Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The CHT is a Greystone CO2 sensor with optional RH and temperature, talking native BACnet MS/TP. Measurements are three Analog Inputs; relay setup, offsets and altitude are Analog Values, and units, auto-calibration and relay test are Binary Values. Objects for options that are not fitted report a fault.

This page lists 15 BACnet objects for the Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP) — 11 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
CHT Series CO2 / RH / temperature sensor (BACnet MS/TP)
Equipment
CO2 / RH / temperature sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
15 (11 writable)
Transport
BACnet MS/TP
Firmware
1.4 (PICS, June 13, 2022)
Default device instance
381003
Also known as
CHT, CHTDT, CHTXXXBAC, Greystone CHT
Source document
CO2/RH/T Sensor CHT Series - Setup Guide BACnet Communication · SG-CHTXXXBAC-02 · rev. 04/22
Download CSV 15 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP)

Integration in brief

Set a unique MS/TP MAC and device instance in the menu, then read CO2 (AI 1) plus the RH and temperature inputs if fitted. AVs and BVs are setup values.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1CO2 ValueSpace CO2, ppmRead
AI 2RH ValueSpace RH (RH option)Read
AI 3Temperature ValueSpace temperature (temperature option)Read
BI 1Relay StatusCO2 relay energizedRead

Network setup

Watch out for

Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

15 of 15 shown
Type
Multi-state
Access
Show
Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1CO2 ValueCO2 reading, 0-10,000 ppmppmRead
AImin2RH ValueRelative humidity (RH option)%RHRead
AImin3Temperature ValueTemperature (temperature option); units follow BV 1°F / °CRead
AV1Relay SetpointCO2 relay trip point, 500-1500 ppm (default 1000)ppmWrite
AV2Relay HysteresisRelay hysteresis, 25-200 ppm (default 50)ppmWrite
AV3Relay ON DelayRelay on delay, 0-255 s (default 15)sWrite
AV4Temperature OffsetTemperature calibration offset (default 0)delta °C / °FWrite
AV5RH OffsetRH calibration offset, -10 to 10 %RH%RHWrite
AV6AltitudeInstalled altitude, 0-2550 m in 50 m stepsmWrite
BV1Temperature UnitsTemperature unit selectWrite0=°C, 1=°F
BV2Auto Cal EnableCO2 automatic calibration (default enabled)Write0=Disable, 1=Enable
BV3Relay TestForces the relay for testingWrite0=Relay off, 1=Relay on
BImin1Relay StatusCO2 relay energizedRead0=Inactivated, 1=Activated
MV1LCD BacklightLCD backlight mode (default Auto)Write0=AUTO, 1=OFF, 2=ON
MV2Display ModesValues shown on the LCDWrite0=CO2, 1=CO2+RH+T
Object ID lookup: Greystone Energy Systems CHT Series CO2 / RH / temperature sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CHT Series CO2 / RH / temperature sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP) have?

This list has 15 BACnet objects: 3 analog inputs, 6 analog values, 1 binary input, 3 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP) BACnet points are writable?

11 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP) BACnet documentation?

The source is CO2/RH/T Sensor CHT Series - Setup Guide BACnet Communication (SG-CHTXXXBAC-02), revision 04/22, published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-CHTXXXBAC-002.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems CHT Series CO2 / RH / temperature sensor (BACnet MS/TP)?

Start with AI 1 CO2 Value (Space CO2, ppm); AI 2 RH Value (Space RH (RH option)); AI 3 Temperature Value (Space temperature (temperature option)); BI 1 Relay Status (CO2 relay energized).

How do I check these points on the real CHT Series CO2 / RH / temperature sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: CO2/RH/T Sensor CHT Series - Setup Guide BACnet Communication · SG-CHTXXXBAC-02 · rev. 04/22. Object names, instances and units are reproduced as published; descriptions are our own.