Carbon monoxide (CO) gas sensor / transmitter · BACnet points list

Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The CMD is a Greystone carbon monoxide transmitter with native BACnet MS/TP. It reports CO and temperature as Analog Inputs, buzzer and relay settings and timers as Analog Values, enables, resets and relay action as Binary Values, and alarm, relay and fault states as Binary Inputs.

This page lists 32 BACnet objects for the Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP) — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
CMD Series CO transmitter (BACnet MS/TP)
Equipment
Carbon monoxide (CO) gas sensor / transmitter
Equipment type
Thermostats, sensors & meters
BACnet objects
32 (24 writable)
Transport
BACnet MS/TP
Firmware
1.2 (PICS, Feb 15, 2016)
Default device instance
381004
Also known as
CMD, CMD5B, CMDXXXBAC, Greystone CMD carbon monoxide
Source document
CMD Series Carbon Monoxide Transmitter - Setup Guide BACnet Communication · SG-CMDXXXBAC-01-01 · rev. 05/19
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC and baud in the local menu, then read CO (AI 1) and the alarm and fault BIs. Relay and buzzer setpoints are stored settings, set once.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1CO Sensor ValueSpace CO, ppmRead
BI 3Relay 1 StatusRelay 1 (fan or alarm stage) activeRead
BI 4Relay 2 StatusRelay 2 active (if fitted)Read
BI 1CO StatusAny CO alarm presentRead
BI 6Fault StatusSensor fault / end-of-life alarmRead

Network setup

Watch out for

Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

32 of 32 shown
Type
Access
Show
Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1CO Sensor ValueCO concentrationppmRead
AI2TemperatureTemperature; units follow BV 9 (space models only)°C / °FRead
AV1Buzzer SetpointBuzzer alarm level, 20-500 ppm (default 150)ppmWrite
AV2Buzzer DelayBuzzer delay, 0-10 min (default 5)minWrite
AV3Relay 1 SetpointRelay 1 trip level, 20-500 ppm (default 50)ppmWrite
AV4Relay 1 HysteresisRelay 1 hysteresis, 10-100 ppm (default 10)ppmWrite
AV5Relay 1 DelayRelay 1 delay, 0-10 min (default 2)minWrite
AV6Relay 2 SetpointRelay 2 trip level, 20-500 ppm (default 150)ppmWrite
AV7Relay 2 HysteresisRelay 2 hysteresis, 10-100 ppm (default 20)ppmWrite
AV8Relay 2 DelayRelay 2 delay, 0-10 min (default 2)minWrite
AV9Test Mode TimeTest mode duration, 1-15 min (default 5)minWrite
AV10Output TestOutput test selection, 0-6 (default 0)Write
AV11Fault Mode TimeSensor-life fault timer: 3, 4, 5 or 6 years (default 3)yearsWrite
AV12ReCal Mode TimeRecalibration reminder: 1, 2 or 3 years (default 1)yearsWrite
AV13Temperature OffsetTemperature calibration offset (default 0)delta °C / °FWrite
BV1Buzzer Enable/DisableBuzzer enable (normally 1)Write0=Disabled, 1=Enabled
BV2Fault Mode Enable/DisableSensor-life fault alarm enable (normally 0)Write0=Disabled, 1=Enabled
BV3Fault Mode ResetWrite 1 to reset the fault mode and its timerWrite0=Normal, 1=Reset
BV4Display ModeShow CO on the LCD (0 hides the reading)Write0=Suppress CO reading, 1=Show
BV5Backlight Enable/DisableLCD backlight enable (normally 1)Write0=Disabled, 1=Enabled
BV6Test Mode Enable/DisableWrite 1 to start test modeWrite0=Off, 1=Test mode
BV7ReCal Mode Enable/DisableRecalibration reminder alarm enable (normally 1)Write0=Disabled, 1=Enabled
BV8ReCal Mode ResetWrite 1 to reset the recal reminder and its timerWrite0=Normal, 1=Reset
BV9Temperature UnitsTemperature unit selectWrite0=°C, 1=°F
BV10Relay 1 OperationRelay 1 actionWrite0=Direct, 1=Reverse
BV11Relay 2 OperationRelay 2 actionWrite0=Direct, 1=Reverse
BImin1CO StatusAny alarm presentRead0=Normal, 1=Alarm
BI2Buzzer StatusBuzzer activeRead0=Off, 1=Active
BImin3Relay 1 StatusRelay 1 activeRead0=Off, 1=Active
BImin4Relay 2 StatusRelay 2 activeRead0=Off, 1=Active
BI5Test Mode StatusTest mode runningRead0=Off, 1=Active
BImin6Fault StatusFault alarm activeRead0=Normal, 1=Fault
Object ID lookup: Greystone Energy Systems CMD Series CO transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CMD Series CO transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP) have?

This list has 32 BACnet objects: 2 analog inputs, 13 analog values, 6 binary inputs, 11 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP) BACnet points are writable?

24 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP) BACnet documentation?

The source is CMD Series Carbon Monoxide Transmitter - Setup Guide BACnet Communication (SG-CMDXXXBAC-01-01), revision 05/19, published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/Website%20Documents/CMD/SG-CMDXXXBAC.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems CMD Series CO transmitter (BACnet MS/TP)?

Start with AI 1 CO Sensor Value (Space CO, ppm); BI 3 Relay 1 Status (Relay 1 (fan or alarm stage) active); BI 4 Relay 2 Status (Relay 2 active (if fitted)); BI 1 CO Status (Any CO alarm present); BI 6 Fault Status (Sensor fault / end-of-life alarm).

How do I check these points on the real CMD Series CO transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: CMD Series Carbon Monoxide Transmitter - Setup Guide BACnet Communication · SG-CMDXXXBAC-01-01 · rev. 05/19. Object names, instances and units are reproduced as published; descriptions are our own.