CO2 sensor / transmitter · BACnet points list

Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The CDD3 is a Greystone CO2 transmitter with native BACnet MS/TP. It reports CO2 and, when fitted, RH, temperature and a setpoint adjust value as Analog Inputs, with Analog and Binary Values for relay setup, calibration offsets and units. Objects for options that are not installed stay in the list but report a fault.

This page lists 19 BACnet objects for the Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP) — 13 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
CDD3 Series CO2 transmitter (BACnet MS/TP)
Equipment
CO2 sensor / transmitter
Equipment type
Thermostats, sensors & meters
BACnet objects
19 (13 writable)
Transport
BACnet MS/TP
Firmware
1.0 (PICS, April 21, 2022)
Default device instance
381003
Also known as
CDD3, CDD3A1XXXBAC, CDD3 BACnet, Greystone CDD3 CO2
Source document
CDD3 Series Carbon Dioxide Transmitter - Setup Guide BACnet Communication · SG-CDD3A1XXXBAC-003 · rev. 2022-04-21 (PICS date)
Download CSV 19 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP)

Integration in brief

Give each sensor a unique MS/TP MAC and device instance from the menu, then read CO2 (AI 1) and any fitted RH and temperature inputs. The relay setpoint and offsets are setup values.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1CO2 ValueSpace CO2, ppmRead
AI 2RH ValueSpace RH (RH option)Read
AI 3Temperature ValueSpace temperature (temperature option)Read
BI 1Relay StatusCO2 relay energizedRead

Network setup

Watch out for

Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

19 of 19 shown
Type
Multi-state
Access
Show
Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1CO2 ValueCO2 reading, 0-10,000 ppmppmRead
AImin2RH ValueRelative humidity (RH option)%RHRead
AImin3Temperature ValueTemperature (temperature option); units follow BV 1°F / °CRead
AI4Setpoint ValueLocal setpoint adjust value (setpoint option)%Read
AV1Relay SetpointCO2 relay trip point, 500-1500 ppm (default 1000)ppmWrite
AV2Relay HysteresisRelay hysteresis, 25-200 ppm (default 50)ppmWrite
AV3Relay ON DelayRelay on delay, 0-255 s (default 15)sWrite
AV4Temperature OffsetTemperature calibration offset (default 0)delta °C / °FWrite
AV5RH OffsetRH calibration offset, -10 to 10 %RH%RHWrite
AV6AltitudeInstalled altitude, 0-2550 m in 50 m stepsmWrite
BV1Temperature UnitsTemperature unit selectWrite0=°C, 1=°F
BV2Auto Cal EnableCO2 automatic calibration (default enabled)Write0=Disable, 1=Enable
BV3Relay TestForces the relay for testingWrite0=Relay off, 1=Relay on
BV4Override TestOverride on/off (object page name: Override Operation)Write0=Off, 1=On
BImin1Relay StatusCO2 relay energizedRead0=Inactivated, 1=Activated
BI2Override StatusOverride activeRead0=Inactivated, 1=Activated
MV1LCD BacklightLCD backlight mode (default Auto)Write0=AUTO, 1=OFF, 2=ON
MV2Display ModesValues shown on the LCDWrite0=CO2, 1=CO2+RH, 2=CO2+T, 3=CO2+RH+T
MV3Setpoint ModesSetpoint adjust scale (default %)Write0=%, 1=°C1, 2=°C2, 3=°F1, 4=°F2, 5=%RH, 6=ppm
Object ID lookup: Greystone Energy Systems CDD3 Series CO2 transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CDD3 Series CO2 transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP) have?

This list has 19 BACnet objects: 4 analog inputs, 6 analog values, 2 binary inputs, 4 binary values, 3 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP) BACnet points are writable?

13 of the 19 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP) BACnet documentation?

The source is CDD3 Series Carbon Dioxide Transmitter - Setup Guide BACnet Communication (SG-CDD3A1XXXBAC-003), revision 2022-04-21 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-CDD3A1XXXBAC-003.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems CDD3 Series CO2 transmitter (BACnet MS/TP)?

Start with AI 1 CO2 Value (Space CO2, ppm); AI 2 RH Value (Space RH (RH option)); AI 3 Temperature Value (Space temperature (temperature option)); BI 1 Relay Status (CO2 relay energized).

How do I check these points on the real CDD3 Series CO2 transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: CDD3 Series Carbon Dioxide Transmitter - Setup Guide BACnet Communication · SG-CDD3A1XXXBAC-003 · rev. 2022-04-21 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.