Room temperature / humidity sensor · BACnet points list

Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The NTRC is a Greystone wall sensor with native BACnet MS/TP. It reports temperature, optional RH and the fan speed switch as Analog Inputs; the local setpoint, its limits, offsets and display/override settings are Analog Values; Binary Values carry units, override status and a BMS-controlled relay, and a Binary Input reports the digital input.

This page lists 19 BACnet objects for the Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP) — 15 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
NTRC Series temperature / humidity room sensor (BACnet MS/TP)
Equipment
Room temperature / humidity sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
19 (15 writable)
Transport
BACnet MS/TP
Firmware
1.3 (PICS, Oct 4, 2017)
Default device instance
381003
Also known as
NTRC, NTRCXXXBAC, STAT, Greystone NTRC network room sensor
Source document
Temperature/Humidity Sensor NTRC Series - Setup Guide BACnet Communication · SG-NTRCXXXBAC-003 · rev. 2017-10-04 (PICS date)
Download CSV 19 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP)

Integration in brief

Set the MS/TP MAC in the menu, then read room temperature, RH, setpoint and override status. The BMS can switch the optional relay with BV 4 and must reset a latched override by writing 0 to BV 3.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 4Relay EnableRelay command, 1 = on (relay option)Write
AI 1TemperatureRoom temperatureRead
AI 2Relative HumidityRoom RH (option)Read
AV 1SetpointOccupant setpoint from the front panelWrite
AI 3Fan SpeedFan switch: 0 Auto, 1 Off, 2-4 Low-HighRead
BV 3Override StatusOverride pressed; write 0 to clear (latch)Write

Network setup

Watch out for

Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

19 of 19 shown
Type
Access
Show
Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1TemperatureRoom temperature, 0.1° resolution°C / °FRead
AImin2Relative HumidityRoom RH (RH option)%RHRead
AImin3Fan SpeedFan speed switch position (fan switch option)Read0=Auto, 1=Off, 2=Low, 3=Med, 4=High
AVmin1SetpointFront panel setpoint (temperature or RH per BV 5)°C / °F / %RHWrite
AV2Temperature OffsetTemperature offset, ±5 °C or ±10 °F (default 0)delta °C / °FWrite
AV3RH OffsetRH offset, ±10 %RH (default 0)%RHWrite
AV4Setpoint MinimumLowest allowed setpoint (default 5 °C / 41 °F / 40 %RH)°C / °F / %RHWrite
AV5Setpoint MaximumHighest allowed setpoint (default 50 °C / 122 °F / 60 %RH)°C / °F / %RHWrite
AV6Display ModeLCD display selectionWrite0=No display, 1=Temperature only, 2=RH only, 3=Temperature and RH toggle
AV7Override ModeOverride button behaviour (default 0)Write0=LATCH, 1=TOGGLE, 2=MOMENTARY
AV8Override Mode TimeMomentary override time, 1-60 min (default 1)minWrite
AV9Temperature ResolutionLCD temperature resolution (default 0)Write0=1°, 1=0.5°, 2=0.1°
BV1Temperature UnitsTemperature unit selectWrite0=°C, 1=°F
BV2OCC EnableShows the OCC segment on the LCDWrite0=OCC Off, 1=OCC On
BVmin3Override StatusOverride button pressed; write 0 to reset in latch modeWrite0=Inactive, 1=Override
BVmin4Relay EnableOptional relay commandWrite0=Relay Off, 1=Relay On
BV5Setpoint ModeWhat the front setpoint adjustsWrite0=Temperature, 1=%RH
BV6Setpoint ResolutionSetpoint step sizeWrite0=1 degree, 1=0.5 degree
BI1DI OnDigital input (DI models; active when pulled to common)Read0=Inactive, 1=Active
Object ID lookup: Greystone Energy Systems NTRC Series temperature / humidity room sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the NTRC Series temperature / humidity room sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP) have?

This list has 19 BACnet objects: 3 analog inputs, 9 analog values, 1 binary input, 6 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP) BACnet points are writable?

15 of the 19 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP) BACnet documentation?

The source is Temperature/Humidity Sensor NTRC Series - Setup Guide BACnet Communication (SG-NTRCXXXBAC-003), revision 2017-10-04 (PICS date), published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/SG/SG-NTRCXXXBAC-003.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems NTRC Series temperature / humidity room sensor (BACnet MS/TP)?

Start with BV 4 Relay Enable (Relay command, 1 = on (relay option)); AI 1 Temperature (Room temperature); AI 2 Relative Humidity (Room RH (option)); AV 1 Setpoint (Occupant setpoint from the front panel); AI 3 Fan Speed (Fan switch: 0 Auto, 1 Off, 2-4 Low-High); BV 3 Override Status (Override pressed; write 0 to clear (latch)).

How do I check these points on the real NTRC Series temperature / humidity room sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: Temperature/Humidity Sensor NTRC Series - Setup Guide BACnet Communication · SG-NTRCXXXBAC-003 · rev. 2017-10-04 (PICS date). Object names, instances and units are reproduced as published; descriptions are our own.