Particulate matter (PM2.5 / PM10) sensor · BACnet points list

Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The PM Series is a Greystone particulate transmitter with native BACnet MS/TP. PM1.0, PM2.5, PM4.0 and PM10 mass are Analog Inputs; the alarm setpoint, hysteresis, delay and analog output scale are Analog Values, and a Multi-State Input gives a simple Good / Moderate / Poor air quality band.

This page lists 15 BACnet objects for the Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP) — 9 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
PM Series particulate matter transmitter (BACnet MS/TP)
Equipment
Particulate matter (PM2.5 / PM10) sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
15 (9 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS, May 2, 2019)
Default device instance
381003
Also known as
PM Series, PMRMC, PMDT, PMOS, PMXXXBAC, Greystone particulate sensor
Source document
PM Series Particulate Matter Transmitter - Setup Guide BACnet Communication · SG-PMXXXBAC-05 · rev. 2019-05-02 (PICS date)
Download CSV 15 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC and baud in the Setup menu, then read PM2.5 and PM10 and the alarm status. Alarm and output settings are set once.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 2PM2.5 Particulate MassPM2.5, µg/m3Read
AI 4PM10 Particulates MassPM10, µg/m3Read
MI 1AQI StatusAir quality band: Good / Moderate / PoorRead
BI 1PM Alarm StatusPM alarm activeRead

Network setup

Watch out for

Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

15 of 15 shown
Type
Access
Show
Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AI1PM1.0 Particulate MassPM1.0 mass, 0-1000 µg/m3µg/m3Read
AImin2PM2.5 Particulate MassPM2.5 mass, 0-1000 µg/m3µg/m3Read
AI3PM4.0 Particulate MassPM4.0 mass, 0-1000 µg/m3µg/m3Read
AImin4PM10 Particulates MassPM10 mass, 0-1000 µg/m3µg/m3Read
AV1Analog Output ScaleAnalog output full scale, 500-1000 µg/m3 (default 1000)µg/m3Write
AV2PM Alarm SetpointPM alarm trip point, 50-900 µg/m3 (default 150)µg/m3Write
AV3PM Alarm HysteresisPM alarm hysteresis, 10-40 µg/m3 (default 20)µg/m3Write
AV4PM Alarm DelayPM alarm delay, 0-10 min (default 0)minWrite
BV1Display FormatLCD display format (default µg/m3)Write0=AQI, 1=µg/m3
BV2PM Alarm TestForces the alarm for testingWrite0=Normal, 1=Test
BV3Analog Output DirectionAnalog output actionWrite0=Direct, 1=Reverse
BImin1PM Alarm StatusPM alarm activeRead0=Normal, 1=Alarm
MV1LCD BacklightLCD backlight mode (default Auto)Write1=Auto, 2=Off, 3=On
MV2PM OutputPM size used for the output and alarm (default PM10)Write1=PM1.0, 2=PM2.5, 3=PM4.0, 4=PM10
MImin1AQI StatusAir quality index bandRead1=Good, 2=Moderate, 3=Poor
Object ID lookup: Greystone Energy Systems PM Series particulate matter transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PM Series particulate matter transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP) have?

This list has 15 BACnet objects: 4 analog inputs, 4 analog values, 1 binary input, 3 binary values, 1 multi-state input, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP) BACnet points are writable?

9 of the 15 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP) BACnet documentation?

The source is PM Series Particulate Matter Transmitter - Setup Guide BACnet Communication (SG-PMXXXBAC-05), revision 2019-05-02 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-PMXXXBAC.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems PM Series particulate matter transmitter (BACnet MS/TP)?

Start with AI 2 PM2.5 Particulate Mass (PM2.5, µg/m3); AI 4 PM10 Particulates Mass (PM10, µg/m3); MI 1 AQI Status (Air quality band: Good / Moderate / Poor); BI 1 PM Alarm Status (PM alarm active).

How do I check these points on the real PM Series particulate matter transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: PM Series Particulate Matter Transmitter - Setup Guide BACnet Communication · SG-PMXXXBAC-05 · rev. 2019-05-02 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.