Water-source heat pump controller (console) · BACnet points list

WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) BACnet points list

Updated 4 November 2026

Short answer

BACnet objects for WaterFurnace's single-compressor console heat pump on the FX10 controller. It is a short list: space and discharge air temperatures, effective setpoints, an alarm code, flash-stored setpoints and limits, and read-only status of the fan, compressor, reversing valve and two digital inputs. The BAS can shift both setpoints with Space Setpoint (AO1) and override the space temperature (AO2).

This page lists 24 BACnet objects for the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.

Manufacturer
WaterFurnace
Model
Single Compressor Water-to-Air Console Unit (FX10)
Equipment
Water-source heat pump controller (console)
Equipment type
Heat pumps
BACnet objects
24 (12 writable)
Transport
—
Firmware
Not stated
Also known as
PROSSWAC-02, PROSSWAC, WaterFurnace console heat pump FX10, WaterFurnace FX10
Source document
BACnet Points for Single Compressor Water-to-Air Console Units Utilizing the FX10 Controller · PROSSWAC-02 · rev. 2013-02
Download CSV 24 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WaterFurnace’s current documentation and the live device before use. Not official WaterFurnace information. Terms of use.

BMS integration notes: WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)

Integration in brief

The console unit runs on its own setpoints; the BAS mainly adjusts them and monitors. Use Space Setpoint (AO1) to move both setpoints from one command, or AO2 to feed a network space temperature. Keep frequent writes on the volatile AO points, not the flash-backed AV setpoints.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AO 1Space SetpointMidpoint setpoint; shifts heat and cool togetherWrite
AV 1Occupied CoolOccupied cooling setpoint (flash; write rarely)Write
AV 3Occupied HeatOccupied heating setpoint (flash; write rarely)Write
MI 1Mode StatusUnit mode: auto or shutdownRead
MI 6Compr Cmd StatusCompressor commanded on/offRead
AI 1Space TemperatureSpace sensor temperature (terminals RS/AIC)Read
AI 2Discharge AirDischarge (supply) air temperatureRead
AI 5AlarmsActive alarm codeRead

Enable & remote start

The sheet has no enable, occupancy or shutdown command; the unit runs on its local control and the BAS adjusts setpoints.

Sensors & values from the BMS

AO2 Space Temp Override replaces the space sensor reading from the network. It is a volatile output, so it reverts to uncommanded after a power cycle.

Watch out for

WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

24 of 24 shown
Type
Multi-state
Access
Show
WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) BACnet Points List
DescriptionStates
AImin1Space TemperatureSpace sensor reading (terminals RS/AIC)Read
AImin2Discharge AirDischarge air sensor (field mounted unless factory special)Read
AI3Effective Clg SetptEffective cooling setpointRead
AI4Effective Hgt SetptEffective heating setpointRead
AImin5AlarmsActive alarm code (see alarm table)Read0=No Alarm; 1=Condensate Detected; 2=Compressor High Discharge Pressure; 3=Compressor Low Suction Pressure; 4=Freeze Protection; 8=Faulty Freeze Sensor Alarm
AOmin1Space SetpointMidpoint setpoint; moves heating and cooling setpoints togetherWrite
AO2Space Temp OverrideNetwork override of the space temperature readingWrite
AVmin1Occupied CoolOccupied cooling setpoint (flash)Write
AV2Unoccupied CoolUnoccupied cooling setpoint (flash)Write
AVmin3Occupied HeatOccupied heating setpoint (flash)Write
AV4Unoccupied HeatUnoccupied heating setpoint (flash)Write
AV5Max Hgt SetptUpper limit for the heating setpointWrite
AV6Min Clg SetptLower limit for the cooling setpointWrite
AV7Remote Setpt MaxSensor setpoint shift, plus sideWrite
AV8Remote Setpt MinSensor setpoint shift, minus sideWrite
AV9Space Sensor CalibrateCalibration offset for the zone sensorWrite
AV10Compr DifferentialCompressor call deadbandWrite
MImin1Mode StatusCurrent unit modeRead1=Auto (Normal); 7=Off (Shutdown)
MI2Effective OccupancyCurrent occupancy statusRead1=Occupied; 2=Unoccupied; 3=Bypass (temporary occupancy)
MI3Comp/Fan ProveDigital input 6 (field-installed current relay)Read1=Off; 2=On
MI4Dirty Filter InputDigital input 12 (field-installed current relay)Read1=Off; 2=On
MI5Fan Cmd StatusCommanded fan statusRead1=Off; 2=On
MImin6Compr Cmd StatusCommanded compressor statusRead1=Off; 2=On
MI7Rev Valve StatusCommanded reversing valve positionRead1=Heating; 2=Cooling
Object ID lookup: WaterFurnace Water-to-Air Console (FX10) point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Single Compressor Water-to-Air Console Unit (FX10) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)

How many BACnet points does the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) have?

This list has 24 BACnet objects: 5 analog inputs, 2 analog outputs, 10 analog values, 7 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) BACnet points are writable?

12 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WaterFurnace Single Compressor Water-to-Air Console Unit (FX10) BACnet documentation?

The source is BACnet Points for Single Compressor Water-to-Air Console Units Utilizing the FX10 Controller (PROSSWAC-02), revision 2013-02, published free by WaterFurnace at https://www.waterfurnace.com/downloads/ddc/BACnet-Resources/BACnet-points-pdfs/PROSSWAC-02.pdf.

What are the minimum BACnet points to integrate the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)?

Start with AO 1 Space Setpoint (Midpoint setpoint; shifts heat and cool together); AV 1 Occupied Cool (Occupied cooling setpoint (flash; write rarely)); AV 3 Occupied Heat (Occupied heating setpoint (flash; write rarely)); MI 1 Mode Status (Unit mode: auto or shutdown); MI 6 Compr Cmd Status (Compressor commanded on/off); AI 1 Space Temperature (Space sensor temperature (terminals RS/AIC)); AI 2 Discharge Air (Discharge (supply) air temperature); AI 5 Alarms (Active alarm code).

How do I enable BMS control of the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)?

The sheet has no enable, occupancy or shutdown command; the unit runs on its local control and the BAS adjusts setpoints.

Can the BMS supply sensor values to the WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)?

AO2 Space Temp Override replaces the space sensor reading from the network. It is a volatile output, so it reverts to uncommanded after a power cycle.

How do I check these points on the real Single Compressor Water-to-Air Console Unit (FX10)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WaterFurnace BACnet points lists

Source: BACnet Points for Single Compressor Water-to-Air Console Units Utilizing the FX10 Controller · PROSSWAC-02 · rev. 2013-02. Object names, instances and units are reproduced as published; descriptions are our own.