Room dewpoint / humidity sensor · BACnet points list

Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The DPRC is a Greystone room sensor that measures temperature and RH and calculates dewpoint, wet bulb and enthalpy, all reported as Analog Inputs over native BACnet MS/TP. Analog Values hold offsets, barometric pressure/altitude and the display mode; two Binary Values pick the units.

This page lists 12 BACnet objects for the Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
DPRC Series room dewpoint transmitter (BACnet MS/TP)
Equipment
Room dewpoint / humidity sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
12 (7 writable)
Transport
BACnet MS/TP
Firmware
1.4 (PICS, Feb 21, 2017)
Default device instance
381001
Also known as
DPRC, DPRCB, DPRCXXXBAC, Greystone room dewpoint sensor
Source document
DPRC Series Room Dewpoint Transmitter - Setup Guide for BACnet Communication · SG-DPRCXXXBAC-01 · rev. 2017-02-21 (PICS date)
Download CSV 12 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC and baud in the menu, set the altitude or barometric pressure for the site, then read the temperature, RH and dewpoint AIs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3Dewpoint TemperatureRoom dewpointRead
AI 1TemperatureRoom temperatureRead
AI 2Relative HumidityRoom RHRead

Network setup

Watch out for

Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

12 of 12 shown
Type
Binary
Access
Show
Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1TemperatureTemperature, -30 to 50 °C°C / °FRead
AImin2Relative HumidityRelative humidity, 0-100 %%RHRead
AImin3Dewpoint TemperatureCalculated dewpoint°C / °FRead
AI4Wet Bulb TemperatureCalculated wet bulb temperature°C / °FRead
AI5EnthalpyCalculated enthalpykJ/kg / BTU/lbRead
AV1Temperature OffsetTemperature offset, ±5 Δ°C or ±10 Δ°F (default 0)delta °C / °FWrite
AV2RH OffsetRH offset, ±10 %RH (default 0)%RHWrite
AV3Atmospheric PressureBarometric pressure for calculations, 812-1013 hPa (default 1013)hPaWrite
AV4AltitudeAltitude, 0-6000 ft (default 0); linked to AV 3ftWrite
AV5Display ModeLCD display selection, 0-10Write0=No display, 1=Temperature, 2=Dewpoint, 3=Wet bulb, 4=Enthalpy, 5=T+dewpoint, 6=T+wet bulb, 7=T+enthalpy, 8=Dewpoint+wet bulb, 9=Dewpoint+enthalpy, 10=Wet bulb+enthalpy
BV1Temperature UnitTemperature unit selectWrite0=°C, 1=°F
BV2Enthalpy UnitEnthalpy unit selectWrite0=kJ/kg, 1=BTU/lb
Object ID lookup: Greystone Energy Systems DPRC Series room dewpoint transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DPRC Series room dewpoint transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP) have?

This list has 12 BACnet objects: 5 analog inputs, 5 analog values, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP) BACnet points are writable?

7 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP) BACnet documentation?

The source is DPRC Series Room Dewpoint Transmitter - Setup Guide for BACnet Communication (SG-DPRCXXXBAC-01), revision 2017-02-21 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-DPRCXXXBAC.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems DPRC Series room dewpoint transmitter (BACnet MS/TP)?

Start with AI 3 Dewpoint Temperature (Room dewpoint); AI 1 Temperature (Room temperature); AI 2 Relative Humidity (Room RH).

How do I check these points on the real DPRC Series room dewpoint transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: DPRC Series Room Dewpoint Transmitter - Setup Guide for BACnet Communication · SG-DPRCXXXBAC-01 · rev. 2017-02-21 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.