Room temperature / RH / differential pressure monitor · BACnet points list

Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The CR3 is a Greystone room monitor that measures temperature, RH and room differential pressure and talks native BACnet MS/TP. Nine Analog Inputs give the readings and their min/max values; Analog Values hold the low/high alarm setpoints, their allowed ranges, hysteresis and delays; Binary Inputs carry the six alarm states; Binary and Multi-State Values set units, display, outputs, alarms and menu locks.

This page lists 81 BACnet objects for the Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP) — 65 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
CR3 Series cleanroom monitor (BACnet MS/TP)
Equipment
Room temperature / RH / differential pressure monitor
Equipment type
Thermostats, sensors & meters
BACnet objects
81 (65 writable)
Transport
BACnet MS/TP
Firmware
1.05 (PICS, August 16, 2021)
Default device instance
381003
Also known as
CR3, CR3XXXBAC, CR3C, Greystone CR3 critical room monitor
Source document
CR3 Series Cleanroom Monitor - Setup Guide: BACnet Communication · SG-CR3XXXBAC-002 · rev. 2021-08-16 (PICS date)
Download CSV 81 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC in the menu, then read temperature, RH and DP (AI 1-3) and the alarm BIs. Set alarm setpoints and enable alarms with MV 1-3 once at commissioning.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3Differential Pressure (DP)Room differential pressure, Pa or mmWcRead
AI 1Temperature (TEMP)Room temperatureRead
AI 2Relative Humidity (RH)Room RHRead
BI 6DP Alarm Low StatusLow room pressure alarmRead
BI 7DP Alarm High StatusHigh room pressure alarmRead
BI 2TEMP Alarm Low StatusLow temperature alarmRead
BI 3TEMP Alarm High StatusHigh temperature alarmRead
BI 5RH Alarm High StatusHigh RH alarmRead

Network setup

Watch out for

Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

81 of 81 shown
Type
Multi-state
Access
Show
Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Temperature (TEMP)Room temperature, 0-50 °C°C / °FRead
AImin2Relative Humidity (RH)Room RH, 0-100 %%RHRead
AImin3Differential Pressure (DP)Room differential pressure, ±500 PaPa / mmWcRead
AI4TEMP MinimumLowest temperature since last BV 27 reset°C / °FRead
AI5TEMP MaximumHighest temperature since last BV 27 reset°C / °FRead
AI6RH MinimumLowest RH since last BV 27 reset%RHRead
AI7RH MaximumHighest RH since last BV 27 reset%RHRead
AI8DP MinimumLowest DP since last BV 27 resetPa / mmWcRead
AI9DP MaximumHighest DP since last BV 27 resetPa / mmWcRead
AV1TEMP OffsetTemperature offset, ±5 Δ°C (default 0)delta °C / °FWrite
AV2RH OffsetRH offset, ±10 %RH (default 0)%RHWrite
AV3TEMP Alarm Low SetpointLow temperature alarm (default 15 °C), within AV 4-5°C / °FWrite
AV4TEMP Low Setpoint MinLower limit for the low temp alarm setpoint°C / °FWrite
AV5TEMP Low Setpoint MaxUpper limit for the low temp alarm setpoint°C / °FWrite
AV6TEMP Alarm High SetpointHigh temperature alarm (default 25 °C), within AV 7-8°C / °FWrite
AV7TEMP High Setpoint MinLower limit for the high temp alarm setpoint°C / °FWrite
AV8TEMP High Setpoint MaxUpper limit for the high temp alarm setpoint°C / °FWrite
AV9TEMP Alarm HysteresisTemperature alarm hysteresis, 0-1 Δ°C (default 0.2)delta °C / °FWrite
AV10TEMP Alarm On DelayTemperature alarm delay, 0-255 s (default 5)sWrite
AV11RH Alarm Low SetpointLow RH alarm (default 30 %RH), within AV 12-13%RHWrite
AV12RH Low Setpoint MinLower limit for the low RH alarm setpoint%RHWrite
AV13RH Low Setpoint MaxUpper limit for the low RH alarm setpoint%RHWrite
AV14RH Alarm High SetpointHigh RH alarm (default 65 %RH), within AV 15-16%RHWrite
AV15RH High Setpoint MinLower limit for the high RH alarm setpoint%RHWrite
AV16RH High Setpoint MaxUpper limit for the high RH alarm setpoint%RHWrite
AV17RH Alarm HysteresisRH alarm hysteresis, 0-5 %RH (default 2)%RHWrite
AV18RH Alarm On DelayRH alarm delay, 0-255 s (default 15)sWrite
AV19DP Alarm Low SetpointLow DP alarm (default 0 Pa), within AV 20-21Pa / mmWcWrite
AV20DP Low Setpoint MinLower limit for the low DP alarm setpointPa / mmWcWrite
AV21DP Low Setpoint MaxUpper limit for the low DP alarm setpointPa / mmWcWrite
AV22DP Alarm High SetpointHigh DP alarm (default 200 Pa), within AV 23-24Pa / mmWcWrite
AV23DP High Setpoint MinLower limit for the high DP alarm setpointPa / mmWcWrite
AV24DP High Setpoint MaxUpper limit for the high DP alarm setpointPa / mmWcWrite
AV25DP Alarm HysteresisDP alarm hysteresis, 0-50 Pa (default 5)Pa / mmWcWrite
AV26DP Alarm On DelayDP alarm delay, 0-255 s (default 10)sWrite
AV27Buzzer Auto Reset TimeBuzzer auto reset time, 5-255 s (default 15)sWrite
AV28Analog Out TEMP OverrideTemperature output value when overridden, 0-100 %%Write
AV29Analog Out RH OverrideRH output value when overridden, 0-100 %%Write
AV30Analog Out DP OverrideDP output value when overridden, 0-100 %%Write
AV31Digital Input Self-reset TimeDigital input self-reset time, 1-255 s (default 30)sWrite
AV32DP Low RangeDP range low end, -500 to 0 Pa (default -500)Pa / mmWcWrite
AV33DP High RangeDP range high end, 0 to 500 Pa (default 500)Pa / mmWcWrite
BI1Digital InputDigital input stateRead0=Inactive, 1=Active
BImin2TEMP Alarm Low StatusLow temperature alarmRead0=No alarm, 1=Alarm
BImin3TEMP Alarm High StatusHigh temperature alarmRead0=No alarm, 1=Alarm
BI4RH Alarm Low StatusLow RH alarmRead0=No alarm, 1=Alarm
BImin5RH Alarm High StatusHigh RH alarmRead0=No alarm, 1=Alarm
BImin6DP Alarm Low StatusLow DP alarmRead0=No alarm, 1=Alarm
BImin7DP Alarm High StatusHigh DP alarmRead0=No alarm, 1=Alarm
BV1TEMP UnitsTemperature unitsWrite0=°C, 1=°F
BV2DP UnitsPressure unitsWrite0=Pa, 1=mmWc
BV3DP Auto ZeroWrite 1 to auto-zero the DP sensorWrite0=Normal Operation, 1=Perform Auto Zero
BV4TEMP Response TimeTemperature response speedWrite0=Fast, 1=Slow
BV5RH Response TimeRH response speedWrite0=Fast, 1=Slow
BV6DP Response TimeDP response speedWrite0=Fast, 1=Slow
BV7TEMP DisplayShow temperature on the displayWrite0=Off, 1=On
BV8RH DisplayShow RH on the displayWrite0=Off, 1=On
BV9DP DisplayShow DP on the displayWrite0=Off, 1=On
BV10TEMP Out DirectionTemperature analog output actionWrite0=Direct, 1=Reverse
BV11RH Out DirectionRH analog output actionWrite0=Direct, 1=Reverse
BV12DP Out DirectionDP analog output actionWrite0=Direct, 1=Reverse
BV13Analog Output OverridePuts the analog outputs on the AV 28-30 valuesWrite0=Normal, 1=Override
BV14Buzzer ResetBuzzer reset mode (default 1)Write0=Manual Only, 1=Manual + Automatic
BV15Alarm AcknowledgeAlarm acknowledgeWrite0=Normal, 1=Alarm Acknowledged
BV16Digital Input ModeDigital input status latch mode (default 1)Write0=Latch, 1=Momentary Self-reset
BV17Digital Input StatusLatched digital input; write 0 to clearWrite0=Inactive, 1=Active
BV18Setpoint LockLocks setpoints on the local displayWrite0=Not Locked, 1=Locked
BV19User Menu LockLocks the user menuWrite0=Not Locked, 1=Locked
BV20Installer Menu LockLocks the installer menuWrite0=Not Locked, 1=Locked
BV21Display BrightnessDisplay brightnessWrite0=Low, 1=High
BV22TEMP Analog Input RangeTemperature range (default 0-50 °C)Write0=0-35 °C (32-95 °F), 1=0-50 °C (32-122 °F)
BV23Analog Input Signal TypeAnalog input signal typeWrite0=mA, 1=Voltage
BV24Analog Input Volt RangeAnalog input voltage rangeWrite0=0-5 V, 1=0-10 V
BV25Analog Output Signal TypeAnalog output signal typeWrite0=mA, 1=Voltage
BV26Analog Output Volt RangeAnalog output voltage rangeWrite0=0-5 V, 1=0-10 V
BV27Min Max ResetWrite 1 to reset all min/max valuesWrite0=Normal, 1=Reset all values
MV1TEMP Alarm OperationTemperature alarm mode (default Disable)Write1=Low Alrm, 2=High Alrm, 3=Both, 4=Disable
MV2RH Alarm OperationRH alarm mode (default Disable)Write1=Low Alrm, 2=High Alrm, 3=Both, 4=Disable
MV3DP Alarm OperationDP alarm mode (default Both)Write1=Low Alrm, 2=High Alrm, 3=Both, 4=Disable
MV4Buzzer AssignmentWhich alarm sounds the buzzer (default DP)Write1=TEMP, 2=RH, 3=DP, 4=Disable, 5=All
MV5Digital Input FunctionDigital input function (default Disable)Write1=Disable, 2=Freeze, 3=Silence
Object ID lookup: Greystone Energy Systems CR3 Series cleanroom monitor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CR3 Series cleanroom monitor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP) have?

This list has 81 BACnet objects: 9 analog inputs, 33 analog values, 7 binary inputs, 27 binary values, 5 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP) BACnet points are writable?

65 of the 81 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP) BACnet documentation?

The source is CR3 Series Cleanroom Monitor - Setup Guide: BACnet Communication (SG-CR3XXXBAC-002), revision 2021-08-16 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-CR3XXXBAC-002.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems CR3 Series cleanroom monitor (BACnet MS/TP)?

Start with AI 3 Differential Pressure (DP) (Room differential pressure, Pa or mmWc); AI 1 Temperature (TEMP) (Room temperature); AI 2 Relative Humidity (RH) (Room RH); BI 6 DP Alarm Low Status (Low room pressure alarm); BI 7 DP Alarm High Status (High room pressure alarm); BI 2 TEMP Alarm Low Status (Low temperature alarm); BI 3 TEMP Alarm High Status (High temperature alarm); BI 5 RH Alarm High Status (High RH alarm).

How do I check these points on the real CR3 Series cleanroom monitor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: CR3 Series Cleanroom Monitor - Setup Guide: BACnet Communication · SG-CR3XXXBAC-002 · rev. 2021-08-16 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.