Water-source heat pump controller · BACnet points list

WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton BACnet points list

Updated 28 October 2026

Short answer

BACnet variables for WaterFurnace Envision 1-6 ton water-to-air heat pumps. The BAS can command occupancy and let the controller hold its occupied/unoccupied setpoints, or send G, Y1, Y2 and O calls directly. Unit statuses are binary inputs in this version, and ECM fan speeds, passive dehumidification, sensor type and fan cycling are set through writable values.

This page lists 55 BACnet objects for the WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton — 33 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.

Manufacturer
WaterFurnace
Model
Envision Water-to-Air Heat Pump, 1-6 Ton
Equipment
Water-source heat pump controller
Equipment type
Heat pumps
BACnet objects
55 (33 writable)
Transport
—
Firmware
Not stated
Also known as
Envision BACnet Variables, Envision BACnet Variables with BI, Envision 1-6 Ton
Source document
Envision BACnet Variables
Download CSV 55 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton

Integration in brief

The BAS can run this heat pump in two ways: command occupancy (MO1) and let the controller hold its occupied/unoccupied setpoints, or act as the thermostat and send fan, Y1, Y2 and O calls directly (MO2-MO5). Space temperature can be overridden from the network on AO4, and MO6 forces an emergency shutdown.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 1Occupancy CommandOccupied/unoccupied/bypass commandWrite
MO 6Emergency OverideNetwork emergency shutdownWrite
AV 1Occupied CoolOccupied cooling setpoint (write rarely)Write
AV 3Occupied HeatOccupied heating setpoint (write rarely)Write
MO 7Alarm ResetReset manual-reset alarmsWrite
MI 2Mode StatusAuto or shutdown statusRead
BI 2Comp Cmd StatusCompressor commanded on/offRead
AI 1Space TempSpace sensor temperatureRead
AI 2Discharge Air TempDischarge (supply) air temperatureRead
AI 9Alarms EnumeratedActive alarm codeRead

Enable & remote start

The sheet has no separate BAS-enable point. MO6 Emergency Overide puts the unit in shutdown (5) or back to normal (1). MO2-MO5 let the BAS send fan, compressor and reversing-valve calls directly.

Sensors & values from the BMS

AO4 Space temp Ovrd sends the space temperature from the network and supersedes the wired sensor. It is volatile and reverts to uncommanded after a power outage.

Network setup

Watch out for

WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

55 of 55 shown
Type
Binary
Access
Show
WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton BACnet Points List
DescriptionStates
AImin1Space TempSpace temperatureRead
AImin2Discharge Air TempDischarge air sensor (field mounted unless factory special)Read
AI3Effective Clg SetptActive cooling setpointRead
AI4Effective Htg SetptActive heating setpointRead
AI5Space HumiditySpace humidityRead
AI6Water Coil TempColdest refrigerant temperature, for freeze detectionRead
AI7Low Temp LimitWater coil low limit that shuts the unit downRead
AI8ECM Cmd OutputCommanded ECM blower speed%Read
AImin9Alarms EnumeratedActive alarm codeRead0=No alarms; 1=Condensate; 2=Compressor Hi Discharge Pressure; 3=Compressor Low Suction Pressure; 4=Freeze Protection; 8=Faulty Freeze Sensor; 9=Loss of Charge
AI10AO2 ValueOutput value of AO2%Read
AO1Space SetpointMidpoint setpoint; moves heating and cooling setpoints togetherWrite
AO2ECM Fan OvrdNetwork control of ECM blower speedWrite
AO3AO2 OverrideNetwork control of analog output 2Write
AO4Space temp OvrdNetwork space temperature; supersedes the wired sensorWrite
AVmin1Occupied CoolOccupied cooling setpointWrite
AV2Unoccupied CoolUnoccupied cooling setpointWrite
AVmin3Occupied HeatOccupied heating setpointWrite
AV4Unoccupied HeatUnoccupied heating setpointWrite
AV5Temporary Occ TimeDuration of the zone-sensor temporary occupancy timerWrite
AV6Remote Setpt SpanRange of the zone sensor setpoint knobWrite
AV7Remote Setpt BiasBias of the remote setpoint adjust rangeWrite
AV8Space Temp OffsetCalibration offset added to Space TempWrite
AV9Dehumidify SetptHumidity that starts passive dehumidificationWrite
AV10Low Temp Limit AdjWater coil low temperature shutdown limitWrite
AV11Fan Only SpeedFan speed for ECM switch 1Write
AV12Medium FanFan speed for ECM switch 2Write
AV13High FanFan speed for ECM switch 3Write
BI1Fan Cmd StatusCommanded fan outputReadInactive=Off; Active=On
BImin2Comp Cmd StatusCommanded compressor outputReadInactive=Off; Active=On
BI3Comp Hi Capacity CmdCommanded high-capacity compressor controlReadInactive=Off; Active=On
BI4Reversing ValveCommanded reversing valve positionReadInactive=Heating; Active=Cooling
BI5Accessory 1 OutputX1 (accessory 1) output stateReadInactive=Off; Active=On
BI6Accessory 2 OutputX2 (accessory 2) output stateReadInactive=Off; Active=On
BI7Dirty Filter BI-12Dirty filter contact on BI-12ReadInactive=Off; Active=On
BI8Alarm StatusIn alarm / out of alarmReadInactive=Off; Active=On
BI9BO5 OutputBO5 (electric heat) output stateReadInactive=Off; Active=On
BI10BO9 OutputBO9 output stateReadInactive=Off; Active=On
MI1Effective OccupancyCurrent occupancy statusRead1=Occupied; 2=Unoccupied; 3=Bypass; 255=Invalid
MImin2Mode StatusAuto or shutdownRead1=Auto; 7=Shutdown
MOmin1Occupancy CommandNetwork occupancy commandWrite1=Occupied; 2=Unoccupied; 3=Bypass; 255=Invalid
MO2Fan Command (G)Network fan call (thermostat G)Write
MO3Compressor Cmd (Y1)Network compressor call (thermostat Y1)Write
MO4Compressor Cmd (Y2)Network compressor call (thermostat Y2)Write
MO5Reversing Vlv Cmd (O)Network reversing valve call (thermostat O)Write
MOmin6Emergency OverideRapid network shutdown (fire etc.)Write1=Normal; 5=Shutdown
MOmin7Alarm ResetReset lockout alarms: On for 20 s, then OffWrite1=Off; 2=On
MO8Emergency Heat BO5Network emergency heat command; can stop auto emergency heatWrite
MO9BO9Network control of spare output BO9Write1=Off; 2=On
MO10Dehum CmdDehumidify command (no description in the sheet)Write
MV1SW1ECM switch 1 selectionWrite2=Selected
MV2SW2ECM switch 2 selectionWrite2=Selected
MV3SW3ECM switch 3 selectionWrite2=Selected
MV4DehumEnaDisEnable passive dehumidificationWrite1=Disable; 2=Enable
MV5SensorSelZone sensor model selectionWrite1=TAXXJ02; 2=TAXXA01
MV6FanCyclingContinuous or cycled fanWrite1=Continuous; 2=Cycled

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Envision Water-to-Air Heat Pump, 1-6 Ton and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton

How many BACnet points does the WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton have?

This list has 55 BACnet objects: 10 analog inputs, 4 analog outputs, 13 analog values, 10 binary inputs, 2 multi-state inputs, 10 multi-state outputs, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton BACnet points are writable?

33 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton BACnet documentation?

The source is Envision BACnet Variables, published free by WaterFurnace at https://www.waterfurnace.com/downloads/ddc/BACnet-Resources/BACnet-points-pdfs/Envision-BACnet-Variables-with-BI-1-6-Ton.pdf.

What are the minimum BACnet points to integrate the WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton?

Start with MO 1 Occupancy Command (Occupied/unoccupied/bypass command); MO 6 Emergency Overide (Network emergency shutdown); AV 1 Occupied Cool (Occupied cooling setpoint (write rarely)); AV 3 Occupied Heat (Occupied heating setpoint (write rarely)); MO 7 Alarm Reset (Reset manual-reset alarms); MI 2 Mode Status (Auto or shutdown status); BI 2 Comp Cmd Status (Compressor commanded on/off); AI 1 Space Temp (Space sensor temperature); AI 2 Discharge Air Temp (Discharge (supply) air temperature); AI 9 Alarms Enumerated (Active alarm code).

How do I enable BMS control of the WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton?

The sheet has no separate BAS-enable point. MO6 Emergency Overide puts the unit in shutdown (5) or back to normal (1). MO2-MO5 let the BAS send fan, compressor and reversing-valve calls directly.

Can the BMS supply sensor values to the WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton?

AO4 Space temp Ovrd sends the space temperature from the network and supersedes the wired sensor. It is volatile and reverts to uncommanded after a power outage.

How do I check these points on the real Envision Water-to-Air Heat Pump, 1-6 Ton?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WaterFurnace BACnet points lists

Source: Envision BACnet Variables. Object names, instances and units are reproduced as published; descriptions are our own.