Easy BACnet
  1. Home
  2. BACnet points lists
  3. Greystone Energy Systems
  4. TN Series BACnet temperature sensor (BACnet MS/TP)

Temperature sensor · BACnet points list

Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The TN series are single-point temperature sensors with native BACnet MS/TP. They expose just three objects: the temperature, a calibration offset and a °C/°F units switch. The same object list is used across the TN mounting styles.

This page lists 3 BACnet objects for the Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
TN Series BACnet temperature sensor (BACnet MS/TP)
Equipment
Temperature sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
3 (2 writable)
Transport
BACnet MS/TP
Firmware
Firmware 1.0, application 1.0
Default device instance
381001
Also known as
TN, TNAP, TNDC, TNDF, TNDR, TNFL, TNGL, TNOS, TNRP, TNSO, TNAPXXXBAC, Greystone network temperature sensor
Source document
BACnet All Purpose Temperature Sensor TNAP Series - Installation Instructions · IN-GE-TNAPXXXBAC-01-01 · rev. 06/19
Download CSV 3 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP)

Integration in brief

Set the MAC on the device and let it auto-baud, then read AI 1. Pick °C or °F with BV 1 before setting any offset.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1TemperatureMeasured temperatureRead

Network setup

Watch out for

Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

3 of 3 shown
Type
Binary
Access
Show
Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1TemperatureTemperature, -40 to 100 °C / -40 to 212 °F°C / °FRead
AV1Temperature OffsetCalibration offset, ±5 °C / ±10 °F (default 0)°C / °FWrite
BV1Temperature UnitsTemperature units (default °C)Write0=°C, 1=°F
Object ID lookup: Greystone Energy Systems TN Series BACnet temperature sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the TN Series BACnet temperature sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP) have?

This list has 3 BACnet objects: 1 analog input, 1 analog value, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP) BACnet points are writable?

2 of the 3 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP) BACnet documentation?

The source is BACnet All Purpose Temperature Sensor TNAP Series - Installation Instructions (IN-GE-TNAPXXXBAC-01-01), revision 06/19, published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/Website%20Documents/TN/IN-GE-TNAPXXXBAC.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems TN Series BACnet temperature sensor (BACnet MS/TP)?

Start with AI 1 Temperature (Measured temperature).

How do I check these points on the real TN Series BACnet temperature sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: BACnet All Purpose Temperature Sensor TNAP Series - Installation Instructions · IN-GE-TNAPXXXBAC-01-01 · rev. 06/19. Object names, instances and units are reproduced as published; descriptions are our own.