Water-source DOAS controller with energy recovery · BACnet points list

WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC) BACnet points list

Updated 6 November 2026

Short answer

BACnet point list for the WaterFurnace Versatec 700 indoor DOAS. System points cover enable, emergency shutdown, occupancy, SAT targets and reset, blower and duct static control, sensor sources and BAS overrides, dehumidification and reheat, DCV and water- and air-side economizers. Each of up to four heat pump modules has its own block (unit 1 below 100, units 2-4 in the 1000s, 2000s and 3000s), and the energy recovery unit sits in the 9000s.

This page lists 748 BACnet objects for the WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC) — 252 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.

Manufacturer
WaterFurnace
Model
Versatec 700 Indoor DOAS (Aurora UPC)
Equipment
Water-source DOAS controller with energy recovery
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
748 (252 writable)
Transport
—
Firmware
Not stated
Also known as
Versatec 700, Versatec DOAS, WaterFurnace DOAS, DOAS BACnet Point List 1.00
Source document
DOAS BACnet Point List · rev. Version 1.00
Download CSV 748 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WaterFurnace’s current documentation and the live device before use. Not official WaterFurnace information. Terms of use.

BMS integration notes: WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC)

Integration in brief

Enable the system with BV 302, pick the external schedule on BV 401 and drive occupancy with BV 400 (or MV 315 for standby and temporary occupancy). Set the cooling and heating SAT targets and reset options, and read mode, supply air temperature and the per-unit fault codes.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 302sys_enable_cSystem enable for network and setpoint controlWrite
BV 2e_stop_cEmergency shutdown commandWrite
BV 400occ_command_cOccupancy command (external schedule)Write
BV 401sched_select_cMust be External for BV 400 to applyWrite
AV 305targ_clg_sat_cCooling supply air temperature targetWrite
AV 306targ_htg_sat_cHeating supply air temperature targetWrite
BV 8alarm_reset_cAlarm resetWrite
MV 11mode_st_msvUnit operating modeRead
AV 500sat_stSupply air temperature in useRead
AV 7system_fault1_stUnit 1 fault or lockout codeRead

Enable & remote start

BV 302 sys_enable_c enables the system for network and setpoint control. BV 2 e_stop_c is the emergency shutdown, BV 102 a shutdown that keeps the exhaust fan running, and BV 4 load shed. Occupancy follows the internal schedule unless BV 401 is set to External; then BV 400 or MV 315 set the occupancy mode.

Sensors & values from the BMS

Each sensed value has a source selector and a BAS override: MV 303-307 and MV 311 pick Rnet sensor, unit/ERW sensor or BAS for supply, return, space and outdoor values, written on AV 502/505/512/515/522/525/532/535. MV 309/310/312/314 pick BAS or AEC for the energy recovery inputs (AV 9024-9065). AV 551 takes a BAS DOAS control temperature, AV 343 a BAS duct static value, and AV 591/593 BAS CO2 and VOC.

Network setup

Watch out for

WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

748 of 748 shown
Type
BinaryMulti-state
Access
Show
WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC) BACnet Points List
DescriptionStates
AV3mode_stCurrent operating mode of the heat pump system (numeric)Read
AV4filter_alarm_hrs_cBlower run hours before the filter alarm (default 1000)hrWrite
AV5filter_hours_stBlower run hours since the last filter alarm resethrRead
AV200valve_min_pos_cSets the minimum modulating valve position (Minimum variable speed pump operating speed) (default 50)%Write
AV201valve_max_pos_cSets the maximum modulating valve position (Maximum variable speed pump operating speed) (default 100)%Write
AV202valve_delay_cSets the delay for a slow opening water valve (default 60)secondsWrite
AV490morn_warm_rat_cSets the target return air temperature for morning warm-up operation (default 65)°FWrite
AV491morn_warm_time_cSets the maximum opertaing time for the morning warm-up mode (default 60)minWrite
AV492morn_cool_rat_cSets the target return air temperature for morning cool-down operation (default 75)°FWrite
AV493morn_cool_time_cSets the maximum opertaing time for the morning cool-down mode (default 60)minWrite
AV494morn_samp_cSets the minimum morning warm-up / cool-down operating time (default 5)minWrite
AV550doas_ctrl_temp_stCurrent control temperture for DOAS heat pump operation°FRead
AV551dctrlt_override_cBAS-written DOAS control temperature value (default 70)°FWrite
AV580atm_pres_stCurrent atmospheric pressure value being used for enthalpy calculationspsiRead
AV581atm_pres_cBAS-written current atmospheric pressure for enthalpy calculations (default 14.1)psiWrite
AV582elev_feet_cBAS-written site elevation for enthalpy calculations (default 1000)ftWrite
BVmin2e_stop_cEmergency shutdown command to the unitWriteInactive=Normal Operation, Active=Shutdown
BV3e_stop_stStatus of the emergency shutdown operationReadInactive=Normal, Active=Shutdown
BV4load_shed_cEnable/disable load shedWriteInactive=Off, Active=On
BV5loadshed_stStatus of the load shed operationReadInactive=Normal, Active=Load Shed
BV6heat_cool_stOperating mode from reversing valve positionReadInactive=Heat, Active=Cool
BVmin8alarm_reset_cCommand the alarm resetWriteInactive=Off, Active=On
BV10dirty_filter_alarm_stStatus of the dirty filter alarm logicReadInactive=Off, Active=On
BV11filter_alm_reset_cDirty filter alarm to be resetWriteInactive=Off, Active=On
BV300sys_demand_cSelects the system demand controlWriteInactive=Discrete, Active=Setpoint
BVmin302sys_enable_cEnables system for network and setpoint controlWriteInactive=Disabled, Active=Enabled
BV305vav_blow_cEnables blower operation for VAVWriteInactive=Inactive, Active=Active
BV306vav_cool_cEnables VAV cooling operationWriteInactive=Inactive, Active=Active
BV307vav_heat_cEnables VAV heating operationWriteInactive=Inactive, Active=Active
BV308dehum_cEnables dehumidifcation operationWriteInactive=Inactive, Active=Active
BV382pres_select_cSelects between atmospheric pressure and elevation for enthalpy calculationsWriteInactive=Pressure, Active=Elevation
BV410valid_ctIndicates if a valid control temperature value is selected and presentReadInactive=Invalid, Active=Valid
BV411valid_ch_stIndicates if a valid control humidity value is selected and presentReadInactive=Invalid, Active=Valid
BV412valid_dew_stIndicates if a valid control dew point value is selected and presentReadInactive=Invalid, Active=Valid
BV490morn_warm_en_cEnables the morning warm-up modeWriteInactive=Disabled, Active=Enabled
BV491morn_cool_en_cEnables the morning cool-down modeWriteInactive=Disabled, Active=Enabled
MVmin11mode_st_msvCurrent operating mode of the unitRead1=Standby, 2=Blower Only, 3=Economizer Only, 4=Economizer with Compressor, 5=Compressor Cooling, 6=Compressor Heating, 7=Modulating Reheat - SAT Control, 8=Modulating Reheat - Dehumidification, 9=Emergency Shutdown, 10=Load Shed, 11=Test Mode, 12=Fault / Lock Out Unit 1, 13=Fault / Lockout Unit 2, 14=Fault / Lockout Unit 3, 15=Fault / Lockout Unit 4, 16=Fault / Lockout Multiple Units, 17=Fault / Lock Out All Units
MV301sys_config_cSelects the system blower control configuration (default 1)Write1=Multizone VAV, 2=Single Zone VAV, 3=CAV
MV302doas_demand_cSelects the type fo DOAS SAT control (default 1)Write1=Single Target SAT, 2=Discrete Demand Selection of Target SAT, 3=Setpoint Demand Selection of Target SAT
MV317ctrl_t_select_cSelects the control temperature for setpoint operation (default 1)Write1=Space Temperature, 2=Return Air Temperature, 3=BAS Supplied Temperature, 4=Outdoor Temperature (DOAS Only)
MV332doas_ctrl_t_select_cSets the control temperture for DOAS heat pump operation (default 2)Write1=BAS, 2=Return Air, 3=Outdoor Air, 4=Entering Air
AV6abc_fault1_stCurrent ABC fault code value for unit 1Read
AVmin7system_fault1_stSystem fault or lockout code, unit 1Read
AV10mod_valve_pwm1_stCurrent modulating water valve position for unit 1%Read
AV11eev1_stCurrent EEV position for unit 1%Read
AV12coax_temp1_stCoax temperature read by the FP1 sensor for unit 1°FRead
AV13air_coil_temp1_stAir coil temperature (FP2) for unit 1°FRead
AV14lat1_stLeaving air temperature for unit 1°FRead
AV15suct_press1_stSuction pressure for unit 1psiRead
AV16sat_evap_temp1_stCalculated saturated (suction) evaporator temperature for unit 1°FRead
AV17super_heat1_stCalculated super-heat value for unit 1°FRead
AV18dischg_press1_stDischarge pressure of the compressor for unit 1psiRead
AV19dischg_temp1_stCompressor discharge temperature for unit 1°FRead
AV20suct_temp1_stSuction temperature for unit 1°FRead
AV21hgt_subcooling1_stCalculated subcooling while operating in heating for unit 1°FRead
AV22clg_subcooling1_stCalculated subcooling while operating in cooling for unit 1°FRead
AV23liq_line_temp1_stLiquid line temperature for unit 1°FRead
AV24lwt1_stLeaving water temperature for unit 1°FRead
AV25ewt1_stEntering water temperature for unit 1°FRead
AV26water_flow1_stCalculated GPM thru the heat exchanger for unit 1gpmRead
AV27cond_temp1_stCalculated saturated (discharge) condenser temperature for unit 1°FRead
AV28entering_air1_stEntering air temperature (HWT) for unit 1°FRead
AV30control_voltage1_stABC's low voltage control value for unit 1VRead
AV31est_line_voltage1_stEstimated line voltage to the unit for unit 1VRead
AV32line_volts1_stLine voltage measured by the compressor drive for unit 1VRead
AV33vdc_volts1_stInverter DC voltage measured by the compressor drive for unit 1VRead
AV34invert_temp1_stMeasured inverter temperature for unit 1°FRead
AV35drive_temp1_stMeasured compressor drive temperature for unit 1°FRead
AV36fan_current1_stMeasured fan current for unit 1ARead
AV37aux_current1_stMeasured auxiliary heat current for unit 1ARead
AV38comp_current1_stMeasured compressor current for unit 1ARead
AV40total_current1_stMeasured total current value for unit 1ARead
AV41comp_power1_stCompressor power consumption for unit 1WRead
AV42fan_power1_stCalculated fan power consumption for unit 1WRead
AV43aux_power1_stCalculated auxiliary heat power consumption for unit 1WRead
AV44total_power1_stTotal power consumption for unit 1WRead
AV46total_capacity1_stTotal BTU operating capacity for unit 1Btu/hrRead
AV47he_hr1_stCalculated heat of extraction/rejection for unit 1Btu/hrRead
AV48co_of_perf1_stCalculated COP value for unit 1Read
AV49eer1_stCalculated EER value for unit 1Read
AV50reheat_valve_pos1_stCurrent position of MHGR valve for unit 1%Read
AV62measured_line_voltage_cCalibrate the measured line voltage for all units (default 230)VWrite
AV209eev_start1_cSets the initial EEV position for unit 1 (default 50)Write
BV12modbus_comm_alarm1_stABC-to-UPC Modbus communication status, unit 1ReadInactive=Communication Normal, Active=Communication Lost
BV13lockout1_stStatus of the lockout alarm output for unit 1ReadInactive=Normal, Active=Lockout
BV14lockout_hdw1_stStatus of the relay for the ABC's Lockout output for unit 1ReadInactive=Normal, Active=Lockout
BV15alm_rht_hdw1_stStatus of the ABC's alarm output for unit 1ReadInactive=Off, Active=On
BV17fp1_lim1_stCurrent FP1 freeze detection set point for unit 1ReadInactive=15°, Active=30°
BV18fp2_lim1_stCurrent FP2 freeze detection set point for unit 1ReadInactive=Not Used, Active=30°
BV19rhstat1_stStatus of the SW2-3 dipswitch for unit 1ReadInactive=Off, Active=On
BV20sw_2_4_1_stStatus of the SW2-4 dipswitchReadInactive=Off, Active=On
BV21sw_2_5_1_stStatus of the SW2-5 dipswitchReadInactive=Off, Active=On
BV25y1_hdw1_stStatus of the "Y1" input to the ABC for unit 1ReadInactive=Off, Active=On
BV26y2_hdw1_stStatus of the "Y2" input to the ABC for unit 1ReadInactive=Off, Active=On
BV27w_hdw1_stStatus of the "W" input to the ABC for unit 1ReadInactive=Off, Active=On
BV28o_hdw1_stStatus of the "O" input to the ABC for unit 1ReadInactive=Off, Active=On
BV29g_hdw1_stStatus of the "G" input to the ABC for unit 1ReadInactive=Off, Active=On
BV30dehum_hdw1_stStatus of the "DH" input to the ABC for unit 1ReadInactive=Off, Active=On
BV31es_hdw1_stStatus of the emergency shutdown hardware input for unit 1ReadInactive=Normal, Active=Shutdown
BV32low_press_hdw1_stStatus of the low pressure switch hardware input for unit 1ReadInactive=Open, Active=Closed
BV33high_press_hdw1_stStatus of the high pressure hardware input for unit 1ReadInactive=Off, Active=On
BV34load_shed_hdw1_stStatus of the load shed hardware input for unit 1ReadInactive=Normal, Active=Load Shed
BV35rev_vlv1_stStatus of the reversing valve output for unit 1ReadInactive=Heat, Active=Cool
BV36fan1_stCurrent status of the fan output for unit 1ReadInactive=Off, Active=On
BV38wse_relay_1_stCurrent status of the WSE output for unit 1ReadInactive=Inactive, Active=Active
BV39acc1_1_stStatus of the ACC-1 output for unit 1ReadInactive=Off, Active=On
AV1006abc_fault2_stCurrent ABC fault code value for unit 2Read
AV1007system_fault2_stSystem fault or lockout code, unit 2Read
AV1010mod_valve_pwm2_stCurrent modulating water valve position for unit 2%Read
AV1011eev2_stCurrent EEV position for unit 2%Read
AV1012coax_temp2_stCoax temperature read by the FP1 sensor for unit 2°FRead
AV1013air_coil_temp2_stAir coil temperature (FP2) for unit 2°FRead
AV1014lat2_stLeaving air temperature for unit 2°FRead
AV1015suct_press2_stSuction pressure for unit 2psiRead
AV1016sat_evap_temp2_stCalculated saturated (suction) evaporator temperature for unit 2°FRead
AV1017super_heat2_stCalculated super-heat value for unit 2°FRead
AV1018dischg_press2_stDischarge pressure of the compressor for unit 2psiRead
AV1019dischg_temp2_stCompressor discharge temperature for unit 2°FRead
AV1020suct_temp2_stSuction temperature for unit 2°FRead
AV1021hgt_subcooling2_stCalculated subcooling while operating in heating for unit 2°FRead
AV1022clg_subcooling2_stCalculated subcooling while operating in cooling for unit 2°FRead
AV1023liq_line_temp2_stLiquid line temperature for unit 2°FRead
AV1024lwt2_stLeaving water temperature for unit 2°FRead
AV1025ewt2_stEntering water temperature for unit 2°FRead
AV1026water_flow2_stCalculated GPM thru the heat exchanger for unit 2gpmRead
AV1027cond_temp2_stCalculated saturated (discharge) condenser temperature for unit 2°FRead
AV1028entering_air2_stEntering air temperature (HWT) for unit 2°FRead
AV1030control_voltage2_stABC's low voltage control value for unit 2VRead
AV1031est_line_voltage2_stEstimated line voltage to the unit for unit 2VRead
AV1032line_volts2_stLine voltage measured by the compressor drive for unit 2VRead
AV1033vdc_volts2_stInverter DC voltage measured by the compressor drive for unit 2VRead
AV1034invert_temp2_stMeasured inverter temperature for unit 2°FRead
AV1035drive_temp2_stMeasured compressor drive temperature for unit 2°FRead
AV1036fan_current2_stMeasured fan current for unit 2ARead
AV1037aux_current2_stMeasured auxiliary heat current for unit 2ARead
AV1038comp_current2_stMeasured compressor current for unit 2ARead
AV1040total_current2_stMeasured total current value for unit 2ARead
AV1041comp_power2_stCompressor power consumption for unit 2WRead
AV1042fan_power2_stCalculated fan power consumption for unit 2WRead
AV1043aux_power2_stCalculated auxiliary heat power consumption for unit 2WRead
AV1044total_power2_stTotal power consumption for unit 2WRead
AV1046total_capacity2_stTotal BTU operating capacity for unit 2Btu/hrRead
AV1047he_hr2_stCalculated heat of extraction/rejection for unit 2Btu/hrRead
AV1048co_of_perf2_stCalculated COP value for unit 2Read
AV1049eer2_stCalculated EER value for unit 2Read
AV1050reheat_valve_pos2_stCurrent position of MHGR valve for unit 2%Read
AV1209eev_start2_cSets the initial EEV position for unit 2 (default 50)Write
BV1012modbus_comm_alarm2_stABC-to-UPC Modbus communication status, unit 2ReadInactive=Communication Normal, Active=Communication Lost
BV1013lockout2_stStatus of the lockout alarm output for unit 2ReadInactive=Normal, Active=Lockout
BV1014lockout_hdw2_stStatus of the relay for the ABC's Lockout output for unit 2ReadInactive=Normal, Active=Lockout
BV1015alm_rht_hdw2_stStatus of the ABC's alarm output for unit 2ReadInactive=Off, Active=On
BV1017fp1_lim2_stCurrent FP1 freeze detection set point for unit 2ReadInactive=15°, Active=30°
BV1018fp2_lim2_stCurrent FP2 freeze detection set point for unit 2ReadInactive=Not Used, Active=30°
BV1019rhstat2_stStatus of the SW2-3 dipswitch for unit 2ReadInactive=Off, Active=On
BV1020sw_2_4_2_stStatus of the SW2-4 dipswitchReadInactive=Off, Active=On
BV1021sw_2_5_2_stStatus of the SW2-5 dipswitchReadInactive=Off, Active=On
BV1025y1_hdw2_stStatus of the "Y1" input to the ABC for unit 2ReadInactive=Off, Active=On
BV1026y2_hdw2_stStatus of the "Y2" input to the ABC for unit 2ReadInactive=Off, Active=On
BV1027w_hdw2_stStatus of the "W" input to the ABC for unit 2ReadInactive=Off, Active=On
BV1028o_hdw2_stStatus of the "O" input to the ABC for unit 2ReadInactive=Off, Active=On
BV1029g_hdw2_stStatus of the "G" input to the ABC for unit 2ReadInactive=Off, Active=On
BV1030dehum_hdw2_stStatus of the "DH" input to the ABC for unit 2ReadInactive=Off, Active=On
BV1031es_hdw2_stStatus of the emergency shutdown hardware input for unit 2ReadInactive=Normal, Active=Shutdown
BV1032low_press_hdw2_stStatus of the low pressure switch hardware input for unit 2ReadInactive=Open, Active=Closed
BV1033high_press_hdw2_stStatus of the high pressure hardware input for unit 2ReadInactive=Off, Active=On
BV1034load_shed_hdw2_stStatus of the load shed hardware input for unit 2ReadInactive=Normal, Active=Load Shed
BV1035rev_vlv2_stStatus of the reversing valve output for unit 2ReadInactive=Heat, Active=Cool
BV1036fan2_stCurrent status of the fan output for unit 2ReadInactive=Off, Active=On
BV1038wse_relay_2_stCurrent status of the WSE output for unit 2ReadInactive=Inactive, Active=Active
BV1039acc1_2_stStatus of the ACC-1 output for unit 2ReadInactive=Off, Active=On
AV2006abc_fault3_stCurrent ABC fault code value for unit 3Read
AV2007system_fault3_stSystem fault or lockout code, unit 3Read
AV2010mod_valve_pwm3_stCurrent modulating water valve position for unit 3%Read
AV2011eev3_stCurrent EEV position for unit 3%Read
AV2012coax_temp3_stCoax temperature read by the FP1 sensor for unit 3°FRead
AV2013air_coil_temp3_stAir coil temperature (FP2) for unit 3°FRead
AV2014lat3_stLeaving air temperature for unit 3°FRead
AV2015suct_press3_stSuction pressure for unit 3psiRead
AV2016sat_evap_temp3_stCalculated saturated (suction) evaporator temperature for unit 3°FRead
AV2017super_heat3_stCalculated super-heat value for unit 3°FRead
AV2018dischg_press3_stDischarge pressure of the compressor for unit 3psiRead
AV2019dischg_temp3_stCompressor discharge temperature for unit 3°FRead
AV2020suct_temp3_stSuction temperature for unit 3°FRead
AV2021hgt_subcooling3_stCalculated subcooling while operating in heating for unit 3°FRead
AV2022clg_subcooling3_stCalculated subcooling while operating in cooling for unit 3°FRead
AV2023liq_line_temp3_stLiquid line temperature for unit 3°FRead
AV2024lwt3_stLeaving water temperature for unit 3°FRead
AV2025ewt3_stEntering water temperature for unit 3°FRead
AV2026water_flow3_stCalculated GPM thru the heat exchanger for unit 3gpmRead
AV2027cond_temp3_stCalculated saturated (discharge) condenser temperature for unit 3°FRead
AV2028entering_air3_stEntering air temperature (HWT) for unit 3°FRead
AV2030control_voltage3_stABC's low voltage control value for unit 3VRead
AV2031est_line_voltage3_stEstimated line voltage to the unit for unit 3VRead
AV2032line_volts3_stLine voltage measured by the compressor drive for unit 3VRead
AV2033vdc_volts3_stInverter DC voltage measured by the compressor drive for unit 3VRead
AV2034invert_temp3_stMeasured inverter temperature for unit 3°FRead
AV2035drive_temp3_stMeasured compressor drive temperature for unit 3°FRead
AV2036fan_current3_stMeasured fan current for unit 3ARead
AV2037aux_current3_stMeasured auxiliary heat current for unit 3ARead
AV2038comp_current3_stMeasured compressor current for unit 3ARead
AV2040total_current3_stMeasured total current value for unit 3ARead
AV2041comp_power3_stCompressor power consumption for unit 3WRead
AV2042fan_power3_stCalculated fan power consumption for unit 3WRead
AV2043aux_power3_stCalculated auxiliary heat power consumption for unit 3WRead
AV2044total_power3_stTotal power consumption for unit 3WRead
AV2046total_capacity3_stTotal BTU operating capacity for unit 3Btu/hrRead
AV2047he_hr3_stCalculated heat of extraction/rejection for unit 3Btu/hrRead
AV2048co_of_perf3_stCalculated COP value for unit 3Read
AV2049eer3_stCalculated EER value for unit 3Read
AV2050reheat_valve_pos3_stCurrent position of MHGR valve for unit 3%Read
AV2209eev_start3_cSets the initial EEV position for unit 3 (default 50)Write
BV2012modbus_comm_alarm3_stABC-to-UPC Modbus communication status, unit 3ReadInactive=Communication Normal, Active=Communication Lost
BV2013lockout3_stStatus of the lockout alarm output for unit 3ReadInactive=Normal, Active=Lockout
BV2014lockout_hdw3_stStatus of the relay for the ABC's Lockout output for unit 3ReadInactive=Normal, Active=Lockout
BV2015alm_rht_hdw3_stStatus of the ABC's alarm output for unit 3ReadInactive=Off, Active=On
BV2017fp1_lim3_stCurrent FP1 freeze detection set point for unit 3ReadInactive=15°, Active=30°
BV2018fp2_lim3_stCurrent FP2 freeze detection set point for unit 3ReadInactive=Not Used, Active=30°
BV2019rhstat3_stStatus of the SW2-3 dipswitch for unit 3ReadInactive=Off, Active=On
BV2020sw_2_4_3_stStatus of the SW2-4 dipswitchReadInactive=Off, Active=On
BV2021sw_2_5_3_stStatus of the SW2-5 dipswitchReadInactive=Off, Active=On
BV2025y1_hdw3_stStatus of the "Y1" input to the ABC for unit 3ReadInactive=Off, Active=On
BV2026y2_hdw3_stStatus of the "Y2" input to the ABC for unit 3ReadInactive=Off, Active=On
BV2027w_hdw3_stStatus of the "W" input to the ABC for unit 3ReadInactive=Off, Active=On
BV2028o_hdw3_stStatus of the "O" input to the ABC for unit 3ReadInactive=Off, Active=On
BV2029g_hdw3_stStatus of the "G" input to the ABC for unit 3ReadInactive=Off, Active=On
BV2030dehum_hdw3_stStatus of the "DH" input to the ABC for unit 3ReadInactive=Off, Active=On
BV2031es_hdw3_stStatus of the emergency shutdown hardware input for unit 3ReadInactive=Normal, Active=Shutdown
BV2032low_press_hdw3_stStatus of the low pressure switch hardware input for unit 3ReadInactive=Open, Active=Closed
BV2033high_press_hdw3_stStatus of the high pressure hardware input for unit 3ReadInactive=Off, Active=On
BV2034load_shed_hdw3_stStatus of the load shed hardware input for unit 3ReadInactive=Normal, Active=Load Shed
BV2035rev_vlv3_stStatus of the reversing valve output for unit 3ReadInactive=Heat, Active=Cool
BV2036fan3_stCurrent status of the fan output for unit 3ReadInactive=Off, Active=On
BV2038wse_relay_3_stCurrent status of the WSE output for unit 3ReadInactive=Inactive, Active=Active
BV2039acc1_3_stStatus of the ACC-1 output for unit 3ReadInactive=Off, Active=On
AV3006abc_fault4_stCurrent ABC fault code value for unit 4Read
AV3007system_fault4_stSystem fault or lockout code, unit 4Read
AV3010mod_valve_pwm4_stCurrent modulating water valve position for unit 4%Read
AV3011eev4_stCurrent EEV position for unit 4%Read
AV3012coax_temp4_stCoax temperature read by the FP1 sensor for unit 4°FRead
AV3013air_coil_temp4_stAir coil temperature (FP2) for unit 4°FRead
AV3014lat4_stLeaving air temperature for unit 4°FRead
AV3015suct_press4_stSuction pressure for unit 4psiRead
AV3016sat_evap_temp4_stCalculated saturated (suction) evaporator temperature for unit 4°FRead
AV3017super_heat4_stCalculated super-heat value for unit 4°FRead
AV3018dischg_press4_stDischarge pressure of the compressor for unit 4psiRead
AV3019dischg_temp4_stCompressor discharge temperature for unit 4°FRead
AV3020suct_temp4_stSuction temperature for unit 4°FRead
AV3021hgt_subcooling4_stCalculated subcooling while operating in heating for unit 4°FRead
AV3022clg_subcooling4_stCalculated subcooling while operating in cooling for unit 4°FRead
AV3023liq_line_temp4_stLiquid line temperature for unit 4°FRead
AV3024lwt4_stLeaving water temperature for unit 4°FRead
AV3025ewt4_stEntering water temperature for unit 4°FRead
AV3026water_flow4_stCalculated GPM thru the heat exchanger for unit 4gpmRead
AV3027cond_temp4_stCalculated saturated (discharge) condenser temperature for unit 4°FRead
AV3028entering_air4_stEntering air temperature (HWT) for unit 4°FRead
AV3030control_voltage4_stABC's low voltage control value for unit 4VRead
AV3031est_line_voltage4_stEstimated line voltage to the unit for unit 4VRead
AV3032line_volts4_stLine voltage measured by the compressor drive for unit 4VRead
AV3033vdc_volts4_stInverter DC voltage measured by the compressor drive for unit 4VRead
AV3034invert_temp4_stMeasured inverter temperature for unit 4°FRead
AV3035drive_temp4_stMeasured compressor drive temperature for unit 4°FRead
AV3036fan_current4_stMeasured fan current for unit 4ARead
AV3037aux_current4_stMeasured auxiliary heat current for unit 4ARead
AV3038comp_current4_stMeasured compressor current for unit 4ARead
AV3040total_current4_stMeasured total current value for unit 4ARead
AV3041comp_power4_stCompressor power consumption for unit 4WRead
AV3042fan_power4_stCalculated fan power consumption for unit 4WRead
AV3043aux_power4_stCalculated auxiliary heat power consumption for unit 4WRead
AV3044total_power4_stTotal power consumption for unit 4WRead
AV3046total_capacity4_stTotal BTU operating capacity for unit 4Btu/hrRead
AV3047he_hr4_stCalculated heat of extraction/rejection for unit 4Btu/hrRead
AV3048co_of_perf4_stCalculated COP value for unit 4Read
AV3049eer4_stCalculated EER value for unit 4Read
AV3050reheat_valve_pos4_stCurrent position of MHGR valve for unit 4%Read
AV3209eev_start4_cSets the initial EEV position for unit 4 (default 50)Write
BV3012modbus_comm_alarm4_stABC-to-UPC Modbus communication status, unit 4ReadInactive=Communication Normal, Active=Communication Lost
BV3013lockout4_stStatus of the lockout alarm output for unit 4ReadInactive=Normal, Active=Lockout
BV3014lockout_hdw4_stStatus of the relay for the ABC's Lockout output for unit 4ReadInactive=Normal, Active=Lockout
BV3015alm_rht_hdw4_stStatus of the ABC's alarm output for unit 4ReadInactive=Off, Active=On
BV3017fp1_lim4_stCurrent FP1 freeze detection set point for unit 4ReadInactive=15°, Active=30°
BV3018fp2_lim4_stCurrent FP2 freeze detection set point for unit 4ReadInactive=Not Used, Active=30°
BV3019rhstat4_stStatus of the SW2-3 dipswitch for unit 4ReadInactive=Off, Active=On
BV3020sw_2_4_4_stStatus of the SW2-4 dipswitchReadInactive=Off, Active=On
BV3021sw_2_5_4_stStatus of the SW2-5 dipswitchReadInactive=Off, Active=On
BV3025y1_hdw4_stStatus of the "Y1" input to the ABC for unit 4ReadInactive=Off, Active=On
BV3026y2_hdw4_stStatus of the "Y2" input to the ABC for unit 4ReadInactive=Off, Active=On
BV3027w_hdw4_stStatus of the "W" input to the ABC for unit 4ReadInactive=Off, Active=On
BV3028o_hdw4_stStatus of the "O" input to the ABC for unit 4ReadInactive=Off, Active=On
BV3029g_hdw4_stStatus of the "G" input to the ABC for unit 4ReadInactive=Off, Active=On
BV3030dehum_hdw4_stStatus of the "DH" input to the ABC for unit 4ReadInactive=Off, Active=On
BV3031es_hdw4_stStatus of the emergency shutdown hardware input for unit 4ReadInactive=Normal, Active=Shutdown
BV3032low_press_hdw4_stStatus of the low pressure switch hardware input for unit 4ReadInactive=Open, Active=Closed
BV3033high_press_hdw4_stStatus of the high pressure hardware input for unit 4ReadInactive=Off, Active=On
BV3034load_shed_hdw4_stStatus of the load shed hardware input for unit 4ReadInactive=Normal, Active=Load Shed
BV3035rev_vlv4_stStatus of the reversing valve output for unit 4ReadInactive=Heat, Active=Cool
BV3036fan4_stCurrent status of the fan output for unit 4ReadInactive=Off, Active=On
BV3038wse_relay_4_stCurrent status of the WSE output for unit 4ReadInactive=Inactive, Active=Active
BV3039acc1_4_stStatus of the ACC-1 output for unit 4ReadInactive=Off, Active=On
AV311min_comp_cSets the minimum compressor operating percentage for VAV operation (default 25)%Write
AV312max_comp_cSets the maximum compressor operating percentage for VAV operation (default 100)%Write
AV313comp_up_stage_cCompressor upstaging value (default 80)%Write
AV314comp_dn_stage_cCompressor downstaging value (default 30)%Write
AV315comp_order_1Compressor staging selection for unit 1 (default 1)Write
AV316comp_order_2Compressor staging selection for unit 2 (default 2)Write
AV317comp_order_3Compressor staging selection for unit 3 (default 3)Write
AV318comp_order_4Compressor staging selection for unit 4 (default 4)Write
AV321last_comp_cLast compressor with runtime equalization (3+ units) (default 0)Write
AV322spare_comp_cSpare compressor, runs only when a unit is locked out (default 0)Write
AV323repair_comp_cSelects repair compressor to not be operated (default 0)Write
AV400comp_targ_rpm1_stCurrent target compressor RPM for unit 1rpmRead
AV401comp_targ_pct1_stCurrent target compressor percentage for unit 1%Read
AV402comp_act_rpm1_stCurrent actual compressor operating RPM for unit 1rpmRead
AV403comp_act_pct1_stCurrent actual compressor operating percentage for unit 1%Read
AV404comp_targ_rpm2_stCurrent target compressor RPM for unit 2rpmRead
AV405comp_targ_pct2_stCurrent target compressor percentage for unit 2%Read
AV406comp_act_rpm2_stCurrent actual compressor operating RPM for unit 2rpmRead
AV407comp_act_pct2_stCurrent actual compressor operating percentage for unit 2%Read
AV408comp_targ_rpm3_stCurrent target compressor RPM for unit 3rpmRead
AV409comp_targ_pct3_stCurrent target compressor percentage for unit 3%Read
AV410comp_act_rpm3_stCurrent actual compressor operating RPM for unit 3rpmRead
AV411comp_act_pct3_stCurrent actual compressor operating percentage for unit 3%Read
AV412comp_targ_rpm4_stCurrent target compressor RPM for unit 4rpmRead
AV413comp_targ_pct4_stCurrent target compressor percentage for unit 4%Read
AV414comp_act_rpm4_stCurrent actual compressor operating RPM for unit 4rpmRead
AV415comp_act_pct4_stCurrent actual compressor operating percentage for unit 4%Read
AV440unit_hours1_stCurrent compressor opertaing hours for unit 1hrRead
AV441unit_hours2_stCurrent compressor opertaing hours for unit 2hrRead
AV442unit_hours3_stCurrent compressor opertaing hours for unit 3hrRead
AV443unit_hours4_stCurrent compressor opertaing hours for unit 4hrRead
BV310run_equal_cEnables compressor run equalizationWriteInactive=Disabled, Active=Enabled
AV340static_setpt_cSets the target duct static pressure for VAV operation (default 1.25)in H2OWrite
AV341static_db_cSets the target duct static pressure deadband for VAV operation (default 0.15)in H2OWrite
AV342static_pressure_stActive duct static pressure valuein H2ORead
AV343static_over_cNetwork (BAS) supplied duct static pressure value (default 1)in H2OWrite
AV344min_blow_pct_cSets the minimum blower operating percentage (default 30)%Write
AV345max_blow_pct_cSets the maximum blower operating percentage (default 100)%Write
AV346min_blow_cfm_cSets the minimum blower operating CFM (default 500)cfmWrite
AV347max_blow_cfm_cSets the maximum blower operating CFM (default 3000)cfmWrite
AV350blow_up_stage_cBlower upstaging value (default 85)%Write
AV351blow_dn_stage_cBlower downstaging value (default 40)%Write
AV352blow_off_cSupply blower off delay following compressor operation (default 30)secondsWrite
AV360blow_targ_pct1_stCurrent target blower operating percentage for unit 1%Read
AV361blow_act_pct1_stCurrent actual blower operating percentage for unit 1%Read
AV362blow1rpm_stCurrent actual blower operating RPM for unit 1rpmRead
AV363blow_act_cfm1_stCurrent actual blower operating CFM for unit 1cfmRead
AV364blow_targ_pct2_stCurrent target blower operating percentage for unit 2%Read
AV365blow_act_pct2_stCurrent actual blower operating percentage for unit 2%Read
AV366blow2rpm_stCurrent actual blower operating RPM for unit 2rpmRead
AV367blow_act_cfm2_stCurrent actual blower operating CFM for unit 2cfmRead
AV368blow_targ_pct3_stCurrent target blower operating percentage for unit 3%Read
AV369blow_act_pct3_stCurrent actual blower operating percentage for unit 3%Read
AV370blow3rpm_stCurrent actual blower operating RPM for unit 3rpmRead
AV371blow_act_cfm3_stCurrent actual blower operating CFM for unit 3cfmRead
AV372blow_targ_pct4_stCurrent target blower operating percentage for unit 4%Read
AV373blow_act_pct4_stCurrent actual blower operating percentage for unit 4%Read
AV374blow4rpm_stCurrent actual blower operating RPM for unit 4rpmRead
AV375blow_act_cfm4_stCurrent actual blower operating CFM for unit 4cfmRead
AV384act_system_cfm_stCurrent total calculated system CFMcfmRead
BV321occ_blow_ctrl_cSelects blower operation during the occupied modeWriteInactive=Cycled, Active=Continuous
BV322unocc_blow_ctrl_cSelects blower operation during the unoccupied modeWriteInactive=Cycled, Active=Continuous
MV308statp_select_cSelects the system duct static pressure source (default 2)Write1=BAS, 2=Unit 1 Sensor, 2=Unit 2 Sensor, 4=Unit 3 Sensor, 5=Unit 4 Sensor
AVmin305targ_clg_sat_cSets the target SAT value for cooling operation (default 55)°FWrite
AVmin306targ_htg_sat_cSets the target SAT value for heating operation (default 90)°FWrite
AV307neutral_sat_cSets the target SAT value for neutral air (dehumidification) operation (default 65)°FWrite
AV308eff_targ_clg_sat_stCurrent effective target cooling SAT value°FRead
AV309eff_targ_htg_sat_stCurrent effective target heating SAT value°FRead
AV310eff_targ_sat_stCurrent effective target SAT value°FRead
AV325max_clg_sat_cSets the maximum target cooling SAT value for SAT reset operation (default 65)°FWrite
AV326ctrl_max_clg_sat_cControl temperature for maximum cooling SAT target (reset) (default 65)°FWrite
AV327ctrl_min_clg_sat_cControl temperature for minimum cooling SAT target (reset) (default 75)°FWrite
AV328clg_sar_delay_cCooling delay before SAT reset starts (default 5)minWrite
AV329min_htg_sat_cSets the minimum target heating SAT value for SAT reset operation (default 85)°FWrite
AV330ctrl_max_htg_sat_cControl temperature for maximum heating SAT target (reset) (default 60)°FWrite
AV331ctrl_min_htg_sat_cControl temperature for minimum heating SAT target (reset) (default 70)°FWrite
AV332htg_sar_delay_cHeating delay before SAT reset starts (default 5)minWrite
AV334eff_reset_t_stCurrent effective value of the SAT reset control tempertaure°FRead
AV335min_neu_sat_cSets the minimum target SAT value for single target SAT reset operation (default 60)°FWrite
AV336ctrl_max_neu_sat_cControl temperature for maximum SAT, single target reset (default 70)°FWrite
AV337ctrl_min_neu_sat_cControl temperature for minimum SAT, single target reset (default 75)°FWrite
AV338neu_sar_delay_cSets the time delay before SAT reset begins operating (default 5)minWrite
AV552sat_db_cSets the supply air temperature deadband used for DOAS heat pump control (default 1)°FWrite
MV320sat_reset_clgt_cSelects the operation and control temperature for cooling supply air reset (default 1)Write1=None, 2=Return Air Temperature, 3=Space Temperature, 4=Outdoor Air Temperature
MV321sat_reset_htgt_cSelects the operation and control temperature for heating supply air reset (default 1)Write1=None, 2=Return Air Temperature, 3=Space Temperature, 4=Outdoor Air Temperature
MV322sat_reset_neu_cSingle target or neutral SAT reset mode and control temperature (default 1)Write1=None, 2=Return Air Temperature, 3=Space Temperature, 4=Outdoor Air Temperature
AV9000aec_sat_target_stCurrent target supply air temperature value for the ERW system°FRead
AV9002ex_blow_targ_cfm_stCurrent target exhaust blower airflowcfmRead
AV9003ex_blow_targ_pct_stCurrent exhaust blower target percentage%Read
AV9004ex_blow_pct1_stCurrent operating percentage of exhaust blower #1%Read
AV9005ex_blow_pct2_stCurrent operating percentage of exhaust blower #2%Read
AV9006ex_blow_act_cfm_stCurrent calculated exhaust blower airflowcfmRead
AV9007ex_blow_power1_stCurrent power consumption of exhaust blower #1WRead
AV9008ex_blow_power2_stCurrent power consumption of exhaust blower #2WRead
AV9009aec_fault_code_stCurrent ERW system fault code, refer to appropriate fault table for valuesRead
AV9010aec_mode_stA value associated with the current operating mode of the ERW°FRead
AV9020aec_oat_sensor_stCurrent AEC outdoor sensor air temperature value°FRead
AV9021aec_oat_stCurrent effective outdoor air temperature value°FRead
AV9022aec_ewht_sensor_stCurrent AEC entering wheel sensor air temperature value°FRead
AV9023ewht_stCurrent effective entering wheel air temperature value°FRead
AV9024ewht_override_cBAS-written entering wheel air temperature (default 55)°FWrite
AV9025enat_sensor_stCurrent AEC system entering air sensor temperature value°FRead
AV9026enat_stCurrent effective system entering air temperature value°FRead
AV9027enat_override_cBAS-written system entering air temperature (default 75)°FWrite
AV9028enah_sensor_stCurrent AEC system entering air sensor humidity value%rhRead
AV9029enah_stCurrent effective system entering air humidity value%rhRead
AV9030enah_override_cBAS-written system entering air humidity (default 50)%rhWrite
AV9031enae_stCurrent system entering air enthalpy valueBtu/lbRead
AV9032aec_rat_sensor_stCurrent AEC return air sensor temperature value°FRead
AV9033aec_rat_stCurrent effective return air temperature value°FRead
AV9034aec_rah_sensor_stCurrent AEC return air sensor humidity value%rhRead
AV9035aec_rah_stCurrent effective return air humidity value%rhRead
AV9036aec_rae_stCurrent return air enthalpy valueBtu/lbRead
AV9038lwht_stCurrent effective leaving wheel air temperature value°FRead
AV9044exat_sensor_stCurrent AEC exhaust air sensor temperature value°FRead
AV9045exat_stCurrent effective exhaust air temperature value°FRead
AV9046exat_override_cBAS-written exhaust air temperature (default 55)°FWrite
AV9047exah_sensor_stCurrent AEC exhaust air sensor humidity value%rhRead
AV9048exah_stCurrent effective exhaust air humidity value%rhRead
AV9049exah_override_cBAS-written exhaust air humidity (default 50)%rhWrite
AV9050exae_stCurrent exhaust air enthalpy valueBtu/lbRead
AV9060ebdp_stCurrent value of the exhaust blower differential pressure sensorin H2ORead
AV9061whdp_stCurrent value of the energy wheel differential pressure sensorin H2ORead
AV9062sfdp_stCurrent value of the supply filter differential pressure sensorin H2ORead
AV9063efdp_stCurrent value of the exhaust filter differential pressure sensorin H2ORead
AV9064bdsp_stCurrent value of the building differential pressure sensorin H2ORead
AV9065bdp_over_cBAS-written building pressurization DP value (default 1)in H2OWrite
AV9070aec_erw_speed_stCurrent rotation speed of the energy wheel when equiped with rotation detectionrpmRead
AV9071aec_supply_damper_targ_stCurrent target Supply Bypass Damper position%Read
AV9072aec_exhaust_damper_targ_stCurrent target Exhaust Bypass Damper position%Read
AV9073aec_supply_damper1_pos_stCurrent actual position of Supply Bypass Damper%Read
AV9075aec_exhaust_damper1_pos_stCurrent actual position of Exhaust Bypass Damper%Read
AV9077aec_return_damper_targ_stCurrent target Return Air Bypass Damper position%Read
AV9078aec_return_damper_pos_stCurrent actual position of Return Air Bypass Damper%Read
AV9100exhaust_cfm_cSets the nominal exhaust blower target CFM (default 1000)cfmWrite
AV9101nom_ex_blow_pct_cSets the exhaust blower default or fallback operating percentage (default 50)%Write
AV9110min_oat_cSets the absolute minimum outdoor temperature for system operation (default 15)°FWrite
AV9111min_vent_cMinimum outdoor temperature to run without the energy wheel (default 45)°FWrite
AV9112max_vent_cMaximum outdoor temperature to run without the energy wheel (default 85)°FWrite
AV9113preheat_templimit_cSets the outdoor temperature for activation of preheat (default 20)°FWrite
AV9120enth_db_cSets the enthalpy deadband value (default 0.3)Btu/lbWrite
AV9121diff_press_db_cSets the standard differential pressure deadband value (default 0.01)in H2OWrite
AV9122bp_dp_cSets the target differential pressure for building pressurization operation (default 0.01)in H2OWrite
AV9123whbase_db_cSets the base or clean filter DP value for dirty wheel detection (default 0.25)in H2OWrite
AV9124sfbase_db_cClean supply filter DP baseline for dirty filter detection (default 0.1)in H2OWrite
AV9125efbase_db_cClean exhaust filter DP baseline for dirty filter detection (default 0.1)in H2OWrite
BV102stop_w_exhaust_cShutdown with exhaust fan operation command to the unitWriteInactive=Normal Operation, Active=Shutdown
BV103stop_w_exhaust_stStatus of shutdown with exhaust fan operationReadInactive=Normal, Active=Shutdown
BV9000oad_command_stCommanded state of the Outdoor Air DamperReadInactive=Inactive, Active=Active
BV9001oad_open_stCurrent status of the Outdoor Air DamperReadInactive=Not Open, Active=Open
BV9002exblow_enabled_stCurrent commanded state of the exhaust blowerReadInactive=Inactive, Active=Active
BV9003erw_enabled_stCurrent commanded state of the energy recovery wheelReadInactive=Inactive, Active=Active
BV9004preheat_stCurrent state of the preheat outputReadInactive=Inactive, Active=Active
BV9005aec_acc_stCurrent state of the AEC accessory relay outputReadInactive=Inactive, Active=Active
BV9007supply_dfs_stCurrent state of the supply filter dirty filter switchReadInactive=Inactive, Active=Active
BV9008exhaust_dfs_stCurrent state of the exhaust filter dirty filter switchReadInactive=Inactive, Active=Active
BV9009erw_rotation_stCurrent state of the energy wheel rotationReadInactive=Inactive, Active=Active
BV9010bpc_stCurrent operational status of the building pressurization logicReadInactive=Inactive, Active=Active
BV9011low_oat_stCurrent status of a potential low OAT conditionReadInactive=Inactive, Active=Active
BV9012aec_fault_stCurrent fault status of the AEC control in the ERWReadInactive=Normal, Active=Fault
BV9100bld_pres_cAllows building pressurization logic to be enabled or disabledWriteInactive=Disabled, Active=Enabled
BV9101sup_dfs_cfg_cConfiguration of a physical dirty supply filter switchWriteInactive=Norm Open, Active=Norm Closed
BV9102exh_dfs_cfg_cConfiguration of a physical dirty exhaust filter switchWriteInactive=Norm Open, Active=Norm Closed
MV309enas_select_cSelects the source for the ERW entering air values (default 2)Write1=BAS, 2=AEC
MV310exas_select_cSelects the source for the ERW exhaust air values (default 2)Write1=BAS, 2=AEC
MV312ewht_select_cSelects the source for the ERW entering wheel temperature value (default 2)Write1=BAS, 2=AEC
MV314blddp_select_cSelects the source for the ERW building pressure values (default 1)Write1=BAS, 2=AEC
MV331doas_cfg_cSets the DOAS system operation (default 1)Write1=Occupied Only, 2=Recirculating
MV9000aec_mode_actual_stActive operating mode for the ERWRead1=Off, 2=Standby, 3=Heating, 4=Cooling
MV9001aec_mode_status_stA value associated with the current operating mode of the ERWRead1=Off, 2=Energy Recovery Cooling, 3=Economizer, 4=Energy Recovery Heating, 5=Economizer with Energy Recovery, 12=Emergency Shutdown, 13=Shutdown with Exhaust, 14=Low OAT Shutdown, 15=System Fault
MV9002outdoor_damper_state_stCurrent operation status of the Outdoor DamperRead1=Startup, 2=Closing, 3=Closed, 4=Opening, 5=Open
MV9003erw_state_stCurrent operation status of the Energy Recovery WheelRead1=Startup, 2=Off, 3=Starting, 4=Running, 5=Stopping
MV9004supply_damper_modeCurrent operation status of the Supply Bypass DamperRead1=Closed, 2=Modulating, 3=Open
MV9005exhaust_damper_modeCurrent operation status of the Exhaust Bypass DamperRead1=Closed, 2=Modulating, 3=Open
MV9006return_damper_modeCurrent operation status of the Return Air Bypass DamperRead1=Closed, 2=Modulating, 3=Open
AVmin500sat_stCurrent usable supply air temperature value°FRead
AV501sat_adjust_cCalibration offset value for supply air temperature sensor (default 0)°FWrite
AV502sat_override_cBAS-written supply air temperature (default 0)°FWrite
AV503sah_stCurrent usable supply air humidity value%rhRead
AV504sah_adjust_cCalibration offset value for supply air humidity sensor (default 0)%rhWrite
AV505sah_override_cBAS-written supply air humidity (default 0)%rhWrite
AV506sae_stCalculated supply air enthalpy valueBtu/lbRead
AV507sad_stCalculated supply air dew point value°FRead
AV510rat_stCurrent usable return air temperature value°FRead
AV511rat_adjust_cCalibration offset value for return air temperature sensor (default 0)°FWrite
AV512rat_override_cBAS-written return air temperature (default 0)°FWrite
AV513rah_stCurrent usable return air humidity value%rhRead
AV514rah_adjust_cCalibration offset value for return air humidity sensor (default 0)%rhWrite
AV515rah_override_cBAS-written return air humidity (default 0)%rhWrite
AV516rae_stCalculated return air enthalpy valueBtu/lbRead
AV517rad_stCalculated return air dew point value°FRead
AV520spt_stCurrent usable space air temperature value°FRead
AV521spt_adjust_cCalibration offset value for space air temperature sensor (default 0)°FWrite
AV522spt_override_cBAS-written space air temperature (default 0)°FWrite
AV523sph_stCurrent usable space air humidity value%rhRead
AV524sph_adjust_cCalibration offset value for space air humidity sensor (default 0)%rhWrite
AV525sph_override_cBAS-written space air humidity (default 0)°FWrite
AV526spe_stCalculated space air enthalpy valueBtu/lbRead
AV527spd_stCalculated space air dew point value°FRead
AV530oat_stCurrent usable outdoor air temperature value°FRead
AV531oat_adjust_cCalibration offset value for outdoor air temperature sensor (default 0)°FWrite
AV532oat_override_cBAS-written outdoor air temperature (default 55)°FWrite
AV533oah_stCurrent usable outdoor air humidity value%rhRead
AV534oah_adjust_cCalibration offset value for outdoor air humidity sensor (default 0)%rhWrite
AV535oah_override_cBAS-written outdoor air humidity (default 50)%rhWrite
AV536oae_stCalculated outdoor air enthalpy valueBtu/lbRead
AV540ent_hp_temp_stCurrent effective heat pump entering air temperature°FRead
BV375sah_select_cSelects the supply air humidity sourceWriteInactive=Sensor, Active=BAS
BV376valid_sat_stIndicates if a valid supply air temperature value is selected and presentReadInactive=Fault, Active=Valid
BV377valid_sah_stIndicates if a valid supply air humidity value is selected and presentReadInactive=Fault, Active=Valid
BV378valid_rat_stIndicates if a valid return air temperature value is selected and presentReadInactive=Fault, Active=Valid
BV379valid_rah_stIndicates if a valid return air humidity value is selected and presentReadInactive=Fault, Active=Valid
BV380valid_spt_stIndicates if a valid space air temperature value is selected and presentReadInactive=Fault, Active=Valid
BV381valid_sph_stIndicates if a valid supply air humidity value is selected and presentReadInactive=Fault, Active=Valid
BV385valid_oat_stIndicates if a valid outdoor air temperature value is selected and presentReadInactive=Fault, Active=Valid
BV386valid_oah_stIndicates if a valid outdoor air humidity value is selected and presentReadInactive=Fault, Active=Valid
MV303sat_select_cSelects the system supply air temperature source (default 1)Write1=Rnet Sensor, 2=BAS, 3=Unit Sensor
MV304rat_select_cSelects the system return air temperature source (default 3)Write1=Rnet Sensor, 2=BAS, 3=ERW
MV305rah_select_cSelects the system return air humidity source (default 1)Write1=Rnet Sensor, 2=BAS, 3=ERW
MV306spt_select_cSelects the system space temperature source (default 1)Write1=Rnet Sensor, 2=BAS
MV307sph_select_cSelects the system space humidity source (default 1)Write1=Rnet Sensor, 2=BAS
MV311oas_select_cSelects the system outdoor air values source (default 1)Write1=Rnet Sensor, 2=BAS, 3=ERW
AV460mrh_max_valve_pos_cSets the maximum modulating reheat valve position (default 100)%Write
AV461targ_sst_cSets the target saturated suction temperature for MHGR operation (default 35)°FWrite
AV462low_sst_cSets the minimum saturated suction temperature for cooling operation (default 30)°FWrite
AV463mrh_net_temp_cNetwork supplied LAT used for MHGR operation (default 60)°FWrite
AV464hpc_setpoint_cSets the head pressure control target saturated discharge temperature for MHGR opertaion (default 100)°FWrite
AV630occ_dehum_cAdjustment of the occupied dehumidification set point (default 53)%rhWrite
AV631unocc_dehum_cAdjustment of the unoccupied dehumidification set point (default 75)%rhWrite
AV632stand_dehum_cAdjustment of the standby dehumidification set point (default 55)%rhWrite
AV633hum_db_cAllows adjustment of the humidity control deadband for dehumidification (default 1)%rhWrite
AV640occ_dew_cAdjustment of the occupied dew point set point (default 53)°FWrite
AV641unocc_dew_cAdjustment of the unoccupied dew point set point (default 55)°FWrite
AV642stand_dew_cAdjustment of the standby dew point set point (default 54)°FWrite
AV643dew_db_cAllows adjustment of the dew point control deadband (default 0.2)°FWrite
AV652ctrl_hum_stCurrent control humidity value for setpoint control%rhRead
AV653ctrlh_override_cSets the control humidity value for setpoint operation (default 0)%rhWrite
AV654ctrl_dew_stCurrent control dew point value for setpoint control°FRead
AV655ctrld_override_cSets the control dew point value for setpoint operation (default 0)°FWrite
BV390unocc_dh_cSelects dehumidifctaion operation during unoccupied modeWriteInactive=Disabled, Active=Enabled
BV465mrh_enable_cEnables modulating hot gas reheat operationWriteInactive=Disabled, Active=Enabled
BV466mrh_app_cSelects application for modulating reheat operationWriteInactive=Dehumidifcation, Active=SAT Control
BV467mrht_select_cSelects the LAT source for MHGR operationWriteInactive=Local, Active=BAS
BV468hpc_enable_cSelects head pressure control for MHGR operationWriteInactive=Disabled, Active=Enabled
MV318ctrl_hum_cSelects the humidity control option for the system (default 1)Write1=None, 2=Discrete Input, 3=Humidity, 4=Dew Point
MV319ctrl_hum_val_cSelects the control humidity source for setpoint control (default 1)Write1=Space Humidity, 2=Return Air Humidity, 3=Supply Air Humidity, 4=BAS Supplied Humidity
AV600occ_clg_setptOccupied cooling set point°FWrite
AV601occ_htg_setptOccupied heating set point°FWrite
AV602unocc_clg_setptUnoccupied cooling set point°FWrite
AV603unocc_htg_setptUnoccupied heating set point°FWrite
AV604standby_cool_cStandby cooling set point (default 76)°FWrite
AV605standby_heat_cStandby heating set point (default 68)°FWrite
AV606eff_clg_setpt_stEffective cooling set point°FRead
AV607eff_htg_setpt_stEffective heating set point°FRead
AV608clg_adj_stCurrent sensor adjustment of the cooling setpoint°FWrite
AV609htg_adj_stCurrent sensor adjustment of the heating setpoint°FWrite
AV610min_sp_diff_cMinimum temperature between the heating and cooling setpoints (default 2)°FWrite
AV611setpt_span_cAdjusts the space temperature set point span (default 5)°FWrite
AV615temp_db_cSets the temperature control deadband value for setpoint operation (default 0.1)°FWrite
AV616temp_over_cSets the temperature control overshoot value for setpoint operation (default 0.5)°FWrite
AV620occ_sens_on_time_cSets the occupancy sensor active recognition time (default 5)secondsWrite
AV621occ_sens_off_time_cSets the occupancy sensor inactive recognition time (default 5)minWrite
AV622temp_occ_timeAmount of time left in temporary occupancy only while in Temp Occm/secRead
AV650ctrl_temp_stCurrent control temperature value for setpoint control°FRead
AV651ctrlt_override_cSets the control temperature value for setpoint operation (default 0)°FWrite
BVmin400occ_command_cExternal occupancy commandWriteInactive=Unoccupied, Active=Occupied
BVmin401sched_select_cSelect between the internal or external scheduleWriteInactive=Internal, Active=External
BV402occ_sensor_cOccupancy sensor input to be enabledWriteInactive=Disabled, Active=Enabled
BV403sensor_occ_stOccupancy sensor statusReadInactive=Inactive, Active=Active
BV404temp_occ_dis_cNetwork control to disable temporary occupancyWriteInactive=Disabled, Active=Enabled
BV405temp_occ_stStatus of the temporary occupancy inputReadInactive=Normal, Active=Temp Occ
MV315occ_selection_cSelects the occupancy mode for external scheduling (default 1)Write1=Occupied, 2=Unoccupied, 3=Temp Occ, 4=Standby
MV316effective_occ_stCurrent occupancy modeRead1=Occupied, 2=Unoccupied, 3=Temp Occ, 4=Standby, 5=Occupancy Sensor
AV470dcv_limit_cSets the target ppm for demand controlled ventilation operation (default 900)ppmWrite
AV473dcv_max_pos_cSets the maximum damper position for demand controlled ventilation (default 60)%Write
AV474co2_db_cSets the ppm deadband value for demand controlled ventilation operation (default 20)ppmWrite
AV475dcv_max_cfm_cSets the maximum CFM value (default 4000)cfmWrite
AV590co2_stCO2 value if the zone sensor is equipped with the sensorppmRead
AV591co2_override_cSets the system CO2 value from the BAS (default 0)ppmWrite
AV592voc_stVOC value if the zone sensor is equipped with the sensorppmRead
AV593voc_override_cSets the system VOC value from the BAS (default 0)ppmWrite
BV470dcv_enable_cAllows demand control ventilation to be enabled or disabledWriteInactive=Disabled, Active=Enabled
BV471dcv_var_cSets the control variable for DCV operationWriteInactive=CO2, Active=VOC
MV327dcv_select_cSets the source for DCV control variable (default 1)Write1=Space Sensor, 2=BAS, 3=ERW
AV450wse_setpt_cWaterside Economizer EWT setpoint value (default 45)°FWrite
AV451wse_ewt_stActive water temperature for waterside economizer operation°FRead
AV452wse_override_cNetwork supplied water temperature for waterside economizer operation (default 50)°FWrite
AV453wse_flush_cycle_cBAS can set the frequency of WSE flush cycles in days (default 2)dayWrite
AV454wse_staging_cSAT offset from target for staging with WSE (default 2)°FWrite
BV350wse_enable_cEnable waterside economizer operationWriteInactive=Disabled, Active=Enabled
BV451wse_available_stCurrent status of Water Side Economizer availabilityReadInactive=Not Avail, Active=Available
BV452wse1_active_stCurrent operational status of the waterside economizer for unit 1ReadInactive=Inactive, Active=Active
BV453wse2_active_stCurrent operational status of the waterside economizer for unit 2ReadInactive=Inactive, Active=Active
BV454wse3_active_stCurrent operational status of the waterside economizer for unit 3ReadInactive=Inactive, Active=Active
BV455wse4_active_stCurrent operational status of the waterside economizer for unit 4ReadInactive=Inactive, Active=Active
BV458wse_flush_stCurrent waterside economizer flush cycle statusReadInactive=Inactive, Active=Active
MV325wse_select_cSelects the control temperature for waterside economizer operation (default 2)Write1=BAS, 2=Unit 1 EWT, 2=Unit 2 EWT, 4=Unit 3 EWT, 5=Unit 4 EWT
AV1abc_fw_rev1_stInternal use; do not map to BASRead
AV2axb_fw_rev1_stInternal use; do not map to BASRead
AV51axb2_fw_rev1_stInternal use; do not map to BASRead
AV159flow_meter_cInternal use; do not map to BASWrite
AV160blower_opt_cInternal use; do not map to BASWrite
AV162energy_mon_cInternal use; do not map to BASWrite
AV349kcfm_cInternal use; do not map to BASWrite
AV9001aec_fw_rev_stInternal use; do not map to BASRead
AV9102kecfm_cInternal use; do not map to BASWrite
AV9200aec_fault_code1_stInternal use; do not map to BASRead
AV9201aec_fault_code2_stInternal use; do not map to BASRead
AV9202aec_fault_code3_stInternal use; do not map to BASRead
AV9203aec_fault_code4_stInternal use; do not map to BASRead
AV9204aec_fault_code5_stInternal use; do not map to BASRead
AV9205aec_fault_code6_stInternal use; do not map to BASRead
AV9900fact_test_pwd_cInternal use; do not map to BASWrite
AV9902man_exhaust_blow_cInternal use; do not map to BAScfmWrite
AV9903man_supply_damp_cInternal use; do not map to BAS%Write
AV9904man_exhaust_damp_cInternal use; do not map to BAS%Write
AV9905man_rad_pos_cInternal use; do not map to BAS%Write
AV9910blow_man_pct_1Internal use; do not map to BAS%Write
AV9911man_flow_1Internal use; do not map to BAS%Write
AV9912comp_man_1Internal use; do not map to BAS%Write
AV9913man_mrh_1Internal use; do not map to BAS%Write
AV9980m409_cmdInternal use; do not map to BASWrite
AV9981m488_cmdInternal use; do not map to BASWrite
AV9982m417_cmdInternal use; do not map to BASWrite
AV9983m494_cmdInternal use; do not map to BASWrite
AV9984m421_cmdInternal use; do not map to BASWrite
AV9985m495_cmdInternal use; do not map to BASWrite
AV9986m425_cmdInternal use; do not map to BASWrite
AV9987m496_cmdInternal use; do not map to BASWrite
AV9988m429_cmdInternal use; do not map to BASWrite
AV9989m497_cmdInternal use; do not map to BASWrite
AV9990m433_cmdInternal use; do not map to BASWrite
AV9991m498_cmdInternal use; do not map to BASWrite
AV9992m441_cmdInternal use; do not map to BASWrite
AV9993m445_cmdInternal use; do not map to BASWrite
AV9994m500_cmdInternal use; do not map to BASWrite
AV9995m449_cmdInternal use; do not map to BASWrite
AV9996m501_cmdInternal use; do not map to BASWrite
AV9997m453_cmdInternal use; do not map to BASWrite
AV10000numunitInternal use; do not map to BASRead
AV10001physical_in_2Internal use; do not map to BASRead
AV10002physical_in_3Internal use; do not map to BASRead
AV10003physical_in_4Internal use; do not map to BASRead
AV10006hum_targInternal use; do not map to BAS%rhRead
AV10007elevationInternal use; do not map to BASftRead
AV10008dew_targInternal use; do not map to BAS°FRead
AV10009mhgr_offsetInternal use; do not map to BAS°FRead
AV20000tsensor8Internal use; do not map to BAS°FRead
AV20001tsensor9Internal use; do not map to BAS°FRead
AV20002hsensor8Internal use; do not map to BAS%rhRead
AV20003hsensor9Internal use; do not map to BAS%rhRead
AV30000axb2comm_st1Internal use; do not map to BASRead
AV30001minrpm1Internal use; do not map to BASrpmRead
AV30002minrpm2Internal use; do not map to BASrpmRead
AV30003minrpm3Internal use; do not map to BASrpmRead
AV30004minrpm4Internal use; do not map to BASrpmRead
AV30007maxrpm1Internal use; do not map to BASrpmRead
AV30008maxrpm2Internal use; do not map to BASrpmRead
AV30009maxrpm3Internal use; do not map to BASrpmRead
AV30010maxrpm4Internal use; do not map to BASrpmRead
AV30013abcfault1Internal use; do not map to BASRead
AV30014abcfault2Internal use; do not map to BASRead
AV30015abcfault3Internal use; do not map to BASRead
AV30016abcfault4Internal use; do not map to BASRead
AV40000dcv_valueInternal use; do not map to BASppmRead
AV50000aec_ratInternal use; do not map to BASRead
AV50001aec_rahInternal use; do not map to BASRead
AV50002aec_oatInternal use; do not map to BASRead
AV50003aec_co2Internal use; do not map to BASRead
AV50004aec_raeInternal use; do not map to BASBtu/lbRead
AI10004read_tempInternal use; do not map to BAS°FRead
AI10005read_humInternal use; do not map to BAS%rhRead
BV7test_mode_hdw_stInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV16condensate1_stInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV77abc_update_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV79za2_enable1_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV80dp_enable1_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV81brine_selection_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV82axb2_enable_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV330set_blwr_addr1_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV331clr_blwr_addr1_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV1016condensate2_stInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV2016condensate3_stInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV3016condensate4_stInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9103wh_rot_warn_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9900fact_test_ena_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9901man_wheel_ctrlInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9932eb_1_address_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9933eb_2_address_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9934clr_address_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9940man_wse1_ctrlInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9941man_acc_1Internal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9950reset_eeprom_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9951clear_faults_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9960wheel_dp_commInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9961ex_blow_dp_comm1Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9962sup_filter_dp_commInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9963ex_filter_dp_commInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9964ex_blow_comm1Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9965ex_blow_comm2Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9966sup_damp_comm1Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9967ex_damp_comm1Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9968ret_damp_commInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV9990wse_option_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV9991ase_option_cInternal use; do not map to BASWriteInactive=Do not map, Active=Do not map
BV10000inhibit_1Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10001inhibit_2Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10002inhibit_3Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10003inhibit_4Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10006compact_1Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10007compact_2Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10008compact_3Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10009compact_4Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10012noaecInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10013factoryInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10014es_cmdInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10015ex_shutInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10016exs_overInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10017preblowInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10018manervblowInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10019erw_dehumInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10020comp_activeInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV10021aecInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV20000oas_ervInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV30000abc_sowv_1Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV30001abc_sowv_2Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV30002abc_sowv_3Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV30003abc_sowv_4Internal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV30006abc_shutdnInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV40000fan_occInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV40001go_occInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV50000man_ervInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV50001ret_damp_okInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
BV50002wheel_rot_wInternal use; do not map to BASReadInactive=Do not map, Active=Do not map
MV2phase_selection_cInternal use; do not map to BASWrite
MV300num_units_cInternal use; do not map to BASWrite
MV330sys_app_cInternal use; do not map to BASWrite
AV471min_dmp_pos_cMinimum damper position for DCV or airside economizer (default 30)%Write
AV472max_dmp_pos_cSets the maximum damper position for airside economizer operation (default 100)%Write
AV480db_setpt_cDry bulb set point for Airside Economizer operation (default 63)°FWrite
AV481db_limit_cDry bulb limit for Airside Economizer operation (default 75)°FWrite
AV482db_diff_cDry bulb differential for Airside Economizer operation (default 2)°FWrite
AV483enth_setpt_cEnthalpy set point for Airside Economizer operation (default 24)Btu/lbWrite
AV484enth_limit_cEnthalpy limit for Airside Economizer operation (default 30)Btu/lbWrite
AV485enth_diff_cEnthalpy differential for Airside Economizer operation (default 2)Btu/lbWrite
AV486min_oat_vent_cMinimum outdoor temperature for ventilation operation (default 0)°FWrite
AV487max_oat_vent_cMaximum outdoor temperature for ventilation operation (default 85)°FWrite
AV488sam_time_cOutdoor air temperature sampling time for Airside Economizer operation (default 60)secondsWrite
BV480econ_on_cBAS flag: economizer available (slave mode)WriteInactive=Not Avail, Active=Available
MV326ase_mode_cSelects the opertaing mode for the airside economizer (Non-ERW applications only) (default 1)Write1=Econ Off, 2=Fixed Temp, 3=Diff Temp, 4=Fixed Enthalpy, 5=Diff Enthalpy, 6=Slave Mode
Object ID lookup: WaterFurnace Versatec 700 DOAS point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Versatec 700 Indoor DOAS (Aurora UPC) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC)

How many BACnet points does the WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC) have?

This list has 748 BACnet objects: 2 analog inputs, 485 analog values, 224 binary values, 37 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC) BACnet points are writable?

252 of the 748 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC) BACnet documentation?

The source is DOAS BACnet Point List, revision Version 1.00, published free by WaterFurnace at https://www.waterfurnace.com/literature/aurora/doas-bacnet-point-list-version-1.00.xlsx.

What are the minimum BACnet points to integrate the WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC)?

Start with BV 302 sys_enable_c (System enable for network and setpoint control); BV 2 e_stop_c (Emergency shutdown command); BV 400 occ_command_c (Occupancy command (external schedule)); BV 401 sched_select_c (Must be External for BV 400 to apply); AV 305 targ_clg_sat_c (Cooling supply air temperature target); AV 306 targ_htg_sat_c (Heating supply air temperature target); BV 8 alarm_reset_c (Alarm reset); MV 11 mode_st_msv (Unit operating mode); AV 500 sat_st (Supply air temperature in use); AV 7 system_fault1_st (Unit 1 fault or lockout code).

How do I enable BMS control of the WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC)?

BV 302 sys_enable_c enables the system for network and setpoint control. BV 2 e_stop_c is the emergency shutdown, BV 102 a shutdown that keeps the exhaust fan running, and BV 4 load shed. Occupancy follows the internal schedule unless BV 401 is set to External; then BV 400 or MV 315 set the occupancy mode.

Can the BMS supply sensor values to the WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC)?

Each sensed value has a source selector and a BAS override: MV 303-307 and MV 311 pick Rnet sensor, unit/ERW sensor or BAS for supply, return, space and outdoor values, written on AV 502/505/512/515/522/525/532/535. MV 309/310/312/314 pick BAS or AEC for the energy recovery inputs (AV 9024-9065). AV 551 takes a BAS DOAS control temperature, AV 343 a BAS duct static value, and AV 591/593 BAS CO2 and VOC.

How do I check these points on the real Versatec 700 Indoor DOAS (Aurora UPC)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WaterFurnace BACnet points lists

Source: DOAS BACnet Point List · rev. Version 1.00. Object names, instances and units are reproduced as published; descriptions are our own.