 "manufacturer": "Greystone Energy Systems",
 "manufacturer_slug": "greystone",
 "model": "DPRC Series room dewpoint transmitter (BACnet MS/TP)",
 "model_slug": "dprc-room-dewpoint-transmitter",
 "aliases": [
  "DPRC",
  "DPRCB",
  "DPRCXXXBAC",
  "Greystone room dewpoint sensor"
 ],
 "equipment_type": "Room dewpoint / humidity sensor",
 "applies_to": "Greystone DPRC series room dewpoint transmitters (PICS model DPRCB) with BACnet MS/TP.",
 "summary": "The DPRC is a Greystone room sensor that measures temperature and RH and calculates dewpoint, wet bulb and enthalpy, all reported as Analog Inputs over native BACnet MS/TP. Analog Values hold offsets, barometric pressure/altitude and the display mode; two Binary Values pick the units.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "1.4 (PICS, Feb 21, 2017)",
 "default_device_instance": 381001,
 "access_inferred": false,
 "notes": [
  "Points from the object table on page 2 of the setup guide.",
  "The object pages spell BV 1 and BV 2 as \"Temperature Units\" and \"Enthalpy Units\"; the table uses the singular.",
  "Dewpoint, wet bulb and enthalpy are calculated from the temperature and RH readings.",
  "Access from the object pages and PICS: AV and BV Present_Value are writable."
 ],
 "source": {
  "title": "DPRC Series Room Dewpoint Transmitter - Setup Guide for BACnet Communication",
  "doc_number": "SG-DPRCXXXBAC-01",
  "revision_date": "2017-02-21 (PICS date)",
  "url": "https://downloads.greystoneenergy.com/SG/SG-DPRCXXXBAC.pdf"
 },
 "integration": {
  "summary": "Set the MS/TP MAC and baud in the menu, set the altitude or barometric pressure for the site, then read the temperature, RH and dewpoint AIs.",
  "minimum_points": [
   {
    "ref": "AI 3",
    "name": "Dewpoint Temperature",
    "why": "Room dewpoint"
   },
   {
    "ref": "AI 1",
    "name": "Temperature",
    "why": "Room temperature"
   },
   {
    "ref": "AI 2",
    "name": "Relative Humidity",
    "why": "Room RH"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Device instance is 381000 + the MS/TP MAC set in the menu; it stops tracking the MAC once written over BACnet.",
   "MS/TP baud rates 9600-115200 are supported; Max_Master defaults to 127 and is writable."
  ],
  "gotchas": [
   "Atmospheric Pressure and Altitude are linked; set one to match the site so the psychrometric values are right.",
   "Enthalpy units follow the enthalpy unit BV (kJ/kg or BTU/lb); temperatures follow the temperature unit BV."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Temperature",
   "description": "Temperature, -30 to 50 °C",
   "units": "°C / °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Relative Humidity",
   "description": "Relative humidity, 0-100 %",
   "units": "%RH",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Dewpoint Temperature",
   "description": "Calculated dewpoint",
   "units": "°C / °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Wet Bulb Temperature",
   "description": "Calculated wet bulb temperature",
   "units": "°C / °F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Enthalpy",
   "description": "Calculated enthalpy",
   "units": "kJ/kg / BTU/lb",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Temperature Offset",
   "description": "Temperature offset, ±5 Δ°C or ±10 Δ°F (default 0)",
   "units": "delta °C / °F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "RH Offset",
   "description": "RH offset, ±10 %RH (default 0)",
   "units": "%RH",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Atmospheric Pressure",
   "description": "Barometric pressure for calculations, 812-1013 hPa (default 1013)",
   "units": "hPa",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Altitude",
   "description": "Altitude, 0-6000 ft (default 0); linked to AV 3",
   "units": "ft",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Display Mode",
   "description": "LCD display selection, 0-10",
   "units": "",
   "access": "W",
   "states": "0=No display, 1=Temperature, 2=Dewpoint, 3=Wet bulb, 4=Enthalpy, 5=T+dewpoint, 6=T+wet bulb, 7=T+enthalpy, 8=Dewpoint+wet bulb, 9=Dewpoint+enthalpy, 10=Wet bulb+enthalpy"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Temperature Unit",
   "description": "Temperature unit select",
   "units": "",
   "access": "W",
   "states": "0=°C, 1=°F"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "Enthalpy Unit",
   "description": "Enthalpy unit select",
   "units": "",
   "access": "W",
   "states": "0=kJ/kg, 1=BTU/lb"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/greystone/dprc-room-dewpoint-transmitter",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}