Room differential pressure sensor / monitor · BACnet points list

Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The RPC is a Greystone room pressure monitor with native BACnet MS/TP. The pressure reading is one Analog Input; averaging time, high/low alarm limits, alarm delays, silence time and buzzer volume are Analog Values; Binary Values set alarm enable/test, backlight, units and range, and three Binary Inputs report the alarms.

This page lists 16 BACnet objects for the Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
RPC Series room pressure sensor (BACnet MS/TP)
Equipment
Room differential pressure sensor / monitor
Equipment type
Thermostats, sensors & meters
BACnet objects
16 (12 writable)
Transport
BACnet MS/TP
Firmware
1.4 (PICS, Nov 8, 2013)
Default device instance
381003
Also known as
RPC, RPCXXXBAC, Greystone room pressure monitor
Source document
RPC Series Room Pressure Sensor - Setup Guide BACnet Communication · SG-RPCXXXBAC · rev. 2013-11-08 (PICS date)
Download CSV 16 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC in the menu, choose units and range, then read the room pressure (AI 1) and the alarm BIs. Set the alarm limits once at commissioning.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Pressure Sensor ValueRoom differential pressureRead
BI 1Alarm StatusAny pressure alarmRead
BI 2Low Alarm StatusLow pressure alarmRead
BI 3High Alarm StatusHigh pressure alarmRead

Network setup

Watch out for

Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

16 of 16 shown
Type
Access
Show
Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Pressure Sensor ValueRoom differential pressure in the selected unitsPa / in. w.c.Read
AV1Pressure Averaging TimeReading averaging time, 1-60 s (default 5)sWrite
AV2Alarm High LimitHigh pressure alarm limit (default +50 % of range)Pa / in. w.c.Write
AV3Alarm Low LimitLow pressure alarm limit (default -50 % of range)Pa / in. w.c.Write
AV4Alarm On DelayAlarm on delay, 1 s to 10 min (default 5 s)sWrite
AV5Alarm Off DelayAlarm off delay, 1 s to 10 min (default 5 s)sWrite
AV6Alarm Silence TimeBuzzer silence time, 1-60 min, 0 = no reset (default 30)minWrite
AV7Buzzer VolumeBuzzer volume (default 2)Write0=Off, 1=Low, 2=High
BV1Alarm EnableAlarm functions enable (normally 1)Write0=Alarm Disable, 1=Alarm Enable
BV2Alarm TestWrite 1 to test the alarmWrite0=Normal Operation, 1=Alarm Test
BV3Backlight EnableLCD backlight (normally 1)Write0=Disable, 1=Enable
BV4Pressure UnitsPressure units (normally 0)Write0=in. w.c., 1=Pa
BV5Pressure RangePressure range select (normally 1)Write0=Low Range, 1=High Range
BImin1Alarm StatusAny pressure alarmRead0=No Alarm, 1=Pressure Alarm
BImin2Low Alarm StatusLow pressure alarmRead0=No Low Alarm, 1=Low Alarm
BImin3High Alarm StatusHigh pressure alarmRead0=No High Alarm, 1=High Alarm
Object ID lookup: Greystone Energy Systems RPC Series room pressure sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RPC Series room pressure sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP) have?

This list has 16 BACnet objects: 1 analog input, 7 analog values, 3 binary inputs, 5 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP) BACnet points are writable?

12 of the 16 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP) BACnet documentation?

The source is RPC Series Room Pressure Sensor - Setup Guide BACnet Communication (SG-RPCXXXBAC), revision 2013-11-08 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-RPCXXXBAC.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems RPC Series room pressure sensor (BACnet MS/TP)?

Start with AI 1 Pressure Sensor Value (Room differential pressure); BI 1 Alarm Status (Any pressure alarm); BI 2 Low Alarm Status (Low pressure alarm); BI 3 High Alarm Status (High pressure alarm).

How do I check these points on the real RPC Series room pressure sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: RPC Series Room Pressure Sensor - Setup Guide BACnet Communication · SG-RPCXXXBAC · rev. 2013-11-08 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.