Easy BACnet
  1. Home
  2. BACnet points lists
  3. Greystone Energy Systems
  4. DW Series duct / outside air dewpoint transmitter (BACnet MS/TP)

Duct / outdoor dewpoint and humidity sensor · BACnet points list

Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The DW is a Greystone duct or outside-air dewpoint transmitter with native BACnet MS/TP. It reports temperature, RH and calculated dewpoint, wet bulb and enthalpy as Analog Inputs; Analog Values hold offsets and barometric pressure/altitude, Binary Values select units, and one Multi-State Value picks what the LCD shows.

This page lists 12 BACnet objects for the Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
DW Series duct / outside air dewpoint transmitter (BACnet MS/TP)
Equipment
Duct / outdoor dewpoint and humidity sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
12 (7 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS, July 27, 2022)
Also known as
DW, DPDDB, DPODB, DWXXXBAC, Greystone duct dewpoint sensor, HTX2, HTX2XXXBAC, Greystone HTX2 high accuracy humidity transmitter
Source document
DW Series Dewpoint Transmitter - Setup Guide BACnet Communication · SG-DWXXXBAC-002 · rev. 2022-07-27 (PICS date)
Download CSV 12 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC and baud in the menu, set the altitude or barometric pressure for the site, then read dewpoint, temperature and RH.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 3Dewpoint TemperatureDuct or outdoor dewpointRead
AI 1TemperatureDuct or outdoor air temperatureRead
AI 2Relative HumidityDuct or outdoor RHRead
AI 5EnthalpyAir enthalpy, kJ/kg or BTU/lbRead

Network setup

Watch out for

Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

12 of 12 shown
Type
BinaryMulti-state
Access
Show
Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1TemperatureTemperature, -30 to 50 °C°C / °FRead
AImin2Relative HumidityRelative humidity, 0-100 %%RHRead
AImin3Dewpoint TemperatureCalculated dewpoint°C / °FRead
AI4Wet Bulb TemperatureCalculated wet bulb temperature°C / °FRead
AImin5EnthalpyCalculated enthalpykJ/kg / BTU/lbRead
AV1Temperature OffsetTemperature offset, ±5 Δ°C or ±10 Δ°F (default 0)delta °C / °FWrite
AV2RH OffsetRH offset, ±10 %RH (default 0)%RHWrite
AV3Atmospheric PressureBarometric pressure for calculations, 812-1013 hPa (default 1013)hPaWrite
AV4AltitudeAltitude, 0-6000 ft (default 0); linked to AV 3ftWrite
BV1Temperature UnitTemperature unit selectWrite0=°C, 1=°F
BV2Enthalpy UnitEnthalpy unit selectWrite0=kJ/kg, 1=BTU/lb
MV1Display ModeLCD display selection (default 1)Write1=Dew Point T, 2=Temperature, 3=Wet Bulb T, 4=RH, 5=Enthalpy, 6=T+dewpoint, 7=T+wet bulb, 8=T+RH, 9=T+enthalpy, 10=Dewpoint+wet bulb, 11=Dewpoint+RH, 12=Dewpoint+enthalpy, 13=Wet bulb+RH, 14=Wet bulb+enthalpy, 15=RH+enthalpy
Object ID lookup: Greystone Energy Systems DW Series duct / outside air dewpoint transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the DW Series duct / outside air dewpoint transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP) have?

This list has 12 BACnet objects: 5 analog inputs, 4 analog values, 2 binary values, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP) BACnet points are writable?

7 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP) BACnet documentation?

The source is DW Series Dewpoint Transmitter - Setup Guide BACnet Communication (SG-DWXXXBAC-002), revision 2022-07-27 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-DWXXXBAC-002.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems DW Series duct / outside air dewpoint transmitter (BACnet MS/TP)?

Start with AI 3 Dewpoint Temperature (Duct or outdoor dewpoint); AI 1 Temperature (Duct or outdoor air temperature); AI 2 Relative Humidity (Duct or outdoor RH); AI 5 Enthalpy (Air enthalpy, kJ/kg or BTU/lb).

How do I check these points on the real DW Series duct / outside air dewpoint transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: DW Series Dewpoint Transmitter - Setup Guide BACnet Communication · SG-DWXXXBAC-002 · rev. 2022-07-27 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.