Humidity / temperature sensor · BACnet points list

Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The HN is a Greystone RH and temperature transmitter with native BACnet MS/TP. RH and temperature are two Analog Inputs; offsets and the optional relay setpoint, hysteresis and delay are Analog Values, and Binary Values set units, relay test and which reading drives the relay.

This page lists 11 BACnet objects for the Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
HN Series humidity / temperature transmitter (BACnet MS/TP)
Equipment
Humidity / temperature sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
11 (8 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS, 16-Sep-20)
Default device instance
381001
Also known as
HN, HNXXXBAC, Greystone HN humidity sensor
Source document
HN Series Humidity/Temperature Transmitter - Setup Guide for BACnet Communication · SG-HNXXXBAC-001 · rev. 2020-09-16 (PICS date)
Download CSV 11 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC in the menu, then read RH (AI 1) and temperature (AI 2). The relay settings only matter when the relay option drives local equipment.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Relative HumiditySpace or duct RHRead
AI 2TemperatureSpace or duct temperatureRead
BI 1Relay StatusRelay alarm active (option)Read

Network setup

Watch out for

Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

11 of 11 shown
Type
Access
Show
Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1Relative HumidityRelative humidity, 0-100 %%RHRead
AImin2TemperatureTemperature, -40 to 50 °C°C / °FRead
AV1Humidity OffsetRH offset, ±10 %RH (default 0)%RHWrite
AV2Temperature OffsetTemperature offset, ±5 Δ°C or ±10 Δ°F (default 0)delta °C / °FWrite
AV3Relay SetpointRelay trip point: 20-90 %RH or 5-40 °C (default 70 %RH)%RH / °C / °FWrite
AV4Relay HysterisisRelay hysteresis: 5-20 %RH or 1-5 °C (default 10 %RH)%RH / °C / °FWrite
AV5Relay On TimeRelay on/off delay, 0-255 s (default 0)sWrite
BV1Temperature UnitsTemperature unit selectWrite0=°C, 1=°F
BV2Relay TestForces the relay for testingWrite0=Normal, 1=Test
BV3Relay AssignmentWhich reading the relay setpoint usesWrite0=RH, 1=Temperature
BImin1Relay StatusRelay alarm state (relay option)Read0=Normal, 1=Alarm
Object ID lookup: Greystone Energy Systems HN Series humidity / temperature transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HN Series humidity / temperature transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP) have?

This list has 11 BACnet objects: 2 analog inputs, 5 analog values, 1 binary input, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP) BACnet points are writable?

8 of the 11 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP) BACnet documentation?

The source is HN Series Humidity/Temperature Transmitter - Setup Guide for BACnet Communication (SG-HNXXXBAC-001), revision 2020-09-16 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-HNXXXBAC-001.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems HN Series humidity / temperature transmitter (BACnet MS/TP)?

Start with AI 1 Relative Humidity (Space or duct RH); AI 2 Temperature (Space or duct temperature); BI 1 Relay Status (Relay alarm active (option)).

How do I check these points on the real HN Series humidity / temperature transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: HN Series Humidity/Temperature Transmitter - Setup Guide for BACnet Communication · SG-HNXXXBAC-001 · rev. 2020-09-16 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.