Water-to-water heat pump controller · BACnet points list

WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10) BACnet points list

Updated 28 October 2026

Short answer

BACnet objects for WaterFurnace's dual-compressor Versatec water-to-water heat pump on the FX10 controller. The BAS sends the lead (Y1) and lag (Y2) compressor calls and the reversing valve call, and reads water and refrigerant temperatures for both circuits, per-stage alarms and compressor status. Two flash-backed values set the freeze limits.

This page lists 32 BACnet objects for the WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10) — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.

Manufacturer
WaterFurnace
Model
Versatec Dual Compressor Water-to-Water Heat Pump (FX10)
Equipment
Water-to-water heat pump controller
Equipment type
Heat pumps
BACnet objects
32 (7 writable)
Transport
—
Firmware
Not stated
Also known as
PRODCWW-02, PRODCWW, Versatec Dual Compressor, WaterFurnace FX10
Source document
BACnet Points For Versatec Dual Compressor Water to Water · PRODCWW-02
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)

Integration in brief

The BAS stages this unit directly: MO2 is the lead compressor (Y1) call, MO6 the lag compressor (Y2) call and MO3 the reversing valve call. MO1 shuts the unit down from the network and BO1 resets manual-reset alarms. Watch load water temperatures, the AI10 alarm status and the per-stage alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MO 2Compressor 1 EnableStage 1 compressor callWrite
MO 6Compressor 2 EnableStage 2 compressor callWrite
MO 3Valve EnableHeating/cooling selectionWrite
MO 1Emergency OverrideNetwork emergency shutdownWrite
BO 1Alarm ResetReset manual-reset alarmsWrite
MI 1Mode of OperationAuto or shutdown statusRead
BI 1Compr 1 Cmd StatusCompressor 1 commanded on/offRead
AI 3Enter Load TempEntering load water temperatureRead
AI 4Leave Load Temp1Leaving load water temperatureRead
AI 10Alarm Status OutputAny alarm (0 % normal, 100 % alarm)Read

Enable & remote start

There is no internal temperature control or enable point: the unit runs only on external compressor (Y1) and reversing valve (O) calls, sent either at the terminal board or over the network. MO1 Emergency Override (1=Normal, 5=Shutdown) stops both compressors.

Network setup

Watch out for

WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

32 of 32 shown
Type
Access
Show
WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10) BACnet Points List
DescriptionStates
AI1Source Frz 1Refrigerant temp entering source heat exchanger, comp 1Read
AI2Load Frz 1Refrigerant temp entering load heat exchanger, comp 1Read
AImin3Enter Load TempEntering load water temperatureRead
AImin4Leave Load Temp1Leaving load water temperature, heat exchanger 1Read
AI5Enter Source Temp1Entering source water temperature, heat exchanger 1Read
AI6Leave Source TempLeaving source water temperatureRead
AI7Source Frz SetptSource heat exchanger freeze limitRead
AI8Load Frz SetptLoad heat exchanger freeze limitRead
AI9Comp1 Status OutputCompressor 1 state: 0 % off, 100 % on%Read
AImin10Alarm Status OutputAlarm state: 0 % normal, 100 % in alarm%Read
AI11Comp2 Status OutputCompressor 2 state: 0 % off, 100 % on%Read
AI12Source Frz 2Refrigerant temp entering source heat exchanger, comp 2Read
AI13Load Frz 2Refrigerant temp entering load heat exchanger, comp 2Read
AI14Leave Load Temp2Leaving load water temperature, heat exchanger 2Read
AI15Enter Source Temp2Entering source water temperature, heat exchanger 2Read
AV1Frz Setpt 1Freeze limit with selection jumpers installed (flash)Write
AV2Frz Setpt 2Freeze limit with selection jumpers removed (flash)Write
BImin1Compr 1 Cmd StatusCommanded compressor 1 stateReadInactive=Off; Active=On
BI2Compr 2 Cmd StatusCommanded compressor 2 stateReadInactive=Off; Active=On
BI3Rev Valve StatusCommanded reversing valve positionReadInactive=Cooling; Active=Heating
BI4Acc 1 StatusAccessory 1 output stateReadInactive=Off; Active=On
BI5Acc 2 StatusAccessory 2 output stateReadInactive=Off; Active=On
BI6Stage 1 AlarmCompressor 1 alarmReadInactive=Normal; Active=Alarm
BI7Stage 2 AlarmCompressor 2 alarmReadInactive=Normal; Active=Alarm
BOmin1Alarm ResetReset manual-reset alarms: Active, then back to InactiveWriteInactive=Normal; Active=Reset
MImin1Mode of OperationCurrent operating statusRead1=Auto; 7=Shutdown
MOmin1Emergency OverrideNetwork emergency shutdownWrite1=Normal; 5=Shutdown
MOmin2Compressor 1 EnableLead compressor call (thermostat Y1)Write1=Off; 2=On
MOmin3Valve EnableNetwork reversing valve callWrite1=Cooling; 2=Heating
MO4Application ModeNot usedRead
MO5Heat Cool ModeNot usedRead
MOmin6Compressor 2 EnableLag compressor call (thermostat Y2)Write1=Off; 2=On

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Versatec Dual Compressor Water-to-Water Heat Pump (FX10) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)

How many BACnet points does the WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10) have?

This list has 32 BACnet objects: 15 analog inputs, 2 analog values, 7 binary inputs, 1 binary output, 1 multi-state input, 6 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10) BACnet points are writable?

7 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10) BACnet documentation?

The source is BACnet Points For Versatec Dual Compressor Water to Water (PRODCWW-02), published free by WaterFurnace at https://www.waterfurnace.com/downloads/ddc/BACnet-Resources/BACnet-points-pdfs/PRODCWW-02.pdf.

What are the minimum BACnet points to integrate the WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)?

Start with MO 2 Compressor 1 Enable (Stage 1 compressor call); MO 6 Compressor 2 Enable (Stage 2 compressor call); MO 3 Valve Enable (Heating/cooling selection); MO 1 Emergency Override (Network emergency shutdown); BO 1 Alarm Reset (Reset manual-reset alarms); MI 1 Mode of Operation (Auto or shutdown status); BI 1 Compr 1 Cmd Status (Compressor 1 commanded on/off); AI 3 Enter Load Temp (Entering load water temperature); AI 4 Leave Load Temp1 (Leaving load water temperature); AI 10 Alarm Status Output (Any alarm (0 % normal, 100 % alarm)).

How do I enable BMS control of the WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)?

There is no internal temperature control or enable point: the unit runs only on external compressor (Y1) and reversing valve (O) calls, sent either at the terminal board or over the network. MO1 Emergency Override (1=Normal, 5=Shutdown) stops both compressors.

How do I check these points on the real Versatec Dual Compressor Water-to-Water Heat Pump (FX10)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.