Gas detection sensor / monitor · BACnet points list
Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others) BACnet points list
Updated 12 November 2026Unofficial source
Belimo 22G gas monitors measure one or two gases and drive local relays and alarms. The -A and -B models have a BACnet MS/TP port that serves the local gas readings, ambient temperature, an auxiliary input and the alarm/relay states. With menu setting 46 = 2 one monitor also acts as a gateway and publishes the gas readings of every monitor on its CAN bus.
This page lists 7 BACnet objects for the Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Belimo’s documentation hosted by ZOT Supply, not by Belimo itself, so treat it as unofficial.
- Manufacturer
- Belimo
- Model
- Gas monitors 22G (CO, NO2, CO2, refrigerant and others)
- Equipment
- Gas detection sensor / monitor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 7 (3 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- 22G, 22G02-5A, 22G02-5B, 22G14-5A, 22G14-5B, 22G0214-5A, 22G0214-5B, Belimo gas monitor BACnet, Belimo CO monitor
- Source document
- Belimo Gas Monitors Operating Manual, 6.2 PICS: BACnet MS/TP · rev. 04/26 (unofficial copy, hosted by ZOT Supply)
Reference only, provided as-is: verify against Belimo’s current documentation and the live device before use. Not official Belimo information. Terms of use.
BMS integration notes: Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others)
Turn on BACnet with menu setting 46, set the MS/TP address, baud and device instance at the keypad, then read the gas readings and the three alarm objects. Use setting 46 = 2 on one -A or -B monitor to bring a whole CAN bus network into the BMS.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 0 | Gas Reading 1 | Gas reading, sensor A | Read |
| AV 1 | Gas Reading 2 | Gas reading, sensor B (dual-gas models) | Read |
| BO 0 | Relay 1 / Alarm L1 | Alarm 1 / relay 1 state | Write |
| BO 1 | Relay 2 / Alarm L2 | Alarm 2 / relay 2 state | Write |
| BO 2 | Alarm 3 | Alarm 3 state | Write |
Enable & remote start
Menu setting 46: 0 = BACnet off, 1 = BACnet on, 2 = BACnet on plus all CAN bus gas readings.
Network setup
- MS/TP address 0-127, set at the keypad.
- Baud 9600, 19200, 38400 or 76800; power cycle after a change.
- Device instance is entered in two parts at the keypad (1000-4,194,303, then 0-999).
- Set the maximum MAC address no lower than the highest address on the network, or devices are hidden.
- EOL jumpers go ON only on the first and last devices.
Watch out for
- Gas reading objects appear only when menu setting 46 is 1 or 2.
- A menu setting can make CAN bus alarms and relays follow BACnet alarms on the gateway monitor.
Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 0 | Gas Reading 1 | Sensor A (top) gas reading; menu setting 46 = 1 | Read | ||
| AVmin | 1 | Gas Reading 2 | Sensor B (bottom) gas reading; menu setting 46 = 1 | Read | ||
| AV | 2 | Ambient Temp. | Ambient temperature, °C or °F | Read | ||
| BI | 0 | Input 1 | Auxiliary input state | Read | 0/1 | |
| BOmin | 0 | Relay 1 / Alarm L1 | Alarm 1 and relay 1 status | Write | 0/1 | |
| BOmin | 1 | Relay 2 / Alarm L2 | Alarm 2 and relay 2 status | Write | 0/1 | |
| BOmin | 2 | Alarm 3 | Alarm 3 status | Write | 0/1 |
No points match these filters.
Object ID lookup: Belimo Gas monitors 22G point IDs by name
Integration notes
- Only the fixed objects are listed. With menu setting 46 = 2, each CAN bus monitor adds 'AV XYY - Gas reading XYY', where X = 1 for sensor A (top) or 2 for sensor B (bottom) and YY = the CAN bus address.
- AV 0 and AV 1 are for setting 46 = 1; AV 1 needs a second sensor.
- Each gas reading object carries the gas type and scale in its description.
- BACnet MS/TP is only on -A and -B models; -C models are CAN bus only.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Gas monitors 22G (CO, NO2, CO2, refrigerant and others) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others)
How many BACnet points does the Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others) have?
This list has 7 BACnet objects: 3 analog values, 1 binary input, 3 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others) BACnet points are writable?
3 of the 7 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others) BACnet documentation?
Belimo does not publish it on its own website. This list comes from Belimo Gas Monitors Operating Manual, 6.2 PICS: BACnet MS/TP, revision 04/26, a copy hosted by ZOT Supply at https://www.zotsupply.com/content/PDFs/Belimo/Gas%20Monitoring/belimo_gas-monitor_operations-manual_en-us.pdf. Ask Belimo or its representative for the current revision.
What are the minimum BACnet points to integrate the Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others)?
Start with AV 0 Gas Reading 1 (Gas reading, sensor A); AV 1 Gas Reading 2 (Gas reading, sensor B (dual-gas models)); BO 0 Relay 1 / Alarm L1 (Alarm 1 / relay 1 state); BO 1 Relay 2 / Alarm L2 (Alarm 2 / relay 2 state); BO 2 Alarm 3 (Alarm 3 state).
How do I enable BMS control of the Belimo Gas monitors 22G (CO, NO2, CO2, refrigerant and others)?
Menu setting 46: 0 = BACnet off, 1 = BACnet on, 2 = BACnet on plus all CAN bus gas readings.
How do I check these points on the real Gas monitors 22G (CO, NO2, CO2, refrigerant and others)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Belimo BACnet points lists
- Pressure-independent control valve
Belimo 2-way EPIV V4
Belimo 2-way electronic pressure-independent valves (EPIV) version 4.2, DN 15 to 50, BACnet models EP..R2+(K)BAC.
Also known as: EPIV, EP..R2+BAC, EP..R2+KBAC, Electronic Pressure Independent Valve, 2-way EPIV DN 15-50 - Ultrasonic liquid flow sensor
Belimo 22PF Flow Sensor
Belimo 22PF-.. ultrasonic flow sensors for water and glycol pipes, interface version 4.3.0.
Also known as: 22PF, 22PF-.., Belimo ultrasonic flow sensor, Flow Sensor 22PF - 6-way pressure-independent control valve
Belimo 6-way EPIV
Belimo 6-way EPIV (EP..R-R6+BAC) used to switch and control a single coil between heating and cooling sequences.
Also known as: EP..R-R6+BAC, 6-way EPIV, 6-way characterised control valve, Belimo 6-way valve - 6-way pressure-independent zone valve
Belimo 6-way PI zone valve (C6..QP..+BAC)
Belimo 6-way pressure-independent zone valves C615QP-B/D/F+BAC and C620QPT-G+BAC, application 6-Way-PIQCV V1.0, on BACnet MS/TP.
Also known as: C6..QP(T)-..+BAC, C615QP-B+BAC, C615QP-D+BAC, C615QP-F+BAC, C620QPT-G+BAC, 6-Way-PIQCV, 6-way PI zone valve, Belimo 6-way PIQCV - Damper and valve actuator
Belimo Air/Water Actuators (BACnet MS/TP)
Belimo general-purpose damper and valve actuators with the BACnet MS/TP interface (rotary, linear and fail-safe types).
Also known as: Belimo air/water actuator, Belimo AirWater BACnet, ..M(C)24A, ..R24A, ..V(K)24A, ..F24A, ..RF24A - Fire damper actuator interface
Belimo BKN230-24-MOD fire damper communication and power unit
Belimo BKN230-24-MOD unit that powers and networks one motorised fire damper actuator (BF24..-ST, BFN24..-ST, BFL24..-ST).
Also known as: BKN230-24-MOD, BKN230-24-MOD-BAC, BKN230, Belimo BKN230 BACnet, Schako BKN230, 71589-00002 - Zone valve actuator
Belimo CQ24A-BAC CQ zone rotary actuator
Belimo CQ24A-BAC rotary actuator for CQ zone valves, BACnet MS/TP application version 01.05.0001.
Also known as: CQ24A-BAC, CQ Zone Rotary Actuator, Belimo CQ BACnet, ZoneTight CQ actuator - Duct / outdoor sensors (temperature, humidity, CO2, VOC, differential pressure)
Belimo Duct and Pipe Sensors (22DTH, 22UTH, 22DTM, 22ADP) BACnet
Belimo BACnet MS/TP sensors: 22DTH duct temperature/humidity, 22UTH outdoor temperature/humidity, 22DTM duct CO2/VOC and 22ADP differential pressure/airflow sensors.
Also known as: 22DTH-..6.., 22UTH-..60X, 22DTM-..6, 22ADP-..6.., 22DTH-16M, 22DTH-56M, 22UTH-160X, 22UTH-560X, 22DTM-16, 22DTM-56, 22ADP-164, 22ADP-164L, 22ADP-56Q, 22ADP-56QB, 22ADP-564L, 22ADP-566L - Pressure-independent control valve with energy meter
Belimo Energy Valve V3
Belimo Energy Valve generation 3 (EV..R+(K)BAC, EV..R3+BAC, EV..F+(K)BAC), the installed base before Energy Valve V4.
Also known as: Energy Valve, EV..R+BAC, EV..R+KBAC, EV..R3+BAC, EV..F+BAC, EV..F+KBAC, Belimo Energy Valve 3 - Pressure-independent control valve with energy meter
Belimo Energy Valve V4
Belimo Energy Valve version 4, DN 15 to 50, BACnet models EV..R2+(K)BAC, EV..R2+MID and EV..R3+BAC.
Also known as: Energy Valve, EV..R2+BAC, EV..R2+KBAC, EV..R2+MID, EV..R3+BAC, Belimo Energy Valve 4 - Fire and smoke damper actuator test module
Belimo FSKN120-BAC / FSKN24-BAC fire and smoke damper test module
Belimo FSKN120-BAC and FSKN24-BAC remote test modules for spring-return fire and combination fire/smoke damper actuators (FSTF, FSLF, FSNF, FSAFB, FSAF*A) in containment applications.
Also known as: FSKN120-BAC, FSKN24-BAC, FSKN, Belimo FSKN BACnet - Valve actuator (Ethernet, IoT)
Belimo IoT Valve Actuators VxM24A-LP1 / VxR24A-LP1 (BACnet IP)
Belimo IoT product range valve actuators VLM/VLR, VNM/VNR, VSM/VSR and VGM/VGR 24A-LP1 with Ethernet and BACnet IP.
Also known as: VLM24A-LP1, VLR24A-LP1, VNM24A-LP1, VNR24A-LP1, VSM24A-LP1, VSR24A-LP1, VGM24A-LP1, VGR24A-LP1, Belimo IoT Product Range - Butterfly valve actuator
Belimo JR..A-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo JR rotary actuators for butterfly valves in the BACnet MS/TP version (JR..A-BAC-..).
Also known as: JR actuator, JR..A-BAC-.., Belimo JR BACnet, JR/QR - Butterfly valve actuator
Belimo PR..-BAC-.. Butterfly Valve Actuator (BACnet MS/TP)
Belimo PR rotary actuators for butterfly valves in the BACnet MS/TP version (PR..-BAC-..).
Also known as: PR..-BAC-.., Belimo PR actuator, PR BACnet - Room sensor / operating unit
Belimo Room Operating Unit 22RT-5U00
Belimo 22RT...-5U00... room operating units with virtual or ePaper touch display, measuring temperature, humidity and CO2.
Also known as: 22RT, 22RT…-5U00…, Room Operating Unit, ROU, 22RTM-5U00, Belimo room sensor BACnet - Thermal (BTU) energy meter
Belimo Thermal Energy Meter V4
Belimo Thermal Energy Meters version 4, DN 15 to 50 (22PE..-1U.., including MID-certified 22PEM models).
Also known as: TEM, Thermal Energy Meter, 22PE-1U, 22PEM-1UC, 22PE…-1U.., Belimo energy meter - VAV compact controller (actuator with flow sensor)
Belimo VAV-Compact
Belimo VAV-Compact volumetric flow controllers with the BACnet/Modbus interface (..MV-D3-MOD and ..HV24A-MOD).
Also known as: VAV-Compact MOD, ..MV-D3-MOD, ..HV24A-MOD, LMV-D3-MOD, NMV-D3-MOD, SMV-D3-MOD, LHV24A-MOD - VAV / CAV / pressure controller
Belimo VAV-Universal VRU
Belimo VAV-Universal controllers VRU-D3-BAC, VRU-M1-BAC and VRU-M1R-BAC used for VAV/CAV airflow, duct pressure and room pressure control.
Also known as: VAV-Universal, VRU-D3-BAC, VRU-M1-BAC, VRU-M1R-BAC, VRU-..-BAC - Rooftop unit economizer controller
Belimo ZIP Economizer (ECON-ZIP-BASE + ECON-ZIP-COM)
Belimo ZIP Economizer controllers for packaged rooftop units (ECON-ZIP-BASE) with the ECON-ZIP-COM communication module for BACnet MS/TP.
Also known as: ZIP Economizer, ECON-ZIP-BASE, ECON-ZIP-COM, ECON-ZIP-EM, Belimo economizer controller BACnet, ZIP Economizer BACnet - VAV zone controller / actuator
Belimo ZoneEase VAV zone control actuator (BACnet MS/TP)
Belimo ZoneEase VAV actuators LMV-BAC-.. and NMV-BAC-.. with the built-in zone control applications, application software ZoneEase 1.7.
Also known as: ZoneEase VAV, LMV-BAC-.., NMV-BAC-.., Belimo ZoneEase
Source: Belimo Gas Monitors Operating Manual, 6.2 PICS: BACnet MS/TP · rev. 04/26. Object names, instances and units are reproduced as published; descriptions are our own.