Indoor air quality multi-sensor (CO2 / PM / VOC / formaldehyde) · BACnet points list

Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The IAQRM is a Greystone room air-quality multi-sensor with native BACnet MS/TP. Fourteen Analog Inputs report VOC, RH, temperature, PM1.0-PM10 mass and particle counts, CO2 and formaldehyde; Analog Values hold offsets, CO2 altitude and the relay settings, Binary Values select units and switch individual sensors and display features, and Multi-State Values assign the relay and VOC units.

This page lists 36 BACnet objects for the Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP) — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
IAQRM Series multi-sensor (BACnet MS/TP)
Equipment
Indoor air quality multi-sensor (CO2 / PM / VOC / formaldehyde)
Equipment type
Thermostats, sensors & meters
BACnet objects
36 (21 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS, March 15, 2023)
Default device instance
381003
Also known as
IAQRM, MSN, IAQRMXXXBAC, Greystone indoor air quality multi sensor
Source document
IAQRM Series Multi Sensor - Setup Guide BACnet Communication · SG-IAQRMXXXBAC-001 · rev. 03/23
Download CSV 36 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC in the menu, then read the fitted measurements: CO2, PM2.5, VOC, temperature and RH. Treat a value of -1000 as a sensor error.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 13CO2 Sensor ValueRoom CO2, ppmRead
AI 5PM 2.5 Particulate MassPM2.5, µg/m3Read
AI 1VOC Sensor ValueVOC level (index, ppb or µg/m3)Read
AI 3Temperature Sensor ValueRoom temperatureRead
AI 2RH Sensor ValueRoom RHRead
AI 14Formaldehyde Sensor ValueFormaldehyde levelRead
BI 1Relay StatusRelay alarm activeRead

Network setup

Watch out for

Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

36 of 36 shown
Type
Multi-state
Access
Show
Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1VOC Sensor ValueVOC: 0-500 index, ppb or µg/m3 per MV 2VOC index / ppb / µg/m3Read
AImin2RH Sensor ValueRelative humidity, 0-100 %%RHRead
AImin3Temperature Sensor ValueTemperature, 0-50 °C°C / °FRead
AI4PM 1.0 Particulate MassPM1.0 mass, 0-1000 µg/m3µg/m3Read
AImin5PM 2.5 Particulate MassPM2.5 mass, 0-1000 µg/m3µg/m3Read
AI6PM 4.0 Particulate MassPM4.0 mass, 0-1000 µg/m3µg/m3Read
AI7PM 10 Particulate MassPM10 mass, 0-1000 µg/m3µg/m3Read
AI8PM 0.5 Number concentration rangePM0.5 particle count, 0-3000 #/cm3#/cm3Read
AI9PM 1.0 Number concentration rangePM1.0 particle count, 0-3000 #/cm3#/cm3Read
AI10PM 2.5 Number concentration rangePM2.5 particle count, 0-3000 #/cm3#/cm3Read
AI11PM 4.0 Number concentration rangePM4.0 particle count, 0-3000 #/cm3#/cm3Read
AI12PM10 Number concentration rangePM10 particle count, 0-3000 #/cm3#/cm3Read
AImin13CO2 Sensor ValueCO2, 0-10,000 ppmppmRead
AImin14Formaldehyde Sensor ValueFormaldehyde, 0-1230 µg/m3 or 0-1000 ppb (per BV 2)µg/m3 / ppbRead
AV1Temperature OffsetTemperature offset, ±5 Δ°C or ±10 Δ°F (default 0)delta °C / °FWrite
AV2Humidity OffsetRH offset, ±10 %RH (default 0)%RHWrite
AV3CO2 OffsetCO2 offset, ±200 ppm (default 0)ppmWrite
AV4CO2 Altitude AdjustmentAltitude for CO2 correction, 0-3000 m (default 0)mWrite
AV5Relay SetpointRelay trip point; range follows MV 1 (default 26 °C)Write
AV6Relay HysteresisRelay hysteresis; range follows MV 1 (default 2 °C)Write
AV7Relay On TimeRelay on/off delay, 0-255 s (default 15)sWrite
BV1Temperature UnitsTemperature unit selectWrite0=°C, 1=°F
BV2CH2O UnitsFormaldehyde unit selectWrite0=µg/m3, 1=ppb
BV3Relay TestForces the relay for testingWrite0=Inactive, 1=Test
BV4LCD BacklightLCD backlightWrite0=Enabled, 1=Disabled
BV5CO2 ASCCO2 automatic self-calibrationWrite0=Enabled, 1=Disabled
BV6CO2 AvailabilityCO2 sensor in useWrite0=Enabled, 1=Disabled
BV7VOC AvailabilityVOC sensor in useWrite0=Enabled, 1=Disabled
BV8PM AvailabilityPM sensor in useWrite0=Enabled, 1=Disabled
BV9CH2O AvailabilityFormaldehyde sensor in useWrite0=Enabled, 1=Disabled
BV10LED AvailabilityStatus LEDWrite0=Enabled, 1=Disabled
BV11Status Bars AvailabilityDisplay status barsWrite0=Enabled, 1=Disabled
BV12Touch Screen AvailabilityTouch screenWrite0=Enabled, 1=Disabled
BImin1Relay StatusRelay alarm stateRead0=Normal, 1=Alarm
MV1Relay AssignmentReading that drives the relay (default 3)Write0=No Relay, 1=VOC, 2=RH, 3=Temperature, 4=CO2, 5=PM_MASS, 6=PM_NUMBER, 7=CH2O
MV2Set VOC UnitsVOC reporting units (default 1)Write1=VOCI, 2=PPB, 3=ug/m3
Object ID lookup: Greystone Energy Systems IAQRM Series multi-sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IAQRM Series multi-sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP) have?

This list has 36 BACnet objects: 14 analog inputs, 7 analog values, 1 binary input, 12 binary values, 2 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP) BACnet points are writable?

21 of the 36 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP) BACnet documentation?

The source is IAQRM Series Multi Sensor - Setup Guide BACnet Communication (SG-IAQRMXXXBAC-001), revision 03/23, published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-IAQXXXBAC-001.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems IAQRM Series multi-sensor (BACnet MS/TP)?

Start with AI 13 CO2 Sensor Value (Room CO2, ppm); AI 5 PM 2.5 Particulate Mass (PM2.5, µg/m3); AI 1 VOC Sensor Value (VOC level (index, ppb or µg/m3)); AI 3 Temperature Sensor Value (Room temperature); AI 2 RH Sensor Value (Room RH); AI 14 Formaldehyde Sensor Value (Formaldehyde level); BI 1 Relay Status (Relay alarm active).

How do I check these points on the real IAQRM Series multi-sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: IAQRM Series Multi Sensor - Setup Guide BACnet Communication · SG-IAQRMXXXBAC-001 · rev. 03/23. Object names, instances and units are reproduced as published; descriptions are our own.