VOC air quality sensor · BACnet points list

Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The VOC Series is a Greystone room air quality transmitter with native BACnet MS/TP. VOC (as an index or ppb), RH and temperature are Analog Inputs; offsets and relay setpoint, hysteresis and delay are Analog Values; Binary Values set units, override, the TVOC clean-air reference and the Bluetooth link, and Multi-State Values assign the relay and the display.

This page lists 20 BACnet objects for the Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP) — 14 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
VOC Series air quality transmitter (BACnet MS/TP)
Equipment
VOC air quality sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
20 (14 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS, 19-Jul-21)
Default device instance
381003
Also known as
VOC Series, VOCXXXBAC, Greystone VOC sensor, Greystone TVOC transmitter
Source document
VOC Series Air Quality Transmitter - Setup Guide for BACnet Communication · SG-VOCXXXBAC-001 · rev. 2021-07-19 (PICS date)
Download CSV 20 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC in the menu, pick VOC units with BV 1, then read VOC, RH and temperature. Treat -1000 as a sensor error.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1VOC Sensor ValueVOC index or TVOC ppb (per BV 1)Read
AI 3Temperature Sensor ValueRoom temperatureRead
AI 2RH Sensor ValueRoom RHRead
BI 2Override StatusOccupant override activeRead
BI 1Relay StatusRelay alarm activeRead

Network setup

Watch out for

Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

20 of 20 shown
Type
Multi-state
Access
Show
Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1VOC Sensor ValueVOC: 0-500 index or 0-1000 ppb per BV 1VOC index / ppbRead
AImin2RH Sensor ValueRelative humidity, 0-100 %%RHRead
AImin3Temperature Sensor ValueTemperature, 0-50 °C°C / °FRead
AV1Temperature OffsetTemperature offset, ±5 Δ°C or ±10 Δ°F (default 0)delta °C / °FWrite
AV2Humidity OffsetRH offset, ±10 %RH (default 0)%RHWrite
AV3Relay SetpointRelay trip point; range follows MV 1 (default 20 VOC index)Write
AV4Relay HysterisisRelay hysteresis; range follows MV 1 (default 20 VOC index)Write
AV5Relay On TimeRelay on/off delay, 0-255 s (default 0)sWrite
BV1VOC UnitsVOC reporting unitsWrite0=VOC Index, 1=TVOC ppb
BV2Temperature UnitsTemperature unit selectWrite0=°C, 1=°F
BV3Relay TestForces the relay for testingWrite0=Inactive, 1=Test
BV4Set OverideOverride commandWrite0=Inactive, 1=Active
BV5Set New TVOC ReferenceWrite 1 in clean air to reset the TVOC reference (reads 50 ppb)Write0=Inactive, 1=Active
BV6Set Wireless EnableBluetooth (BLE) wireless link enableWrite0=Disable, 1=Enable
BImin1Relay StatusRelay alarm stateRead0=Normal, 1=Alarm
BImin2Override StatusOverride activeRead0=Inactive, 1=Active
BI3Wireless Connect StatusBluetooth connection stateRead0=Disconnected, 1=Connected
MV1Relay AssignmentReading that drives the relay (default 1)Write0=No Relay, 1=VOC, 2=RH, 3=Temperature
MV2LCD BacklightLCD backlight mode (default 1)Write1=Auto, 2=Off, 3=On
MV3LCD FormatValues shown on the LCD (default 1)Write1=VOC Index, 2=RH, 3=Temperature, 4=VOC/T/RH
Object ID lookup: Greystone Energy Systems VOC Series air quality transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VOC Series air quality transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP) have?

This list has 20 BACnet objects: 3 analog inputs, 5 analog values, 3 binary inputs, 6 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP) BACnet points are writable?

14 of the 20 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP) BACnet documentation?

The source is VOC Series Air Quality Transmitter - Setup Guide for BACnet Communication (SG-VOCXXXBAC-001), revision 2021-07-19 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-VOCXXXBAC-001.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems VOC Series air quality transmitter (BACnet MS/TP)?

Start with AI 1 VOC Sensor Value (VOC index or TVOC ppb (per BV 1)); AI 3 Temperature Sensor Value (Room temperature); AI 2 RH Sensor Value (Room RH); BI 2 Override Status (Occupant override active); BI 1 Relay Status (Relay alarm active).

How do I check these points on the real VOC Series air quality transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: VOC Series Air Quality Transmitter - Setup Guide for BACnet Communication · SG-VOCXXXBAC-001 · rev. 2021-07-19 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.