Humidity / temperature sensor · BACnet points list

Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

Duct and outside air RH/temperature sensors with native BACnet MS/TP. Temperature and humidity are two Analog Inputs, each with an offset Analog Value, and one Binary Value switches °C/°F. The MAC address is set with DIP switches.

This page lists 5 BACnet objects for the Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Greystone Energy Systems’s own free documentation, linked below.

Manufacturer
Greystone Energy Systems
Model
NT Series duct / outside air RH and temperature sensor (BACnet MS/TP)
Equipment
Humidity / temperature sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
5 (3 writable)
Transport
BACnet MS/TP
Firmware
Firmware 1.2
Default device instance
381001
Also known as
NTDABAC, NTOABAC, NTDA, NTOA, NTDABACXXX, Greystone NT duct RH sensor, Greystone NT outside air RH sensor
Source document
Duct RH/Temp Sensor NTDABAC Installation Instructions · IN-GE-NTDABACXXX-01-01 · rev. 01/16
Download CSV 5 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Greystone Energy Systems’s current documentation and the live device before use. Not official Greystone Energy Systems information. Terms of use.

BMS integration notes: Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP)

Integration in brief

Set the MAC with the DIP switches, then read AI 1 and AI 2. Choose units with BV 1 before writing offsets.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1TemperatureMeasured temperatureRead
AI 2Relative HumidityMeasured relative humidityRead

Network setup

Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

5 of 5 shown
Type
Binary
Access
Show
Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1TemperatureTemperature, 0.1° resolution°C / °FRead
AImin2Relative HumidityRelative humidity, 0.1 % resolution%RHRead
AV1Temperature OffsetOffset, ±5 °C / ±10 °F (default 0)°C / °FWrite
AV2RH OffsetOffset, ±10 %RH (default 0)%RHWrite
BV1Temperature UnitsTemperature units (default °C)Write0=°C, 1=°F
Object ID lookup: Greystone Energy Systems NT Series duct / outside air RH and temperature sensor point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the NT Series duct / outside air RH and temperature sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP)

How many BACnet points does the Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP) have?

This list has 5 BACnet objects: 2 analog inputs, 2 analog values, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP) BACnet points are writable?

3 of the 5 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP) BACnet documentation?

The source is Duct RH/Temp Sensor NTDABAC Installation Instructions (IN-GE-NTDABACXXX-01-01), revision 01/16, published free by Greystone Energy Systems at https://downloads.greystoneenergy.com/Install%20Notes/IN-GE-NTDABACXXX.pdf.

What are the minimum BACnet points to integrate the Greystone Energy Systems NT Series duct / outside air RH and temperature sensor (BACnet MS/TP)?

Start with AI 1 Temperature (Measured temperature); AI 2 Relative Humidity (Measured relative humidity).

How do I check these points on the real NT Series duct / outside air RH and temperature sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Greystone Energy Systems BACnet points lists

Source: Duct RH/Temp Sensor NTDABAC Installation Instructions · IN-GE-NTDABACXXX-01-01 · rev. 01/16. Object names, instances and units are reproduced as published; descriptions are our own.