 "manufacturer": "Belimo",
 "manufacturer_slug": "belimo",
 "model": "Gas monitors 22G (CO, NO2, CO2, refrigerant and others)",
 "model_slug": "gas-monitor-22g",
 "aliases": [
  "22G",
  "22G02-5A",
  "22G02-5B",
  "22G14-5A",
  "22G14-5B",
  "22G0214-5A",
  "22G0214-5B",
  "Belimo gas monitor BACnet",
  "Belimo CO monitor"
 ],
 "equipment_type": "Gas detection sensor / monitor",
 "applies_to": "Belimo 22G..-5A and 22G..-5B wall gas monitors (CO, NO2, CO2, NH3, refrigerant and other gases) with CAN bus and BACnet MS/TP.",
 "summary": "Belimo 22G gas monitors measure one or two gases and drive local relays and alarms. The -A and -B models have a BACnet MS/TP port that serves the local gas readings, ambient temperature, an auxiliary input and the alarm/relay states. With menu setting 46 = 2 one monitor also acts as a gateway and publishes the gas readings of every monitor on its CAN bus.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Only the fixed objects are listed. With menu setting 46 = 2, each CAN bus monitor adds 'AV XYY - Gas reading XYY', where X = 1 for sensor A (top) or 2 for sensor B (bottom) and YY = the CAN bus address.",
  "AV 0 and AV 1 are for setting 46 = 1; AV 1 needs a second sensor.",
  "Each gas reading object carries the gas type and scale in its description.",
  "BACnet MS/TP is only on -A and -B models; -C models are CAN bus only."
 ],
 "integration": {
  "summary": "Turn on BACnet with menu setting 46, set the MS/TP address, baud and device instance at the keypad, then read the gas readings and the three alarm objects. Use setting 46 = 2 on one -A or -B monitor to bring a whole CAN bus network into the BMS.",
  "minimum_points": [
   {
    "ref": "AV 0",
    "name": "Gas Reading 1",
    "why": "Gas reading, sensor A"
   },
   {
    "ref": "AV 1",
    "name": "Gas Reading 2",
    "why": "Gas reading, sensor B (dual-gas models)"
   },
   {
    "ref": "BO 0",
    "name": "Relay 1 / Alarm L1",
    "why": "Alarm 1 / relay 1 state"
   },
   {
    "ref": "BO 1",
    "name": "Relay 2 / Alarm L2",
    "why": "Alarm 2 / relay 2 state"
   },
   {
    "ref": "BO 2",
    "name": "Alarm 3",
    "why": "Alarm 3 state"
   }
  ],
  "enable": "Menu setting 46: 0 = BACnet off, 1 = BACnet on, 2 = BACnet on plus all CAN bus gas readings.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "MS/TP address 0-127, set at the keypad.",
   "Baud 9600, 19200, 38400 or 76800; power cycle after a change.",
   "Device instance is entered in two parts at the keypad (1000-4,194,303, then 0-999).",
   "Set the maximum MAC address no lower than the highest address on the network, or devices are hidden.",
   "EOL jumpers go ON only on the first and last devices."
  ],
  "gotchas": [
   "Gas reading objects appear only when menu setting 46 is 1 or 2.",
   "A menu setting can make CAN bus alarms and relays follow BACnet alarms on the gateway monitor."
  ]
 },
 "source": {
  "title": "Belimo Gas Monitors Operating Manual, 6.2 PICS: BACnet MS/TP",
  "doc_number": null,
  "revision_date": "04/26",
  "url": "https://www.zotsupply.com/content/PDFs/Belimo/Gas%20Monitoring/belimo_gas-monitor_operations-manual_en-us.pdf",
  "unofficial": true,
  "host": "ZOT Supply"
 },
 "points": [
  {
   "type": "AV",
   "instance": 0,
   "name": "Gas Reading 1",
   "description": "Sensor A (top) gas reading; menu setting 46 = 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Gas Reading 2",
   "description": "Sensor B (bottom) gas reading; menu setting 46 = 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Ambient Temp.",
   "description": "Ambient temperature, °C or °F",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 0,
   "name": "Input 1",
   "description": "Auxiliary input state",
   "units": "",
   "access": "R",
   "states": "0/1"
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "Relay 1 / Alarm L1",
   "description": "Alarm 1 and relay 1 status",
   "units": "",
   "access": "W",
   "states": "0/1"
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "Relay 2 / Alarm L2",
   "description": "Alarm 2 and relay 2 status",
   "units": "",
   "access": "W",
   "states": "0/1"
  },
  {
   "type": "BO",
   "instance": 2,
   "name": "Alarm 3",
   "description": "Alarm 3 status",
   "units": "",
   "access": "W",
   "states": "0/1"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/belimo/gas-monitor-22g",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}