Water-to-water heat pump / reversible chiller controller · BACnet points list

WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10) BACnet points list

Updated 28 October 2026

Short answer

BACnet objects for WaterFurnace's dual-compressor reversible chiller water-to-water heat pumps running the FX10 DDC controller. The BAS reads load/source water and refrigerant temperatures, flow switches, compressor and alarm states, and stages the machine by writing Y1/Y2 compressor calls and the reversing valve (O) command. Two flash-backed values set the low-temperature limit adjustment and the compressor on-delay.

This page lists 33 BACnet objects for the WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10) — 10 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.

Manufacturer
WaterFurnace
Model
Reversible Chiller Water-to-Water Heat Pump (FX10)
Equipment
Water-to-water heat pump / reversible chiller controller
Equipment type
Chillers
BACnet objects
33 (10 writable)
Transport
—
Firmware
Not stated
Also known as
PRODCWWE-06B, PRODCWWE-07B, PRODCWWE-08B, PRODCWWE
Source document
BACnet Points for Reversible Chiller Water-to-Water Heat Pumps Utilizing the FX10 Controller · PRODCWWE-06B-07B-08B · rev. 2013-02
Download CSV 33 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)

Integration in brief

The BAS stages this machine directly: MO1/MO2 are the Y1/Y2 compressor calls and MO3 is the reversing valve (O) call. Read load and source water temperatures, flow switches and the alarm code to supervise it. The two configuration values (freeze setpoint adjust, compressor on-delay) are flash-backed and should be set once.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 1Compr 1 Cmd (Y1)Stage 1 compressor callWrite
MO 2Compr 2 Cmd (Y2)Stage 2 compressor callWrite
MO 3Rev Valve Cmd (O)Heating/cooling selectionWrite
MO 4Alarm ResetReset manual-reset alarmsWrite
MI 1Mode of OperationAuto or shutdown statusRead
MI 2Compr 1 Cmd StatusCompressor 1 commanded on/offRead
AI 3Enter Load TempEntering load water temperatureRead
AI 4Leaving Load TempLeaving load water temperatureRead
AI 14AlarmsActive alarm codeRead

Enable & remote start

The sheet has no separate enable or occupancy point. The BAS controls the unit with the MO1/MO2 compressor calls and the MO3 reversing-valve call.

Watch out for

WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

33 of 33 shown
Type
Access
Show
WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10) BACnet Points List
DescriptionStates
AI1Source Frz 1Refrigerant temp entering source heat exchanger, comp 1Read
AI2Load Frz 1Refrigerant temp entering load heat exchanger, comp 1Read
AImin3Enter Load TempEntering load water temperatureRead
AImin4Leaving Load TempLeaving load water temperatureRead
AI5Enter Source TempEntering source water temperatureRead
AI6Leaving Source TempLeaving source water temperatureRead
AI7Source Frz SetptSource heat exchanger low temperature limitRead
AI8Load Frz SetptLoad heat exchanger low temperature limitRead
AI9Comp1 Status OutputCommanded compressor 1 statusRead1=Off; 2=On
AI10Alarm Status OutputCommanded alarm output statusRead1=Off; 2=On
AI11Comp2 Status OutputCommanded compressor 2 statusRead1=Off; 2=On
AI12Source Frz 2Refrigerant temp entering source heat exchanger, comp 2Read
AI13Load Frz 2Refrigerant temp entering load heat exchanger, comp 2Read
AImin14AlarmsActive alarm code (see alarm table)Read0=No alarms; 1=Load Flow Switch; 2=Comp 1 Low Suction Pressure; 3=Source Low Temp Comp 1; 4=Source Predictive Freeze Comp 1; 5=Source Flow Switch; 6=High Pressure Comp 1; 7=Bad Source Sensor Comp 1; 8=Bad Load Sensor Comp 1; 9=Comp 2 Low Suction Pressure; 10=Source Low Temp Comp 2; 11=Bad Source Sensor Comp 2; 12=Source Predictive Freeze Comp 2; 13=Bad Load Sensor Comp 2; 14=High Pressure Comp 2; 15=Comp 1 Start Failure; 16=Low Temp Cutoff Comp 1; 17=Low Temp Cutoff Comp 2; 18=Comp 2 Start Failure; 19=Load Low Temp Comp 1; 20=Load Predictive Freeze Comp 1; 21=Load Low Temp Comp 2; 22=Load Predictive Freeze Comp 2; 23=Comp 1 Charge Loss; 24=Comp 2 Charge Loss
AV1Frz Setpt AdjLow temp limit adjustment (board jumpers removed); flashWrite
AV2Compressor On DelayCompressor on-delay timer, default 90 s; flashWrite
MImin1Mode of OperationCurrent operating statusRead1=Auto; 7=Shutdown
MImin2Compr 1 Cmd StatusCommanded compressor 1 statusRead1=Off; 2=On
MI3Compr 2 Cmd StatusCommanded compressor 2 statusRead1=Off; 2=On
MI4Rev Valve StatusCommanded reversing valve positionRead1=Heating; 2=Cooling
MI5Acc 1 StatusACC 1 (X1) output stateRead1=Off; 2=On
MI6Stage 1 AlarmCompressor 1 alarm statusRead1=Off; 2=Alarm
MI7Stage 2 AlarmCompressor 2 alarm statusRead1=Off; 2=Alarm
MI8Load Flow SwitchLoad flow switch inputRead1=Open; 2=Closed
MI9Source Flow SwitchSource flow switch inputRead1=Open; 2=Closed
MOmin1Compr 1 Cmd (Y1)Network compressor call (thermostat Y1)Write1=Off; 2=On
MOmin2Compr 2 Cmd (Y2)Network compressor call (thermostat Y2)Write1=Off; 2=On
MOmin3Rev Valve Cmd (O)Network reversing valve call (thermostat O)Write1=Heating; 2=Cooling
MOmin4Alarm ResetReset manual-reset alarms: write 2, then back to 1Write
MO5nviEXPBO1Network control of expansion board output 1Write1=Off; 2=On
MO6nviEXPO2Network control of expansion board output 2Write1=Off; 2=On
MO7nviEXPO7Network control of expansion board output 7Write1=Off; 2=On
MO8nviEXPO8Network control of expansion board output 8Write1=Off; 2=On

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Reversible Chiller Water-to-Water Heat Pump (FX10) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)

How many BACnet points does the WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10) have?

This list has 33 BACnet objects: 14 analog inputs, 2 analog values, 9 multi-state inputs, 8 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10) BACnet points are writable?

10 of the 33 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10) BACnet documentation?

The source is BACnet Points for Reversible Chiller Water-to-Water Heat Pumps Utilizing the FX10 Controller (PRODCWWE-06B-07B-08B), revision 2013-02, published free by WaterFurnace at https://www.waterfurnace.com/downloads/ddc/BACnet-Resources/BACnet-points-pdfs/PRODCWWE-06B-07B-08B.pdf.

What are the minimum BACnet points to integrate the WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)?

Start with MO 1 Compr 1 Cmd (Y1) (Stage 1 compressor call); MO 2 Compr 2 Cmd (Y2) (Stage 2 compressor call); MO 3 Rev Valve Cmd (O) (Heating/cooling selection); MO 4 Alarm Reset (Reset manual-reset alarms); MI 1 Mode of Operation (Auto or shutdown status); MI 2 Compr 1 Cmd Status (Compressor 1 commanded on/off); AI 3 Enter Load Temp (Entering load water temperature); AI 4 Leaving Load Temp (Leaving load water temperature); AI 14 Alarms (Active alarm code).

How do I enable BMS control of the WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)?

The sheet has no separate enable or occupancy point. The BAS controls the unit with the MO1/MO2 compressor calls and the MO3 reversing-valve call.

How do I check these points on the real Reversible Chiller Water-to-Water Heat Pump (FX10)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WaterFurnace BACnet points lists