Greenhouse CO2 sensor · BACnet points list

Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The GO3 is a Greystone CO2 sensor for grow rooms and greenhouses, with native BACnet MS/TP. CO2 and the optional temperature and RH readings are Analog Inputs; altitude, relay setpoint, hysteresis, delay and offsets are Analog Values, and the relay state is a Binary Input. Its device object name defaults to "CDD CO2 001".

This page lists 12 BACnet objects for the Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP) — 8 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
GO3 Series horticulture CO2 sensor (BACnet MS/TP)
Equipment
Greenhouse CO2 sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
12 (8 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
381001
Also known as
GO3, GO3 BACnet, Greystone GO3 greenhouse CO2
Source document
GO3 Series Horticulture Sensor - Setup Guide BACnet Communication · SG-GO3-BACnet-01-01 · rev. 08/18
Download CSV 12 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC in the menu, set altitude, then read CO2 (AI 1) and the optional temperature and RH. Use the relay status if the relay drives CO2 dosing or venting.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1CO2Room CO2, ppmRead
AI 2TemperatureRoom temperature (option)Read
AI 3Relative HumidityRoom RH (option)Read
BI 1Relay StatusCO2 relay energizedRead

Network setup

Watch out for

Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

12 of 12 shown
Type
Access
Show
Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1CO2CO2, 0-20,000 ppmppmRead
AImin2TemperatureTemperature, 0-50 °C (temperature option)°C / °FRead
AImin3Relative HumidityRelative humidity, 0-100 % (RH option)%RHRead
AV1AltitudeInstalled altitude, 0-5000 ft (default 0)ftWrite
AV2Relay SetpointCO2 relay trip point (default 1000 ppm); max 5000 auto-cal, 15,000 dual-beamppmWrite
AV3Relay HysteresisRelay hysteresis (default 50 ppm); max 200 auto-cal, 500 dual-beamppmWrite
AV4Relay On DelayRelay on delay, 0-255 s (default 15)sWrite
AV5Temperature OffsetTemperature offset, ±5 Δ°C or ±10 Δ°F (default 0)delta °C / °FWrite
AV6RH OffsetRH offset, ±10 %RH (default 0)%RHWrite
BV1Temperature UnitsTemperature unit selectWrite0=°C, 1=°F
BV2Auto Cal EnableCO2 auto-calibration (auto-cal sensor only; default 1)Write0=Disable, 1=Enable
BImin1Relay StatusCO2 relay energized (relay option)Read0=Inactive, 1=Active
Object ID lookup: Greystone Energy Systems GO3 Series horticulture CO2 sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GO3 Series horticulture CO2 sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP) have?

This list has 12 BACnet objects: 3 analog inputs, 6 analog values, 1 binary input, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP) BACnet points are writable?

8 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP) BACnet documentation?

The source is GO3 Series Horticulture Sensor - Setup Guide BACnet Communication (SG-GO3-BACnet-01-01), revision 08/18, published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/Website%20Documents/GO3/SG-GO3BACnet-01-01.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems GO3 Series horticulture CO2 sensor (BACnet MS/TP)?

Start with AI 1 CO2 (Room CO2, ppm); AI 2 Temperature (Room temperature (option)); AI 3 Relative Humidity (Room RH (option)); BI 1 Relay Status (CO2 relay energized).

How do I check these points on the real GO3 Series horticulture CO2 sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: GO3 Series Horticulture Sensor - Setup Guide BACnet Communication · SG-GO3-BACnet-01-01 · rev. 08/18. Object names, instances and units are reproduced as published; descriptions are our own.