Rooftop unit controller (water-source, with economizer) · BACnet points list

WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer BACnet points list

Updated 28 October 2026

Short answer

BACnet objects of the Aurora UPC on a WaterFurnace single-compressor rooftop unit with an air-side economizer, software version 1.01. Besides occupancy, setpoints and alarms it covers the economizer (outdoor and return air temperature and humidity, enthalpy, damper position), demand controlled ventilation, ECM blower and variable speed pump settings.

This page lists 284 BACnet objects for the WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer — 145 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.

Manufacturer
WaterFurnace
Model
Aurora UPC, Single Compressor Rooftop Unit with Economizer
Equipment
Rooftop unit controller (water-source, with economizer)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
284 (145 writable)
Transport
BACnet MS/TP
Firmware
UPC software version 1.01
Also known as
PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter
Source document
UPC BACnet Points List For Single/Dual Compressor Rooftop Economizer · PL1250EW · rev. 2018-09
Download CSV 284 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer

Integration in brief

Keep BV 502 at External and command occupancy on MSV 500; the UPC holds the occupied, unoccupied and standby setpoints (AV 511-516) and runs the economizer itself. Read MSV 100 for the operating mode and AV 119 for the combined alarm code. BV 110-115 let the BAS send Y1, Y2, W, O, G and DH calls directly.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 500occ_man_msv_cOccupied/unoccupied/temp occ/standby commandWrite
BV 502schedule_select_cMust be External for BAS occupancy commandsWrite
BV 101em_shutdown_cNetwork emergency shutdownWrite
AV 511occ_clg_setpt_cOccupied cooling setpointWrite
AV 512occ_htg_setpt_cOccupied heating setpointWrite
BV 130alarm_reset_cReset manual-reset alarms (On, then back to Off)Write
AV 500zone_tempSpace temperature (sensor or BAS override)Read
MV 100mode_msvCurrent operating modeRead
AV 119alarm_enumCombined alarm code (see alarm table)Read

Enable & remote start

BV 502 schedule_select_c picks the internal schedule (Mon-Fri 7:30-17:00 EST) or external BAS commands; External is the listed default. Occupancy commands go to MSV 500, or to AV 509 after BV 504 is set to AV; BV 506 is a separate binary BAS occupancy signal. BV 101 em_shutdown_c shuts the unit down and BV 105 load_shed_c sheds the compressor.

Sensors & values from the BMS

AV 502 zone_temp_ovrd_c replaces the zone sensor once BV 500 is set to BAS. Outdoor air temperature and humidity, and return air temperature and humidity, can come from the BAS on AV 606, 609, 614 and 617 when BV 609, 611, 613 and 615 are set to BAS. AV 602 (pressure) or AV 603 (elevation), chosen by BV 608, feed the enthalpy calculation. AV 504, 506 and 508 accept humidity, CO2 and VOC values.

Network setup

Watch out for

WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

284 of 284 shown
Type
AnalogBinaryMulti-state
Access
Show
WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer BACnet Points List
DescriptionStates
AV100active_setptSet point that is controlling the call for the compressor°FRead
AV101neut_setptNeutral air setpoint used by the economizer logic°FRead
AV102mode_avCurrent operating mode (numeric)Read1=Standby; 2=Fan Only; 3=Cool Stage 1; 4=Cool Stage 2; 5=Hot Gas Reheat; 6=Heat Stage 1; 7=Heat Stage 2; 8=Emergency Heat; 9=Auxiliary Heat; 10=Emergency Shutdown; 11=Load Shed; 12=ABC Lockout; 13=Demand Ventilation; 14=Economizer Mode; 15=ABC Lockout; 16=Cooling W/Economizer; 17=Low LAT Mode; 18=ABC Lockout; 19=ABC Lockout; 20=Cooling W/Economizer
AV103man_ecm_speed_cInternal use; do not map to BAS (default 0)Write
AV104ecm_overrideInternal use; do not map to BASRead
AV105man_vs_pump_a_cInternal use; do not map to BAS (default 0)%Write
AV107man_damp_pos_cInternal use; do not map to BAS (default 0)%Write
AV108actual_damp_posCurrent damper target position%Read
AV109fp1_setpt_aFP1 freeze detection limit (coax temp) for circuit A°FRead
AV110fp2_setpt_aFP2 freeze detection limit (air coil temp) for circuit A°FRead
AV113filter_alm_hrs_cFilter alarm hours (default 1000)hrWrite
AV114filter_hoursNumber of fan run hours since the last filter alarm resethrRead
AV115lock_stat_reg_aInternal use; do not map to BASRead
AV116alarm_enum_aABC A alarm code (see alarm table)Read0=Normal; 1=E1 Input fault; 2=E2 High pressure; 3=E3 Low pressure; 4=E4 Freeze detection FP2; 5=E5 Freeze detection FP1; 6=E6 Loss of charge; 7=E7 Condensate overflow; 8=E8 Over/under voltage; 9=E9 Airflow monitoring (future); 10=E10 Compressor monitoring; 11=E11 FP1 sensor error; 12=E12 Refrigeration monitoring (future); 13=E13 Non-critical AXB sensor error (future); 14=E14 Critical AXB sensor error (future); 15=E15 Hot water limit; 16=E16 Variable speed pump; 18=E18 Non-critical comm error; 19=E19 Critical comm error; 20=E20 UPC-ABC critical comm error; 30=E30 Zone sensor loss of comm; 101=E101 Faulty OAT sensor; 102=E102 Missing OAT sensor; 103=E103 Faulty OAH sensor; 104=E104 Missing OAH sensor; 105=E105 Faulty RAT sensor; 106=E106 Missing RAT sensor; 107=E107 Faulty RAH sensor; 108=E108 Missing RAH sensor; 121=E121 Blower support fault
AVmin119alarm_enumCombined alarm code (see alarm table)Read0=Normal; 1=E1 Input fault; 2=E2 High pressure; 3=E3 Low pressure; 4=E4 Freeze detection FP2; 5=E5 Freeze detection FP1; 6=E6 Loss of charge; 7=E7 Condensate overflow; 8=E8 Over/under voltage; 9=E9 Airflow monitoring (future); 10=E10 Compressor monitoring; 11=E11 FP1 sensor error; 12=E12 Refrigeration monitoring (future); 13=E13 Non-critical AXB sensor error (future); 14=E14 Critical AXB sensor error (future); 15=E15 Hot water limit; 16=E16 Variable speed pump; 18=E18 Non-critical comm error; 19=E19 Critical comm error; 20=E20 UPC-ABC critical comm error; 30=E30 Zone sensor loss of comm; 101=E101 Faulty OAT sensor; 102=E102 Missing OAT sensor; 103=E103 Faulty OAH sensor; 104=E104 Missing OAH sensor; 105=E105 Faulty RAT sensor; 106=E106 Missing RAT sensor; 107=E107 Faulty RAH sensor; 108=E108 Missing RAH sensor; 121=E121 Blower support fault
AV200ecm_speed_sw_aCurrent ECM target speedRead
AV201ecm_pwm_pct_aCurrent ECM PWM output percentage%Read
AV202vs_pump_spd_stat_aCurrent target % of the VS Pump output for circuit A%Read
AV203vs_pump_pct_stat_aCurrent operating % of the VS Pump output for circuit A%Read
AV206coax_temp_stat_aRefrigerant temperature at the Coax, circuit A°FRead
AV207air_coil_temp_stat_aRefrigerant temperature at the air coil, circuit A°FRead
AV210lwt_stat_aValue of the LWT Input on circuit A°FRead
AV211ewt_stat_aValue of the EWT Input on circuit A°FRead
AV212water_flow_stat_aGPM flow rate of circuit AgpmRead
AV213loop_pres_stat_aLoop pressure for circuit ApsiRead
AV214lat_statLeaving air temperature that is connected to the AXB A°FRead
AV216suct_press_stat_aSuction pressure of circuit ApsiRead
AV217disch_press_stat_aDischarge pressure of circuit ApsiRead
AV218suct_temp_stat_aSuction temperature of circuit A°FRead
AV219disch_temp_stat_aDischarge temperature of circuit A°FRead
AV220liq_line_temp_stat_aHeating liquid line temperature for circuit A°FRead
AV221sat_evap_temp_stat_aSaturated evaporator temperature for circuit A°FRead
AV222cond_temp_stat_aCondenser temperature for circuit A°FRead
AV223est_line_voltage_stat_aEstimated line voltage at circuit AVRead
AV224control_voltage_stat_aLow voltage circuit value that is powering the ABC AVRead
AV225hot_wtr_temp_stat_aHot water temperature input for circuit A°FRead
AV226univ_input_stat_aRaw count value of the circuit A universal inputRead
AV227superheat_stat_aSuperheat of circuit A°FRead
AV228htg_subcool_stat_aSubcooling calculation in the heating mode of circuit A°FRead
AV229clg_subcool_stat_aSubcooling calculation in the cooling mode of circuit A°FRead
AV230fan_current_stat_aAmp draw for the Fan output on circuit AARead
AV231aux_current_stat_aAmp draw for the Auxiliary output on circuit AARead
AV232comp_current_stat_aCompressor amps (L1 or L2), circuit AARead
AV233comp1_current_stat_aCompressor amps (L1 or L2), circuit AARead
AV234total_amps_stat_aCalculated total amp draw for circuit AARead
AV235comp_power_stat_aCompressor power of circuit AWRead
AV236fan_power_stat_aWatt usage for Fan output on circuit AWRead
AV237aux_power_stat_aWatt usage for Auxiliary output on circuit AWRead
AV238total_power_stat_aCalculated total watt usage for circuit AWRead
AV239he_hr_stat_aHeat of rejection/extraction for circuit ABtu/hrRead
AV240total_cap_stat_aCalculated value for circuit A total capacityBtu/hrRead
AV241cop_stat_aCalculated COP of circuit ARead
AV242eer_stat_aEER calculation of circuit ARead
AV301low_ecm_spd_c setting (default 3)Write
AV302med_ecm_spd_c setting (default 7)Write
AV303high_ecm_spd_c setting (default 11)Write
AV304aux_ht_ecm_spd_c setting (default 12)Write
AV305blwr_off_delay_cBlower off delay after the compressor stops (default 30)secondsWrite
AV306clg_cfm_offset_av_cPassive dehumidification CFM offset, numeric (see MV 300) (default 4)Write
AV307occ_dehum_setpt_cOccupied dehumidification set point (default 53)%rhWrite
AV308unocc_dehum_setpt_cUnoccupied dehumidification set point (default 75)%rhWrite
AV309dehum_setptCurrently active dehumidification setpoint%rhRead
AV310dehum_diff_cDehumidification differential, or deadband for operation (default 5)%rhWrite
AV311vs_pump_min_spd_a_c setting (default 50)%Write
AV312vs_pump_max_spd_a_c setting (default 100)%Write
AV313pump_opt_a_cSelects the pump or loop option for circuit A (default 0)Write
AV317flow_meter_a_cSelects the flow meter option for circuit A (default 0)Write
AV319dhw_setpt_a_cHot water setpoint for circuit A (default 130)°FWrite
AV321energy_mon_a_cSelects the energy monitor option for circuit A (default 0)Write
AV323acc1_delay_a_cSets the time delay of the ACC-1 output on circuit A (default 90)secondsWrite
AV325measured_line_volts_cCalibrates the line voltage reading (default 230)VWrite
AV326blower_config_cBlower configuration (default 9)Write
AV400fact_test_cInternal use; do not map to BAS (default 0)Write
AV401m409_cmdInternal use; do not map to BAS (default 0)Write
AV402m488_cmdInternal use; do not map to BAS (default 0)Write
AV403m417_cmdInternal use; do not map to BAS (default 0)Write
AV404m494_cmdInternal use; do not map to BAS (default 0)Write
AV405m421_cmdInternal use; do not map to BAS (default 0)Write
AV406m495_cmdInternal use; do not map to BAS (default 0)Write
AV407m425_cmdInternal use; do not map to BAS (default 0)Write
AV408m496_cmdInternal use; do not map to BAS (default 0)Write
AV409m429_cmdInternal use; do not map to BAS (default 0)Write
AV410m497_cmdInternal use; do not map to BAS (default 0)Write
AV411m433_cmdInternal use; do not map to BAS (default 0)Write
AV412m498_cmdInternal use; do not map to BAS (default 0)Write
AV413m441_cmdInternal use; do not map to BAS (default 0)Write
AV414m445_cmdInternal use; do not map to BAS (default 0)Write
AV415m500_cmdInternal use; do not map to BAS (default 0)Write
AV416m449_cmdInternal use; do not map to BAS (default 0)Write
AV417m501_cmdInternal use; do not map to BAS (default 0)Write
AV418m453_cmdInternal use; do not map to BAS (default 0)Write
AV420tstat_ovrd_cInternal use; do not map to BAS (default 0)Write
AV430abc_fw_rev_aInternal use; do not map to BASRead
AV431sw_part_no_aInternal use; do not map to BASRead
AV432abc_fw_beta_aInternal use; do not map to BASRead
AVmin500zone_tempZone temperature (sensor average or BAS override)°FRead
AV501zone_temp_adj_cZone temperature calibration offset (default 0)°FWrite
AV502zone_temp_ovrd_cBAS override of zone temperature (default 0)°FWrite
AV503zone_humHumidity value of the zone sensor%rhRead
AV504humidity_cBAS override of the space humidity value if desired (default 0)%rhWrite
AV505co2_statCO2 valueppmRead
AV506co2_cmd_cBAS-written CO2 value (default 0)ppmWrite
AV507voc_statVOC valueppmRead
AV508voc_cmd_cBAS-written VOC value (default 0)ppmWrite
AV509occ_man_av_cOccupancy command (used when BV 504 = AV) (default 1)Write
AV510eff_occ_stCurrent occupancy status of the systemRead
AVmin511occ_clg_setpt_cOccupied cooling set point°FWrite
AVmin512occ_htg_setpt_cOccupied heating set point°FWrite
AV513unocc_clg_setpt_cUnoccupied cooling set point°FWrite
AV514unocc_htg_setpt_cUnoccupied heating set point°FWrite
AV515standby_cool_setpt_cStandby cooling set point (default 76)°FWrite
AV516standby_heat_setpt_cStandby heating set point (default 68)°FWrite
AV517eff_clg_setpt_cEffective cooling set point°FRead
AV518eff_htg_setpt_cEffective heating set point°FRead
AV521setpt_diff_cMinimum temperature between the heating and cooling setpoints (default 2)°FWrite
AV522setpt_span_cSpace temperature set point span (default 5)°FWrite
AV523temp_occ_timeAmount of time left in temporary occupancy only while in Temp Occm/secRead
AV524occ_man_valueCurrently selected occupancy valueRead
AV600econ_modeCurrently active Economizer modeRead
AV601econ_damp_posCurrent damper position determined by Economizer logic%Read
AV602atm_pres_cAtmospheric pressure from the BAS for enthalpy calculations (default 14.1)psiWrite
AV603elev_feet_cSite elevation from the BAS for enthalpy calculations (default 1000)ftWrite
AV604air_presCurrent atmospheric pressure value being used for enthalpy calculationspsiRead
AV605oat_adjust_cCalibration offset value for outdoor air temperature sensor (default 0)°FWrite
AV606oat_override_cBAS value for outdoor air temperature (used when BV 609 = BAS) (default 0)°FWrite
AV607oat_statCurrent usable outdoor air temperature value°FRead
AV608oah_adjust_cCalibration offset value for outdoor air humidity sensor (default 0)%rhWrite
AV609oah_override_cBAS value for outdoor air humidity (used when BV 611 = BAS) (default 0)%rhWrite
AV610oah_statCurrent usable outdoor air humidity value%rhRead
AV611out_enthCurrently calculated outdoor air enthalpy valueBtu/lbRead
AV612out_dewCurrently calculated outdoor air dew point value°FRead
AV613rat_adjust_cCalibration offset value for return air temperature sensor (default 0)°FWrite
AV614rat_override_cBAS value for return air temperature (used when BV 613 = BAS) (default 0)°FWrite
AV615rat_statCurrent usable return air temperature value°FRead
AV616rah_adjust_cCalibration offset value for return air humidity sensor (default 0)%rhWrite
AV617rah_override_cBAS value for return air humidity (used when BV 615 = BAS) (default 0)%rhWrite
AV618rah_statCurrent usable return air humidity value%rhRead
AV619ret_enthCurrently calculated return air enthalpy valueBtu/lbRead
AV620ret_dewCurrently calculated return air dew point value°FRead
AV630econ_av_cEconomizer operating mode, numeric (default 5) (default 5)Write
AV631db_setpt_cDry bulb set point for Economizer operation (default 63)°FWrite
AV632db_limit_cDry bulb limit for Economizer operation (default 75)°FWrite
AV633db_diff_cDry bulb differential for Economizer operation (default 2)°FWrite
AV634enth_setpt_cEnthalpy set point for Economizer operation (default 24)Btu/lbWrite
AV635enth_limit_cEnthalpy limit for Economizer operation (default 30)Btu/lbWrite
AV636enth_diff_cEnthalpy differential for Economizer operation (default 2)Btu/lbWrite
AV637ma_setpt_cMixed air set point for Economizer operation (default 53)°FWrite
AV638min_dmp_pos_cMinimum damper position for Economizer operation (default 30)%Write
AV639min_lat_lim_cMinimum leaving air temperature set point for Economizer operation (default 45)°FWrite
AV640min_oat_clg_cMinimum outdoor air temperature for mechanical cooling operation (default 40)°FWrite
AV641min_oat_vent_cMinimum outdoor temperature for ventilation operation (default 0)°FWrite
AV642max_dcv_pos_cMaximum damper position for demand controlled ventilation (default 40)%Write
AV643low_dcv_val_cLower DCV control value (at min/max damper position) (default 600)ppmWrite
AV644high_dcv_val_cUpper DCV control value (at min/max damper position) (default 1200)ppmWrite
AV645sam_time_cOutdoor air temperature sampling time for Economizer operation (default 60)secondsWrite
AV646dmp_cool_cMinimum damper position allowed for mechanical cooling operation with the Economizer active (default 75)%Write
AV647comp_up_time_cMinimum time required for upstaging with Economizer operation (default 120)secondsWrite
AV648comp_dn_time_cMaximum time required for upstaging with Economizer operation (default 120)secondsWrite
AV649na_time_cDamper adjustment time during neutral air operation (default 60)secondsWrite
BV100fan_operation_cSelects either cycled or continuous operation of the fan (default Active)WriteInactive=Cycled; Active=Continuous
BVmin101em_shutdown_cNetwork emergency shutdown command (default Inactive)WriteInactive=Normal Operation; Active=Shutdown
BV102es_statEmergency Shutdown status of SystemReadInactive=Normal; Active=Shutdown
BV103es_stat_aEmergency Shutdown status of ABC AReadInactive=Normal; Active=Shutdown
BV105load_shed_cIssues a load shed command to the unit (default Inactive)WriteInactive=Off; Active=On
BV106ls_stat_aLoad Shed status of ABC AReadInactive=Normal; Active=Load Shed
BV108y1_demStatus of the Y1 demand calculated by the internal PID logicReadInactive=Off; Active=On
BV109y2_demStatus of the Y2 demand calculated by the internal PID logicReadInactive=Off; Active=On
BV110network_y1_cBAS Y1 call (default Inactive)WriteInactive=Off; Active=On
BV111network_y2_cBAS Y2 call (default Inactive)WriteInactive=Off; Active=On
BV112network_w_cBAS W call (default Inactive)WriteInactive=Off; Active=On
BV113network_o_cBAS O call (default Inactive)WriteInactive=Off; Active=On
BV114network_g_cBAS G call (default Inactive)WriteInactive=Off; Active=On
BV115network_dh_cBAS DH call (default Inactive)WriteInactive=Off; Active=On
BV116eh1_override_cDirect BAS control of the ABC A EH1 output (default Inactive)WriteInactive=Off; Active=On
BV117eh2_override_cDirect BAS control of the ABC A EH2 output (default Inactive)WriteInactive=Off; Active=On
BV121y1_cmd_statStatus of the ABC A Y1 call from the UPCReadInactive=Off; Active=On
BV122y2_cmd_statStatus of the ABC A Y2 call from the UPCReadInactive=Off; Active=On
BV123w_cmd_statStatus of the ABC W call from the UPCReadInactive=Off; Active=On
BV124o_cmd_statStatus of the ABC O call from the UPCReadInactive=Heating; Active=Cooling
BV125g_cmd_statStatus of the ABC G call from the UPCReadInactive=Off; Active=On
BV126dh_cmd_statStatus of the ABC DH call from the UPCReadInactive=Off; Active=On
BV127manual_ecm_cInternal use; do not map to BAS (default Inactive)WriteInactive=Off; Active=On
BV128man_vs_pump_cInternal use; do not map to BAS (default Inactive)WriteInactive=Off; Active=On
BV129man_damp_cInternal use; do not map to BAS (default Inactive)WriteInactive=Off; Active=On
BVmin130alarm_reset_cAlarm reset: write On, then back to Off (default Inactive)WriteInactive=Off; Active=On
BV131alarm_reset_statCommanded status of the alarm reset commandReadInactive=Off; Active=On
BV132abc_comm_flt_aModbus link status between the ABC A and the UPCReadInactive=Normal Communication; Active=Communication Fault
BV133modbus_comm_aModbus link status between the ABC A and the UPCReadInactive=Normal Communication; Active=Communication Fault
BV136fp1_fault_aStatus of FP1 fault condition for circuit AReadInactive=Normal; Active=Fault
BV138filter_alm_reset_cReset the dirty filter alarm after the filter has been changed (default Inactive)WriteInactive=Off; Active=On
BV139dirty_filter_alarmStatus of the dirty filter alarmReadInactive=Normal; Active=Change Filter
BV140cond_stat_aStatus of the condensate input on ABC AReadInactive=Normal; Active=Alarm
BV141alarm_hdw_stat_aStatus of the ABC A Alarm outputReadInactive=Off; Active=On
BV142lock_hdw_stat_aStatus of the ABC A Lockout outputReadInactive=Normal; Active=Lockout
BV143lockout_stat_aLockout status of the circuit A systemReadInactive=Normal; Active=Alarm
BV200comp_stat_aStatus of the CC compressor output on ABC AReadInactive=Off; Active=On
BV201hi_comp_stat_aStatus of the CC2 compressor output on ABC AReadInactive=Off; Active=On
BV202rev_vlv_stat_aStatus of the reversing valve output on ABC AReadInactive=Heat; Active=Cool
BV203fan_stat_aStatus of the Fan relay output on ABC AReadInactive=Off; Active=On
BV204eh1_stat_aStatus of the EH1 output on ABC AReadInactive=Off; Active=On
BV205eh2_stat_aStatus of the EH2 output on ABC AReadInactive=Off; Active=On
BV206acc1_stat_aStatus of the ACC1 output on ABC AReadInactive=Off; Active=On
BV214fp1_lim_aFP1 limit temperature for ABC AReadInactive=15 Deg; Active=30 Deg
BV215fp2_lim_aFP2 limit temperature for ABC AReadInactive=15 Deg; Active=30 Deg
BV216rv_setup_aReversing valve setup for ABC AReadInactive=Cooling; Active=Heating
BV217sw_2_4_aPosition of SW2-4 on ABC A which configures the operation of ACC1ReadInactive=Off; Active=On
BV218sw_2_5_aPosition of SW2-5 on ABC A which configures the operation of ACC1ReadInactive=Off; Active=On
BV219comp_cap_aPosition of SW2-6 on ABC AReadInactive=Dual Capacity; Active=Single Capacity
BV220lockout_cfg_aPosition of SW2-7 on ABC AReadInactive=Pulsed; Active=Continuous
BV221reheat_cfg_aPosition of SW2-8 on ABC AReadInactive=Reheat; Active=Normal
BV222sw1_test_aStatus of the SW1 test button on ABC AReadInactive=Off; Active=On
BV232y1_hdw_aStatus of the physical Y1 input on ABC AReadInactive=Off; Active=On
BV233y2_hdw_aStatus of the physical Y2 input on ABC AReadInactive=Off; Active=On
BV234w_hdw_aStatus of the physical W input on ABC AReadInactive=Off; Active=On
BV235o_hdw_aStatus of the physical O input on ABC AReadInactive=Off; Active=On
BV236g_hdw_aStatus of the physical G input on ABC AReadInactive=Off; Active=On
BV237dh_hdw_aStatus of the physical DH input on ABC AReadInactive=Off; Active=On
BV238hp_hdw_aPhysical LP input on ABC A (as labelled in the source)ReadInactive=Open; Active=Closed
BV239lp_hdw_aPhysical HP input on ABC A (as labelled in the source)ReadInactive=Open; Active=Closed
BV240ls_hdw_aStatus of the physical LS input on ABC AReadInactive=Normal; Active=LoadShed
BV241es_hdw_aStatus of the physical ES input on ABC AReadInactive=Normal; Active=Shutdown
BV242abc_test_mode_aCurrent status of the test mode for ABC AReadInactive=Off; Active=On
BV300ddc_enable_cInternal use; do not map to BAS (default Active)WriteInactive=T-Stat; Active=UPC
BV301sys_commStatus of valid system communications with ABC controlsReadInactive=Off; Active=On
BV302eh1_mode_cOperation for ABC A EH1 output (default Inactive)WriteInactive=Aux_Heat; Active=Network_EH
BV303eh2_mode_cOperation for ABC A EH2 output (default Inactive)WriteInactive=Aux_Heat; Active=Network_EH
BV306brine_select_cWater or anti-freeze, for performance calculations (default Inactive)WriteInactive=Water; Active=Anti-Freeze
BV307dh_enable_cEnables/disables dehumidification (default Inactive)WriteInactive=DH Disabled; Active=DH Enabled
BV308dhw_enable_a_cEnables/disables DHW operation on circuit A (default Inactive)WriteInactive=Off; Active=On
BV310sw2_1_a_cSelects the position of SW2-1 on ABC A for override (default Active)WriteInactive=15 Deg; Active=30 Deg
BV311sw2_2_a_cSelects the position of SW2-2 on ABC A for override (default Active)WriteInactive=15 Deg; Active=30 Deg
BV312sw2_3_a_cSelects the position of SW2-3 on ABC A for override (default Active)WriteInactive=Cooling; Active=Heating
BV313sw2_4_a_cSelects the position of SW2-4 on ABC A for override (default Active)WriteInactive=Off; Active=On
BV314sw2_5_a_cSelects the position of SW2-5 on ABC A for override (default Active)WriteInactive=Off; Active=On
BV315sw2_6_a_cSelects the position of SW2-6 on ABC A for override (default Active)WriteInactive=Dual Capacity; Active=Single Capacity
BV316sw2_7_a_cSelects the position of SW2-7 on ABC A for override (default Active)WriteInactive=Pulsed; Active=Continuous
BV317sw2-8_a_cSelects the position of SW2-8 on ABC A for override (default Active)WriteInactive=Reheat; Active=Normal
BV318dip_sw_ovrd_ena_a_cEnables BAS dip switch overrides on ABC A (default Inactive)WriteInactive=Off; Active=On
BV330set_blwr_addr_cInternal use; do not map to BAS (default Inactive)WriteInactive=Off; Active=On
BV331clr_blwr_addr_cInternal use; do not map to BAS (default Inactive)WriteInactive=Off; Active=On
BV400test_mode_ena_cInternal use; do not map to BAS (default Inactive)WriteInactive=Off; Active=On
BV401fact_test_ena_cInternal use; do not map to BAS (default Inactive)WriteInactive=Off; Active=On
BV402clear_faults_cInternal use; do not map to BAS (default Inactive)WriteInactive=Off; Active=On
BV403dev_enable_cAdd communicating devices to the Aurora Control Boards (default Inactive)WriteInactive=Off; Active=On
BV500temp_selector_cSelects between wall sensor and BAS for space temperature value (default Inactive)WriteInactive=Sensor; Active=BAS
BV501valid_sensorCurrent status of having a valid space temperature valueReadInactive=Off; Active=On
BVmin502schedule_select_cSelects between the internal or external schedule (default Active)WriteInactive=Internal; Active=External
BV504occ_cmd_select_cOccupancy command selection between AV:509 & MSV:500 (default Inactive)WriteInactive=MSV; Active=AV
BV505occ_sensor_enable_cEnables or disables occupancy sensor connected to ABC O input (default Inactive)WriteInactive=Disabled; Active=Enabled
BV506occ_man_cmd_bv_cBAS occupancy signal (default Inactive)WriteInactive=Off; Active=On
BV507temp_occ_cEnables or disables temporary occupancy at zone sensors (default Active)WriteInactive=Enable; Active=Disable
BV508temp_occ_statTemporary occupancy statusReadInactive=Normal; Active=Temp Occ
BV509not_unoccupiedInternal use; do not map to BASReadInactive=Off; Active=On
BV510fan_occupiedInternal use; do not map to BASReadInactive=Off; Active=On
BV550archive_now_cForces UPC to Archive the current system settings and database values (default Inactive)WriteInactive=No; Active=Yes
BV600econ_on_cEconomizer available, from the BAS (slave mode) (default Inactive)WriteInactive=Off; Active=On
BV601econ_availCurrent availability of Economizer for free coolingReadInactive=Not Avail; Active=Available
BV602lvt_statusThe low outdoor temperature ventilation logic is activeReadInactive=Inactive; Active=Active
BV603dcv_statusDemand controlled ventilation logic is activeReadInactive=Inactive; Active=Active
BV604econ_statEconomizer operation is activeReadInactive=Off; Active=On
BV605low_latLow LAT logic is activeReadInactive=Off; Active=On
BV606y1_demandEconomizer logic is passing on a Y1 compressor demandReadInactive=Off; Active=On
BV607y2_demandEconomizer logic is passing on a Y2 compressor demandReadInactive=Off; Active=On
BV608pres_select_cSelects between atmospheric pressure and elevation for enthalpy calculations (default Inactive)WriteInactive=Pressure; Active=Elevation
BV609oat_select_cSelection value for OAT source (default Inactive)WriteInactive=Sensor; Active=BAS
BV610oat_validA valid OAT value is presentReadInactive=Off; Active=On
BV611oah_select_cSelection value for OAH source (default Inactive)WriteInactive=Sensor; Active=BAS
BV612oah_validA valid OAH value is presentReadInactive=Off; Active=On
BV613rat_select_cSelection value for RAT source (default Inactive)WriteInactive=Sensor; Active=BAS
BV614rat_validA valid RAT value is presentReadInactive=Off; Active=On
BV615rah_select_cSelection value for RAH source (default Inactive)WriteInactive=Sensor; Active=BAS
BV616rah_validA valid RAH value is presentReadInactive=Off; Active=On
BV620low_lat_pos_cSelects the minimum damper position for operation with low LAT conditions (default Active)WriteInactive=Min Position; Active=Closed
BV621no_dem_econ_cSelects operation of the Economizer with no heating or cooling demand present (default Active)WriteInactive=Min Position; Active=Neutral Air
BV622dem_ctrl_vent_cEnables or disables Demand Controlled Ventilation (default Inactive)WriteInactive=Disabled; Active=Enabled
BV623dcv_variable_cSelects the control variable for Demand Controlled Ventilation (default Inactive)WriteInactive=CO2; Active=VOC
MVmin100mode_msvOperating mode of the unitRead1=Standby; 2=Fan Only; 3=Cool Stage 1; 4=Cool Stage 2; 5=Hot Gas Reheat; 6=Heat Stage 1; 7=Heat Stage 2; 8=Emergency Heat; 9=Auxiliary Heat; 10=Emergency Shutdown; 11=Load Shed; 12=ABC Lockout; 13=Demand Ventilation; 14=Economizer Mode; 15=ABC Lockout; 16=Cooling W/Economizer; 17=Low LAT Mode; 18=ABC Lockout; 19=ABC Lockout; 20=Cooling W/Economizer
MV300clg_cfm_offset_msv_cDehumidification operation for ECM blower (default 4)Write1=Htg CFM = Clg CFM; 2=-5% CFM Clg; 3=-10% CFM Clg; 4=-15% CFM Clg; 5=+5% CFM Clg
MV301phase_select_cSelects the supply power phase (default 1)Write1=Single Phase; 2=Three Phase
MV302flow_meter_a_msv_cFlow meter option for circuit A (default 6)Write1=None; 2=3/4 Inch; 3=1 inch; 4=2 inch; 5=2 1/2 Inch; 6=1 1/4 Inch
MVmin500occ_man_msv_cSystem occupancy status (default 1)Write1=Occupied; 2=Unoccupied; 3=Temp Occ; 4=Standby
MV501eff_occ_msvCurrent system occupancy statusRead1=Occupied; 2=Unoccupied; 3=Temp Occ; 4=Standby; 5=Occupancy Sensor
MV502lockout_enum_msvInternal use; do not map to BASRead
MV600econ_msv_cEconomizer operating mode using multi state value (default 5)Write1=Econ Off; 2=Fixed Temp; 3=Diff Temp; 4=Fixed Enthalpy; 5=Diff Enthalpy; 6=Slave Mode

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aurora UPC, Single Compressor Rooftop Unit with Economizer and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer

How many BACnet points does the WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer have?

This list has 284 BACnet objects: 159 analog values, 117 binary values, 8 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer BACnet points are writable?

145 of the 284 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer BACnet documentation?

The source is UPC BACnet Points List For Single/Dual Compressor Rooftop Economizer (PL1250EW), revision 2018-09, published free by WaterFurnace at https://www.waterfurnace.com/literature/aurora/PL1250EW.pdf.

What are the minimum BACnet points to integrate the WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer?

Start with MV 500 occ_man_msv_c (Occupied/unoccupied/temp occ/standby command); BV 502 schedule_select_c (Must be External for BAS occupancy commands); BV 101 em_shutdown_c (Network emergency shutdown); AV 511 occ_clg_setpt_c (Occupied cooling setpoint); AV 512 occ_htg_setpt_c (Occupied heating setpoint); BV 130 alarm_reset_c (Reset manual-reset alarms (On, then back to Off)); AV 500 zone_temp (Space temperature (sensor or BAS override)); MV 100 mode_msv (Current operating mode); AV 119 alarm_enum (Combined alarm code (see alarm table)).

How do I enable BMS control of the WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer?

BV 502 schedule_select_c picks the internal schedule (Mon-Fri 7:30-17:00 EST) or external BAS commands; External is the listed default. Occupancy commands go to MSV 500, or to AV 509 after BV 504 is set to AV; BV 506 is a separate binary BAS occupancy signal. BV 101 em_shutdown_c shuts the unit down and BV 105 load_shed_c sheds the compressor.

Can the BMS supply sensor values to the WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer?

AV 502 zone_temp_ovrd_c replaces the zone sensor once BV 500 is set to BAS. Outdoor air temperature and humidity, and return air temperature and humidity, can come from the BAS on AV 606, 609, 614 and 617 when BV 609, 611, 613 and 615 are set to BAS. AV 602 (pressure) or AV 603 (elevation), chosen by BV 608, feed the enthalpy calculation. AV 504, 506 and 508 accept humidity, CO2 and VOC values.

How do I check these points on the real Aurora UPC, Single Compressor Rooftop Unit with Economizer?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WaterFurnace BACnet points lists

Source: UPC BACnet Points List For Single/Dual Compressor Rooftop Economizer · PL1250EW · rev. 2018-09. Object names, instances and units are reproduced as published; descriptions are our own.