Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)

Integration in brief

Set MV 122 SpSource to Bus and command AO 1 SpRel. Read AI 1 position and MV 99 summary status. The bus watchdog (AV 130, default 120 s) needs AO 1 or MV 1 to be rewritten within the timeout.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1SpRelValve setpoint, % (up to Max, AV 98)Command
MV 122SpSourceMust be Bus for AO 1 to take effectWrite
AI 1RelPosValve position feedbackRead
MV 99SummaryStatusOK / warning / not OK summaryRead

Enable & remote start

MV 122 SpSource selects the setpoint: Analog (1, default) follows the 0-10 V signal on wire 3; Bus (2) uses AO 1. MV 1 Override can force Open, Close, Mid or Max.

Heartbeat & communication loss

AV 130 BusWatchdog, 5-3600 s, default 120 s. If neither AO 1 nor MV 1 is rewritten within the timeout the actuator runs the action in MV 130 BusFailAction (default None) and MV 135 shows Bus Watchdog active.

Network setup

Watch out for

Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

26 of 26 shown
Type
Multi-state
Access
Show
Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1RelPosRelative position%Read
AI6SpAnalogAnalog setpoint when SpSource is Analog%Read
AI20Sens1Active_VoltSensor 1 as voltage (active sensor)VRead
AI21Sens1Passive_OhmSensor 1 as resistance (passive sensor)ΩRead
AI34Sens2Active_VoltSensor 2 as voltage (active sensor)VRead
AI35Sens2Passive_OhmSensor 2 as resistance (passive sensor)ΩRead
AOmin1SpRelBus setpoint, used when SpSource is Bus%Command
AV2AbsPosAbsolute position°Read
AV20Sens1Temp_UnitSelSensor 1 temperature in the unit set by MV 127Read
AV24Sens2Temp_UnitSelSensor 2 temperature in the unit set by MV 127Read
AV98MaxMaximum limit, at least 30 %%Write
AV130BusWatchdogBus watchdog timeout (5-3600 s, default 120)sWrite
BI20Sens1SwitchSensor 1 as switch inputWrite0=Inactive, 1=Active
BI21Sens2SwitchSensor 2 as switch inputWrite0=Inactive, 1=Active
BV99BusTerminationBus termination enabledRead0=Disabled, 1=Enabled
MV1OverrideOverride the setpoint with fixed positionsWrite1=None, 2=Open, 3=Close, 4=-, 5=Mid, 6=Max, 7-14=-
MVmin99SummaryStatusSummary of all statusRead1=OK, 2=Warning, 3=Not OK
MV106StatusActuatorActuator statusRead1=OK, 2=Mechanical overload, 3=Gear train disengaged / hand crank plugged, 4=-
MVmin122SpSourceSetpoint source: analog 0-10 V or bus AO 1Write1=Analog, 2=Bus
MV127UnitSelTemperatureTemperature unit for AV 20 and AV 24Write1=°C, 2=K, 3=°F
MV130BusFailActionAction when the bus watchdog expiresWrite1=None, 2=Open, 3=Close, 4=Max, 5=-, 6=Mid, 7-14=-
MV135StatusBusWatchdogBus watchdog statusRead1=OK, 2=Bus Watchdog active
MV220Sens1TypeSensor 1 typeWrite1=None, 2=Active Volt, 3=-, 4=Passive, 5=Switch
MV221Sens1TempTypeSensor 1 passive typeWrite1=None, 2=PT1000, 3=Ni1000EU, 4=-, 5=-, 6=-, 7=-, 8=NTC10k2, 9=NTC10k3
MV222Sens2TypeSensor 2 typeWrite1=None, 2=Active Volt, 3=-, 4=Passive, 5=Switch
MV223Sens2TempTypeSensor 2 passive typeWrite1=None, 2=PT1000, 3=Ni1000EU, 4=-, 5=-, 6=-, 7=-, 8=NTC10k2, 9=NTC10k3
Object ID lookup: Belimo JR Butterfly Valve Actuator point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)

How many BACnet points does the Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP) have?

This list has 26 BACnet objects: 6 analog inputs, 1 analog output, 5 analog values, 2 binary inputs, 1 binary value, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP) BACnet points are writable?

13 of the 26 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP) BACnet documentation?

The source is BACnet Interface Description, JR actuator (rotary actuator for butterfly valves) (V1.06), revision 2026-01, published free by Belimo at https://www.belimo.com/mam/general-documents/system_integration/BACnet/belimo_BACnet_Interface-description_JR_V1_6_en-gb.pdf.

What are the minimum BACnet points to integrate the Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)?

Start with AO 1 SpRel (Valve setpoint, % (up to Max, AV 98)); MV 122 SpSource (Must be Bus for AO 1 to take effect); AI 1 RelPos (Valve position feedback); MV 99 SummaryStatus (OK / warning / not OK summary).

How do I enable BMS control of the Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)?

MV 122 SpSource selects the setpoint: Analog (1, default) follows the 0-10 V signal on wire 3; Bus (2) uses AO 1. MV 1 Override can force Open, Close, Mid or Max.

Does the Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

AV 130 BusWatchdog, 5-3600 s, default 120 s. If neither AO 1 nor MV 1 is rewritten within the timeout the actuator runs the action in MV 130 BusFailAction (default None) and MV 135 shows Bus Watchdog active.

How do I check these points on the real JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Belimo BACnet points lists

Source: BACnet Interface Description, JR actuator (rotary actuator for butterfly valves) · V1.06 · rev. 2026-01. Object names, instances and units are reproduced as published; descriptions are our own.