Greenhouse CO2 / RH / temperature sensor · BACnet points list

Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The GH is a Greystone grow-room sensor for temperature, RH and CO2 with native BACnet MS/TP. The three readings are Analog Inputs; offsets and two configurable alarms (setpoint, hysteresis, delay) are Analog Values, and Multi-State Values assign each alarm to CO2, temperature or RH high/low and set the display.

This page lists 21 BACnet objects for the Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP) — 16 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
GH Series horticulture sensor (BACnet MS/TP)
Equipment
Greenhouse CO2 / RH / temperature sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
21 (16 writable)
Transport
BACnet MS/TP
Firmware
1.4 (PICS, March 6, 2019)
Default device instance
381003
Also known as
GH, GHXXXBAC, Greystone greenhouse CO2 RH temperature sensor
Source document
GH Series Horticulture Sensor - Setup Guide BACnet Communication · SG-GHXXXBAC-01 · rev. 05/19
Download CSV 21 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC in the menu, then read temperature, RH and CO2 (AI 1-3). If the relays drive equipment, set the alarm assignment and setpoint once and monitor the alarm BIs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3CO2Room CO2, ppmRead
AI 1TemperatureRoom temperatureRead
AI 2Relative HumidityRoom RHRead
BI 1Alarm 1 StatusAlarm / relay 1 activeRead
BI 2Alarm 2 StatusAlarm / relay 2 activeRead

Network setup

Watch out for

Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

21 of 21 shown
Type
Multi-state
Access
Show
Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1TemperatureTemperature, 0-50 °C°C / °FRead
AImin2Relative HumidityRelative humidity, 0-100 %%RHRead
AImin3CO2CO2, 0-5000 ppmppmRead
AV1Temperature OffsetTemperature offset, ±5 Δ°C (default 0)delta °C / °FWrite
AV2RH OffsetRH offset, ±10 %RH (default 0)%RHWrite
AV3CO2 OffsetCO2 offset, ±300 ppm in 50 ppm steps (default 0)ppmWrite
AV4Alarm 1 SetpointAlarm 1 trip point; range depends on MV 3 assignmentWrite
AV5Alarm 1 HysteresisAlarm 1 hysteresis; range depends on MV 3 assignmentWrite
AV6Alarm 1 DelayAlarm 1 delay, 0-255 s (default 15)sWrite
AV7Alarm 2 SetpointAlarm 2 trip point; range depends on MV 4 assignmentWrite
AV8Alarm 2 HysteresisAlarm 2 hysteresis; range depends on MV 4 assignmentWrite
AV9Alarm 2 DelayAlarm 2 delay, 0-255 s (default 15)sWrite
BV1Temperature UnitsTemperature unit selectWrite0=°C, 1=°F
BV2Relay 1 TestForces relay 1 on; set back to 0 after testWrite0=Normal, 1=Test
BV3Relay 2 TestForces relay 2 on; set back to 0 after testWrite0=Normal, 1=Test
BImin1Alarm 1 StatusAlarm 1 activeRead0=Normal, 1=Alarm
BImin2Alarm 2 StatusAlarm 2 activeRead0=Normal, 1=Alarm
MV1LCD BacklightLCD backlight mode (default Auto)Write1=Auto, 2=Off, 3=On
MV2LCD DisplayValues shown on the LCD (default All)Write1=All, 2=RH, 3=Temp, 4=CO2, 5=RH/Temp, 6=RH/CO2, 7=Temp/CO2, 8=None
MV3Alarm 1 AssignmentWhat alarm 1 / relay 1 watches (default CO2 High)Write1=CO2 High, 2=CO2 Low, 3=Temp High, 4=Temp Low, 5=RH High, 6=RH Low
MV4Alarm 2 AssignmentWhat alarm 2 / relay 2 watches (default CO2 High)Write1=CO2 High, 2=CO2 Low, 3=Temp High, 4=Temp Low, 5=RH High, 6=RH Low
Object ID lookup: Greystone Energy Systems GH Series horticulture sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GH Series horticulture sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP) have?

This list has 21 BACnet objects: 3 analog inputs, 9 analog values, 2 binary inputs, 3 binary values, 4 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP) BACnet points are writable?

16 of the 21 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP) BACnet documentation?

The source is GH Series Horticulture Sensor - Setup Guide BACnet Communication (SG-GHXXXBAC-01), revision 05/19, published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-GHXXXBAC.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems GH Series horticulture sensor (BACnet MS/TP)?

Start with AI 3 CO2 (Room CO2, ppm); AI 1 Temperature (Room temperature); AI 2 Relative Humidity (Room RH); BI 1 Alarm 1 Status (Alarm / relay 1 active); BI 2 Alarm 2 Status (Alarm / relay 2 active).

How do I check these points on the real GH Series horticulture sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: GH Series Horticulture Sensor - Setup Guide BACnet Communication · SG-GHXXXBAC-01 · rev. 05/19. Object names, instances and units are reproduced as published; descriptions are our own.