Humidity / temperature sensor with condensation monitoring · BACnet points list

Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The HTX1 is a Greystone rough-duty RH and temperature transmitter with native BACnet MS/TP. It reports temperature, RH, dewpoint, wet bulb, enthalpy, absolute humidity and pipe temperature as Analog Inputs; Analog Values handle offset or 2-point calibration, altitude and the relay setpoints and timers; Multi-State Values assign the relay source, and Multi-State Inputs give relay status and error codes.

This page lists 46 BACnet objects for the Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP) — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP)
Equipment
Humidity / temperature sensor with condensation monitoring
Equipment type
Thermostats, sensors & meters
BACnet objects
46 (33 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS, 2025/7/8)
Default device instance
381001
Also known as
HTX1, HTX1XXXBAC, DP0011, NPI-56, Greystone rough duty sensor
Source document
Rough Duty Sensor (NPI-56) RH/T Transmitter - Setup Guide BACnet Communication (HTX1 Series) · SG-HTX1XXXBAC-001 · rev. 2025-07-08 (PICS date)
Download CSV 46 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC in the menu, then read temperature, RH and dewpoint. If the relay is to be switched by the BMS, set MV 2 to Free Control by BACnet and write BV 11.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 11Relay Controlled by BACnetRelay command from BMS (MV 2 must be 1)Write
MV 2Relay AssignmentRelay source; 1 = BACnet controlWrite
MI 1Relay StatusRelay state and trigger sourceRead
AI 1TemperatureAir temperatureRead
AI 2Relative HumidityAir RHRead
AI 3Dewpoint TemperatureCalculated dewpointRead
BI 2Condensation StatusCondensation detected on the pipe probeRead
MI 2Generic Error CodesProbe communication errorRead

Enable & remote start

The relay follows BV 11 only when Relay Assignment (MV 2) is set to 1, Free Control by BACnet.

Network setup

Watch out for

Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

46 of 46 shown
Type
Access
Show
Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1TemperatureTemperature, -20 to 60 °C°C / °FRead
AImin2Relative HumidityRelative humidity, 0-100 %%RHRead
AImin3Dewpoint TemperatureDewpoint, -30 to 60 °C°C / °FRead
AI4Wet Bulb TemperatureWet bulb temperature, -20 to 60 °C°C / °FRead
AI5EnthalpyEnthalpykJ/kg / BTU/lbRead
AI6Absolute HumidityAbsolute humidity, 0-130 g/m3g/m3 / lb/ft3Read
AI7Pipe TemperaturePipe temperature from the condensation probe°C / °FRead
AV1Temperature OffsetTemperature offset, ±5 °C (default 0)delta °C / °FWrite
AV2T Calibration Point1Temperature 2-point calibration, point 1 (default 25 °C)°C / °FWrite
AV3T Calibration Value on Point1Correction at temperature point 1 (default 0)delta °C / °FWrite
AV4T Calibration Point2Temperature 2-point calibration, point 2 (default 30 °C)°C / °FWrite
AV5T Calibration Value on Point2Correction at temperature point 2 (default 0)delta °C / °FWrite
AV6RH OffsetRH offset, ±20 %RH (default 0)%RHWrite
AV7RH Calibration Point1RH 2-point calibration, point 1 (default 40 %RH)%RHWrite
AV8RH Calibration Value on Point1Correction at RH point 1 (default 0)%RHWrite
AV9RH Calibration Point2RH 2-point calibration, point 2 (default 60 %RH)%RHWrite
AV10RH Calibration Value on Point2Correction at RH point 2 (default 0)%RHWrite
AV11AltitudeAltitude, 0-3500 m or 0-11,500 ft (default 0)m / ftWrite
AV12Relay Low SetpointRelay low setpoint; units and range follow MV 2Write
AV13Relay High SetpointRelay high setpoint; units and range follow MV 2Write
AV14Relay HysteresisRelay hysteresis; units and range follow MV 2Write
AV15Relay On TimeRelay on delay, 0-3600 ssWrite
AV16Relay Off TimeRelay off delay, 0-3600 s (default 0)sWrite
AV17Relay Contact Time (for DI only)Relay hold time when driven by the DI, 10-3600 ssWrite
BV1Units SelectUnit systemWrite0=Metric, 1=Imperial
BV2Temperature Display EnableShow temperature on the LCDWrite0=Invisible, 1=Visible
BV3RH Display EnableShow RH on the LCDWrite0=Invisible, 1=Visible
BV4DP Display EnableShow dewpoint on the LCDWrite0=Invisible, 1=Visible
BV5WB Display EnableShow wet bulb on the LCDWrite0=Invisible, 1=Visible
BV6EN Display EnableShow enthalpy on the LCDWrite0=Invisible, 1=Visible
BV7AH Display EnableShow absolute humidity on the LCDWrite0=Invisible, 1=Visible
BV8Pipe Temperature Display EnableShow pipe temperature on the LCDWrite0=Invisible, 1=Visible
BV9Factory RestoreWrite 1 to restore factory settingsWrite0=Normal, 1=Restore
BV10Relay DirectRelay actionWrite0=Direct, 1=Reverse
BVmin11Relay Controlled by BACnetRelay command when MV 2 = Free Control by BACnetWrite0=Relay OFF, 1=Relay ON
BV12Relay TestForces the relay on for testingWrite0=OFF, 1=ON
BI1DI StatusDigital input (active when pulled to common)Read0=Inactive, 1=Active
BImin2Condensation StatusCondensation detectedRead0=Inactive, 1=Active
MV1Backlight SelectLCD backlight mode (default Auto)Write0=Auto, 1=ON, 2=OFF
MVmin2Relay AssignmentSource that drives the relay (default 0)Write0=No Assignment, 1=Free Control by BACnet, 2=DI, 3=Temperature, 4=RH, 5=Dew Point, 6=Wet Bulb, 7=Enthalpy, 8=Absolute Humidity, 9=Condensation
MV3T(Probe) Adjust MethodTemperature calibration method (default None)Write0=None, 1=Offset, 2=2-point
MV4RH(Probe) Adjust MethodRH calibration method (default None)Write0=None, 1=Offset, 2=2-point
MImin1Relay StatusRelay state and what turned it onRead0=OFF, 1=ON by BACnet, 2=ON by DI, 3=ON in test, 4=ON low setpoint alarm, 5=ON high setpoint alarm, 6=ON condensation alarm
MImin2Generic Error CodesProbe communication errorRead0=No Error, 1=Probe Comm Error
MI3Communication Error CodesCommunication error codeRead0=No Error, 1=Unknown
MI4Condensation Error CodesCondensation monitoring errorRead0=No Error, 1=Pipe T Sensor not Connected, 2=Other
Object ID lookup: Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP) have?

This list has 46 BACnet objects: 7 analog inputs, 17 analog values, 2 binary inputs, 12 binary values, 4 multi-state inputs, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP) BACnet points are writable?

33 of the 46 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP) BACnet documentation?

The source is Rough Duty Sensor (NPI-56) RH/T Transmitter - Setup Guide BACnet Communication (HTX1 Series) (SG-HTX1XXXBAC-001), revision 2025-07-08 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-HTX1XXXBAC-001.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP)?

Start with BV 11 Relay Controlled by BACnet (Relay command from BMS (MV 2 must be 1)); MV 2 Relay Assignment (Relay source; 1 = BACnet control); MI 1 Relay Status (Relay state and trigger source); AI 1 Temperature (Air temperature); AI 2 Relative Humidity (Air RH); AI 3 Dewpoint Temperature (Calculated dewpoint); BI 2 Condensation Status (Condensation detected on the pipe probe); MI 2 Generic Error Codes (Probe communication error).

How do I enable BMS control of the Greystone Energy Systems HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP)?

The relay follows BV 11 only when Relay Assignment (MV 2) is set to 1, Free Control by BACnet.

How do I check these points on the real HTX1 Series rough duty RH / temperature transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.