Water-to-water heat pump controller · BACnet points list

WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10) BACnet points list

Updated 28 October 2026

Short answer

BACnet objects for WaterFurnace's single-compressor Envision water-to-water heat pump on the FX10 controller. The BAS sends the compressor (Y1) and reversing valve calls and can shut the unit down or reset lockouts. Statuses (compressor, valve, accessory outputs, flow switches, alarm) are multistate inputs, and AI14 gives an alarm code.

This page lists 24 BACnet objects for the WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10) — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.

Manufacturer
WaterFurnace
Model
Envision Single Compressor Water-to-Water Heat Pump (FX10)
Equipment
Water-to-water heat pump controller
Equipment type
Heat pumps
BACnet objects
24 (4 writable)
Transport
—
Firmware
Not stated
Also known as
PROSSWWE-01, PROSSWWE, Envision Water-to-Water, WaterFurnace FX10
Source document
BACnet Points List for Single Compressor Water to Water · PROSSWWE-01
Download CSV 24 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)

Integration in brief

The BAS stages this unit directly with MO1 (compressor Y1 call) and MO2 (reversing valve). MO3 gives a network emergency shutdown and MO5 resets lockouts. Supervise it with the load water temperatures, MI1 mode and the AI14 alarm code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 1Compressor EnableCompressor call (Y1)Write
MO 2Valve EnableHeating/cooling selectionWrite
MO 3Emerg OverrideNetwork emergency shutdownWrite
MO 5Alarm ResetReset lockout alarmsWrite
MI 1Mode of OperationAuto or shutdown statusRead
MI 2Comp Cmd StatusCompressor commanded on/offRead
AI 3Enter Load TempEntering load water temperatureRead
AI 4Leave Load tempLeaving load water temperatureRead
AI 14Alarms EnumeratedActive alarm codeRead

Enable & remote start

There is no internal temperature control or enable point: the unit runs only on external compressor (Y1) and reversing valve (O) calls, sent either at the terminal board or over the network. Emergency shutdown comes from MO3 Emerg Override (5=Shutdown) or a closed contact on BI-2.

Network setup

Watch out for

WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

24 of 24 shown
Type
Analog
Access
Show
WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10) BACnet Points List
DescriptionStates
AI1Source FrzRefrigerant temp entering source heat exchangerRead
AI2Load FrzRefrigerant temp entering load heat exchangerRead
AImin3Enter Load TempEntering load water temperatureRead
AImin4Leave Load tempLeaving load water temperatureRead
AI5Enter Source TempEntering source water temperatureRead
AI6Leave Source TempLeaving source water temperatureRead
AI7Source Frz SetptSource heat exchanger freeze limitRead
AI8Load Frz SetptLoad heat exchanger freeze limitRead
AImin14Alarms EnumeratedActive alarm codeRead0=No alarms; 1=Load Flow Switch; 2=Compressor Low Suction Pressure; 3=Source Low Temp; 4=Load Low Temp; 5=Source Flow Switch; 6=Hi Pressure; 7=Bad Sensor Source Low Limit; 8=Bad Sensor Load Low Limit; 9=Loss of Charge; 10=High Limit Shutdown
MImin1Mode of OperationCurrent operating statusRead1=Auto; 7=Shutdown
MImin2Comp Cmd StatusCommanded compressor stateRead1=Off; 2=On
MI3Rev Vlv StatusCommanded reversing valve positionRead1=Heating; 2=Cooling
MI4LoadPmpStatusAccessory 1 output stateRead1=Off; 2=On
MI5SrcPmpStatusAccessory 2 output stateRead1=Off; 2=On
MI6Alarm StatusAlarm output stateRead1=Off; 2=On
MI7Comp Status ProveCompressor proving input (optional, field mounted)Read1=Off; 2=On
MI8BI9 StatusBI9 contact stateRead1=Open; 2=Closed
MI9Load Flow StatusLoad flow switchRead1=Off; 2=On
MI10Src Flow StatusSource flow switchRead1=Off; 2=On
MI11BI6 StatusBI6 contact stateRead1=Open; 2=Closed
MOmin1Compressor EnableNetwork compressor call (thermostat Y1)Write1=Off; 2=On
MOmin2Valve EnableNetwork reversing valve callWrite1=Cooling; 2=Heating
MOmin3Emerg OverrideNetwork emergency shutdownWrite1=Normal; 5=Shutdown
MOmin5Alarm ResetReset lockout alarms: change from 1 to 2Write

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Envision Single Compressor Water-to-Water Heat Pump (FX10) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)

How many BACnet points does the WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10) have?

This list has 24 BACnet objects: 9 analog inputs, 11 multi-state inputs, 4 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10) BACnet points are writable?

4 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10) BACnet documentation?

The source is BACnet Points List for Single Compressor Water to Water (PROSSWWE-01), published free by WaterFurnace at https://www.waterfurnace.com/downloads/ddc/BACnet-Resources/BACnet-points-pdfs/PROSSWWE-01.pdf.

What are the minimum BACnet points to integrate the WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)?

Start with MO 1 Compressor Enable (Compressor call (Y1)); MO 2 Valve Enable (Heating/cooling selection); MO 3 Emerg Override (Network emergency shutdown); MO 5 Alarm Reset (Reset lockout alarms); MI 1 Mode of Operation (Auto or shutdown status); MI 2 Comp Cmd Status (Compressor commanded on/off); AI 3 Enter Load Temp (Entering load water temperature); AI 4 Leave Load temp (Leaving load water temperature); AI 14 Alarms Enumerated (Active alarm code).

How do I enable BMS control of the WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)?

There is no internal temperature control or enable point: the unit runs only on external compressor (Y1) and reversing valve (O) calls, sent either at the terminal board or over the network. Emergency shutdown comes from MO3 Emerg Override (5=Shutdown) or a closed contact on BI-2.

How do I check these points on the real Envision Single Compressor Water-to-Water Heat Pump (FX10)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WaterFurnace BACnet points lists

Source: BACnet Points List for Single Compressor Water to Water · PROSSWWE-01. Object names, instances and units are reproduced as published; descriptions are our own.