- Home
- BACnet points lists
- WaterFurnace
- Single Compressor Water-to-Air Console Unit (FX10)
Water-source heat pump controller (console) · BACnet points list
WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) BACnet points list
Updated 4 November 2026
BACnet objects for WaterFurnace's single-compressor console heat pump on the FX10 controller. It is a short list: space and discharge air temperatures, effective setpoints, an alarm code, flash-stored setpoints and limits, and read-only status of the fan, compressor, reversing valve and two digital inputs. The BAS can shift both setpoints with Space Setpoint (AO1) and override the space temperature (AO2).
This page lists 24 BACnet objects for the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.
- Manufacturer
- WaterFurnace
- Model
- Single Compressor Water-to-Air Console Unit (FX10)
- Equipment
- Water-source heat pump controller (console)
- Equipment type
- Heat pumps
- BACnet objects
- 24 (12 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- PROSSWAC-02, PROSSWAC, WaterFurnace console heat pump FX10, WaterFurnace FX10
Reference only, provided as-is: verify against WaterFurnace’s current documentation and the live device before use. Not official WaterFurnace information. Terms of use.
BMS integration notes: WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)
The console unit runs on its own setpoints; the BAS mainly adjusts them and monitors. Use Space Setpoint (AO1) to move both setpoints from one command, or AO2 to feed a network space temperature. Keep frequent writes on the volatile AO points, not the flash-backed AV setpoints.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AO 1 | Space Setpoint | Midpoint setpoint; shifts heat and cool together | Write |
| AV 1 | Occupied Cool | Occupied cooling setpoint (flash; write rarely) | Write |
| AV 3 | Occupied Heat | Occupied heating setpoint (flash; write rarely) | Write |
| MI 1 | Mode Status | Unit mode: auto or shutdown | Read |
| MI 6 | Compr Cmd Status | Compressor commanded on/off | Read |
| AI 1 | Space Temperature | Space sensor temperature (terminals RS/AIC) | Read |
| AI 2 | Discharge Air | Discharge (supply) air temperature | Read |
| AI 5 | Alarms | Active alarm code | Read |
Enable & remote start
The sheet has no enable, occupancy or shutdown command; the unit runs on its local control and the BAS adjusts setpoints.
Sensors & values from the BMS
AO2 Space Temp Override replaces the space sensor reading from the network. It is a volatile output, so it reverts to uncommanded after a power cycle.
Watch out for
- AV points are stored in flash (about 2,000,000 writes); write them only manually or by schedule, never from automatic reset logic.
- Output points (AO) are volatile and go back to uncommanded after a power cycle, so rewrite them after power returns.
- If the BAS shows 254 as uncommanded instead of 255, every multistate value is one lower.
WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Space Temperature | Space sensor reading (terminals RS/AIC) | Read | ||
| AImin | 2 | Discharge Air | Discharge air sensor (field mounted unless factory special) | Read | ||
| AI | 3 | Effective Clg Setpt | Effective cooling setpoint | Read | ||
| AI | 4 | Effective Hgt Setpt | Effective heating setpoint | Read | ||
| AImin | 5 | Alarms | Active alarm code (see alarm table) | Read | 0=No Alarm; 1=Condensate Detected; 2=Compressor High Discharge Pressure; 3=Compressor Low Suction Pressure; 4=Freeze Protection; 8=Faulty Freeze Sensor Alarm | |
| AOmin | 1 | Space Setpoint | Midpoint setpoint; moves heating and cooling setpoints together | Write | ||
| AO | 2 | Space Temp Override | Network override of the space temperature reading | Write | ||
| AVmin | 1 | Occupied Cool | Occupied cooling setpoint (flash) | Write | ||
| AV | 2 | Unoccupied Cool | Unoccupied cooling setpoint (flash) | Write | ||
| AVmin | 3 | Occupied Heat | Occupied heating setpoint (flash) | Write | ||
| AV | 4 | Unoccupied Heat | Unoccupied heating setpoint (flash) | Write | ||
| AV | 5 | Max Hgt Setpt | Upper limit for the heating setpoint | Write | ||
| AV | 6 | Min Clg Setpt | Lower limit for the cooling setpoint | Write | ||
| AV | 7 | Remote Setpt Max | Sensor setpoint shift, plus side | Write | ||
| AV | 8 | Remote Setpt Min | Sensor setpoint shift, minus side | Write | ||
| AV | 9 | Space Sensor Calibrate | Calibration offset for the zone sensor | Write | ||
| AV | 10 | Compr Differential | Compressor call deadband | Write | ||
| MImin | 1 | Mode Status | Current unit mode | Read | 1=Auto (Normal); 7=Off (Shutdown) | |
| MI | 2 | Effective Occupancy | Current occupancy status | Read | 1=Occupied; 2=Unoccupied; 3=Bypass (temporary occupancy) | |
| MI | 3 | Comp/Fan Prove | Digital input 6 (field-installed current relay) | Read | 1=Off; 2=On | |
| MI | 4 | Dirty Filter Input | Digital input 12 (field-installed current relay) | Read | 1=Off; 2=On | |
| MI | 5 | Fan Cmd Status | Commanded fan status | Read | 1=Off; 2=On | |
| MImin | 6 | Compr Cmd Status | Commanded compressor status | Read | 1=Off; 2=On | |
| MI | 7 | Rev Valve Status | Commanded reversing valve position | Read | 1=Heating; 2=Cooling |
No points match these filters.
Object ID lookup: WaterFurnace Water-to-Air Console (FX10) point IDs by name
AI1Space TemperatureAI2Discharge AirAI3Effective Clg SetptAI4Effective Hgt SetptAI5AlarmsAO1Space SetpointAO2Space Temp OverrideAV1Occupied CoolAV2Unoccupied CoolAV3Occupied HeatAV4Unoccupied HeatAV5Max Hgt SetptAV6Min Clg SetptAV7Remote Setpt MaxAV8Remote Setpt MinAV9Space Sensor CalibrateAV10Compr DifferentialMI1Mode StatusMI2Effective OccupancyMI3Comp/Fan ProveMI4Dirty Filter InputMI5Fan Cmd StatusMI6Compr Cmd StatusMI7Rev Valve Status
Integration notes
- Output-type points (AO/MO) are volatile and fall back to uncommanded after a power cycle; unlimited writes.
- Value-type points (AV/MV) are stored in flash (about 2,000,000 write life); never write them from automatic reset logic.
- Multistate numbers assume the BAS shows 255 as uncommanded; if yours shows 254, every state number is one lower (0=Off, 1=On).
- Units are not printed on the sheet. The sheet does not state the BACnet transport.
- This sheet has no occupancy command, fan/compressor command or alarm reset point.
- Alarm codes 5-7 are not listed in the alarm table.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Single Compressor Water-to-Air Console Unit (FX10) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)
How many BACnet points does the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) have?
This list has 24 BACnet objects: 5 analog inputs, 2 analog outputs, 10 analog values, 7 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) BACnet points are writable?
12 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) BACnet documentation?
The source is BACnet Points for Single Compressor Water-to-Air Console Units Utilizing the FX10 Controller (PROSSWAC-02), revision 2013-02, published free by WaterFurnace at https://www.waterfurnace.com/downloads/ddc/BACnet-Resources/BACnet-points-pdfs/PROSSWAC-02.pdf.
What are the minimum BACnet points to integrate the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)?
Start with AO 1 Space Setpoint (Midpoint setpoint; shifts heat and cool together); AV 1 Occupied Cool (Occupied cooling setpoint (flash; write rarely)); AV 3 Occupied Heat (Occupied heating setpoint (flash; write rarely)); MI 1 Mode Status (Unit mode: auto or shutdown); MI 6 Compr Cmd Status (Compressor commanded on/off); AI 1 Space Temperature (Space sensor temperature (terminals RS/AIC)); AI 2 Discharge Air (Discharge (supply) air temperature); AI 5 Alarms (Active alarm code).
How do I enable BMS control of the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)?
The sheet has no enable, occupancy or shutdown command; the unit runs on its local control and the BAS adjusts setpoints.
Can the BMS supply sensor values to the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)?
AO2 Space Temp Override replaces the space sensor reading from the network. It is a volatile output, so it reverts to uncommanded after a power cycle.
How do I check these points on the real Single Compressor Water-to-Air Console Unit (FX10)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More WaterFurnace BACnet points lists
- Water-to-water heat pump controller
WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps
WaterFurnace NXW and SKW dual-scroll water-to-water heat pumps (including header rack arrangements) with the Aurora HydroLink controller.
Also known as: PL2500EW, HydroLink, NXW, SKW, WCHDM, HYDWWB01 - Modular chiller / water-to-water heat pump controller
WaterFurnace Aurora HydroLink2 for TruClimate 100 / TruClimate 500 Modular Chillers
WaterFurnace TruClimate 100 dual scroll (NXW) and TruClimate 500 modular chillers with the Aurora HydroLink2 controller, including 4-pipe and 6-pipe header rack builds and variable speed modules.
Also known as: HydroLink2, HydroLink 2, TruClimate 100, TruClimate 500, NXW, HydroLink2 BACnet Objects 3.04 - Water-cooled screw chiller / heat pump controller
WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller
WaterFurnace TruClimate 700 single screw water-to-water chillers with the Aurora HydroLink2 controller.
Also known as: HydroLink2 Single Screw, TruClimate 700, HydroLink2 - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Dual Compressor Rooftop Unit with Economizer
WaterFurnace dual-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump
WaterFurnace dual-compressor water-to-air heat pumps with two Aurora Base Controllers (ABC A and B) and the Aurora UPC.
Also known as: PL1500EW, Aurora Universal Protocol Converter, Aurora UPC dual compressor - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer
WaterFurnace single-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump
WaterFurnace single-compressor water-to-air heat pumps with the Aurora controls and the Aurora UPC protocol converter.
Also known as: AG1569EW, Aurora Universal Protocol Converter, Aurora UPC, UPCSWASTD01-01 - Water-source heat pump controller
WaterFurnace Aurora UPC, Variable Speed Water-Source Heat Pump
WaterFurnace variable speed water-to-air heat pumps with Aurora controls and the Aurora UPC.
Also known as: PL1700EW, Aurora Universal Protocol Converter, Aurora UPC variable speed - Water-source heat pump controller
WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace commercial dual-compressor water-to-air heat pumps fitted with the FX10 DDC controller.
Also known as: PRODCWA-05, PRODCWA, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Dual Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace dual-compressor water-to-air heat pumps with hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PRODCWA-RH-03, PRODCWA-RH, WaterFurnace dual compressor reheat FX10, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Envision single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWWE-01, PROSSWWE, Envision Water-to-Water, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton
WaterFurnace Envision 1 to 6 ton water-to-air heat pumps with the DDC controller option.
Also known as: Envision BACnet Variables, Envision BACnet Variables with BI, Envision 1-6 Ton - Geothermal heat pump zoning controller
WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet
WaterFurnace geothermal heat pumps with Aurora controls and the IntelliZone2 zoning system (up to 6 zones), read through the Aurora BACnet controller.
Also known as: IZ2, IntelliZone2, IntelliZone 2, Aurora IZ2 - Water-to-water heat pump / reversible chiller controller
WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)
WaterFurnace dual-compressor reversible chiller (water-to-water) heat pumps with the FX10 controller.
Also known as: PRODCWWE-06B, PRODCWWE-07B, PRODCWWE-08B, PRODCWWE - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace single-compressor water-to-air heat pumps without hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PROFXENV-00, PROFXENV, Envision FX10, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace single-compressor water-to-air heat pumps with hot gas reheat and the FX10 DDC controller.
Also known as: PROFXENV-RH-00, PROFXENV-RH, Envision hot gas reheat, WaterFurnace FX10 - Water-source DOAS controller with energy recovery
WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC)
WaterFurnace Versatec 700 indoor dedicated outdoor air systems: up to four variable speed water-source heat pump modules with an energy recovery wheel, economizers and DCV, on the Aurora UPC.
Also known as: Versatec 700, Versatec DOAS, WaterFurnace DOAS, DOAS BACnet Point List 1.00 - Water-to-water heat pump controller
WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec dual-compressor water-to-water heat pumps with the FX10 DDC controller and expansion board.
Also known as: PRODCWW-02, PRODCWW, Versatec Dual Compressor, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Versatec Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWW-03, PROSSWW, Versatec Water-to-Water, WaterFurnace FX10
Source: BACnet Points for Single Compressor Water-to-Air Console Units Utilizing the FX10 Controller · PROSSWAC-02 · rev. 2013-02. Object names, instances and units are reproduced as published; descriptions are our own.