Water-source heat pump controller · BACnet points list
WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump BACnet points list
Updated 28 October 2026
BACnet objects of the Aurora UPC on a dual-compressor water-source heat pump, software version 1.01. Each compressor circuit has its own Aurora Base Controller, so most status, sensor and dip-switch points come in A/B pairs. The UPC adds occupancy scheduling, setpoints, an optional water economizer and energy monitoring when AXB boards are fitted.
This page lists 348 BACnet objects for the WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump — 142 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.
- Manufacturer
- WaterFurnace
- Model
- Aurora UPC, Dual Compressor Water-Source Heat Pump
- Equipment
- Water-source heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 348 (142 writable)
- Transport
- BACnet MS/TP
- Firmware
- UPC software version 1.01
- Also known as
- PL1500EW, Aurora Universal Protocol Converter, Aurora UPC dual compressor
BMS integration notes: WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump
Keep BV 116 at External and command occupancy on MSV 9; the UPC then holds the occupied, unoccupied and standby setpoints (AV 100-105). Read MSV 8 for the operating mode and MSV 6/7 for each circuit's alarm code. BV 94-98 let the BAS send G, O, W and the two compressor calls directly.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 9 | occ_man_cmd_c | Occupied/unoccupied/temp occ/standby command | Write |
| BV 116 | schedule_selector_c | Must be External for BAS occupancy commands | Write |
| BV 61 | e_stop_c | Network emergency shutdown | Write |
| AV 100 | occ_clg_sp_c | Occupied cooling setpoint | Write |
| AV 101 | occ_htg_sp_c | Occupied heating setpoint | Write |
| BV 7 | alarm_reset_c | Reset manual-reset alarms (On, then back to Off) | Write |
| AV 133 | zone_temp_an | Space temperature (sensor or BAS override) | Read |
| MV 8 | mode_st | Current operating mode | Read |
| MV 6 | lockout_enumerated_st_a | Circuit A alarm code (see alarm table) | Read |
| MV 7 | lockout_enumerated_st_b | Circuit B alarm code (see alarm table) | Read |
Enable & remote start
BV 116 schedule_selector_c picks the internal schedule (Mon-Fri 7:30-17:00 EST) or external BAS commands; the sheet lists External as the default. Occupancy commands go to MSV 9, or to AV 92 after BV 101 is set to AV. BV 61 e_stop_c shuts the unit down. BV 94-98 send G, O, W, Y1 (ABC A) and Y2 (ABC B) calls directly.
Sensors & values from the BMS
AV 132 zone_temp_ovrd_c replaces the zone sensor once BV 136 zone_temp_selector_c is set to BAS. AV 75 humidity_c and AV 27 co2_c accept BAS values. AV 88 network_loop_temp_c feeds the economizer when BV 88 is set to Network. AV 90 oat_c is shown but not used in control.
Network setup
- Port 1a is the BAS port: EIA-485 for BACnet MS/TP (or N2), set by DIP switches, with baud 9600, 19.2k, 38.4k or 76.8k. It ships set to BACnet at 38,400 baud. (From AG1568EW, written for the single-compressor UPC.)
- Port 1a can instead be jumpered for ARC156 (BACnet over ARCNET at 156 kbps). A LonWorks plug-in card uses port 1b and disables port 1a.
- The MAC address is set on two rotary switches (tens and ones), 1 from the factory and 99 at most. The UPC only reads a new address after a power cycle.
- The device instance is built from the network number and the MAC: network 7000 with MAC 12 gives 7012.
- Wiring: 22 or 24 AWG shielded twisted pair, daisy-chained, polarity-sensitive (Net+, Net-, shield). About 30 devices and 2,000 ft per trunk; every MAC on a trunk must be unique.
Watch out for
- Dip switch overrides (BV 24-39) only pass to each ABC while BV 44 (ABC A) or BV 45 (ABC B) is enabled; record the physical switch settings first.
- Alarm reset: command BV 7 On, then back to Off.
- BV 12/13 (AXB enable) must match the hardware fitted, or nuisance alarms follow.
- Points shown with * in the source need an AXB board and its sensors; per-circuit pairs read from ABC A and ABC B.
- BV 93 network_dh_c only works with BV 41 set to enable dehumidification.
WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | abc_fw_beta_an_a | Internal use; do not map to BAS | Read | ||
| AV | 2 | abc_fw_beta_an_b | Internal use; do not map to BAS | Read | ||
| AV | 3 | abc_fw_rev_an_a | Internal use; do not map to BAS | Read | ||
| AV | 4 | abc_fw_rev_an_b | Internal use; do not map to BAS | Read | ||
| AV | 5 | abc_lat_an_a | Leaving air temperature on the ABC FP2 input | °F | Read | |
| AV | 6 | acc1_delay_c_a | Sets the time delay of the ACC-1 output on circuit A (default 90) | seconds | Write | |
| AV | 7 | acc1_delay_c_b | Sets the time delay of the ACC-1 output on circuit B (default 90) | seconds | Write | |
| AV | 8 | active_setpt_an | Set point that is controlling the call for the compressor | °F | Read | |
| AV | 9 | aux_current_an_a | Amp draw for the Auxiliary output on circuit A or B (needs AXB) | A | Read | |
| AV | 10 | aux_current_an_b | Amp draw for the Auxiliary output on circuit A or B (needs AXB) | A | Read | |
| AV | 11 | aux_output_pwr_an_a | Watt usage for Auxiliary output on circuit A or B (needs AXB) | W | Read | |
| AV | 12 | aux_output_pwr_an_b | Watt usage for Auxiliary output on circuit A or B (needs AXB) | W | Read | |
| AV | 13 | axb_spare_ana_input_an_a | Spare Analog output value located on the AXB for circuit A or B | °F | Read | |
| AV | 14 | axb_spare_ana_input_an_b | Spare Analog output value located on the AXB for circuit A or B | °F | Read | |
| AV | 15 | axb_pwm_high_c_a | AXB PWM output, high value (default 100) (default 100) | % | Write | |
| AV | 16 | axb_pwm_high_c_b | AXB PWM output, high value (default 100) (default 100) | % | Write | |
| AV | 17 | axb_lat_an_a | Leaving air temperature input on the AXB | °F | Read | |
| AV | 18 | axb_lat_an_b | Leaving air temperature input on the AXB | °F | Read | |
| AV | 19 | axb_pwm_low_c_a | AXB PWM output, low value (default 75) (default 75) | % | Write | |
| AV | 20 | axb_pwm_low_c_b | AXB PWM output, low value (default 75) (default 75) | % | Write | |
| AV | 21 | blower_off_adjust_c | Blower off delay after the compressor stops (cycled fan) (default 30) | seconds | Write | |
| AV | 22 | circuit_a_eer_an | EER calculation of circuit A or B (needs AXB) | Read | ||
| AV | 23 | circuit_b_eer_an | EER calculation of circuit A or B (needs AXB) | Read | ||
| AV | 24 | clg_subcooling_an_a | Subcooling calculation of circuit A or B (needs AXB) | °F | Read | |
| AV | 25 | clg_subcooling_an_b | Subcooling calculation of circuit A or B (needs AXB) | °F | Read | |
| AV | 26 | co2_an | CO2 value | ppm | Read | |
| AV | 27 | co2_c | BAS-written CO2 value (default 0) | ppm | Write | |
| AV | 28 | coax_temp_an_a | Refrigerant temperature at the Coax, circuit A | °F | Read | |
| AV | 29 | coax_temp_an_b | Refrigerant temperature at the Coax, circuit B | °F | Read | |
| AV | 30 | coefficient_of_performance_an_a | Calculated COP of circuit A or B (needs AXB) | Read | ||
| AV | 31 | coefficient_of_performance_an_b | Calculated COP of circuit A or B (needs AXB) | Read | ||
| AV | 32 | combined_he_hr_total_an | Combined heat of extraction/rejection, both circuits (needs AXB) | Btu/hr | Read | |
| AV | 33 | combined_total_capacity_an | Combined capacity of both circuits (needs AXB) | Btu/hr | Read | |
| AV | 34 | combined_total_power_an | Combined total power of both circuits (needs AXB) | W | Read | |
| AV | 35 | compressor_power_an_a | Compressor power of circuit A or B (needs AXB) | W | Read | |
| AV | 36 | compressor_power_an_b | Compressor power of circuit A or B (needs AXB) | W | Read | |
| AV | 37 | compressor_1_current_an_a | Compressor amps (L1 or L2), circuit A or B (needs AXB) | A | Read | |
| AV | 38 | compressor_2_current_an_b | Compressor amps (L1 or L2), circuit A or B (needs AXB) | A | Read | |
| AV | 39 | comp_1_current_an_a | Compressor amps (L1 or L2), circuit A or B (needs AXB) | A | Read | |
| AV | 40 | comp_2_current_an_b | Compressor amps (L1 or L2), circuit A or B | A | Read | |
| AV | 41 | condensor_temp_an_a | Condenser temperature for circuit A or B (needs AXB) | °F | Read | |
| AV | 42 | condensor_temp_an_b | Condenser temperature for circuit A or B (needs AXB) | °F | Read | |
| AV | 43 | control_voltage_an_a | Low voltage circuit value that is powering the ABC A and B | V | Read | |
| AV | 44 | control_voltage_an_b | Low voltage circuit value that is powering the ABC A and B | V | Read | |
| AV | 45 | dehum_diff_c | Dehumidify dead band (default 5) | %rh | Write | |
| AV | 46 | discharge_line_temp_an_a | Discharge line temperature for circuit A or B (needs AXB) | °F | Read | |
| AV | 47 | discharge_line_temp_an_b | Discharge line temperature for circuit A or B (needs AXB) | °F | Read | |
| AV | 48 | dischg_press_an_a | Discharge line pressure for circuit A or B (needs AXB) | psi | Read | |
| AV | 49 | dischg_press_an_b | Discharge line pressure for circuit A or B (needs AXB) | psi | Read | |
| AV | 50 | dom_hot_wtr_an_a | Internal use; do not map to BAS | °F | Read | |
| AV | 51 | dom_hot_wtr_an_b | Internal use; do not map to BAS | °F | Read | |
| AV | 52 | econo_sample_an | Sets economizer sample timer (needs AXB) (default 90) | seconds | Write | |
| AV | 53 | economizer_setpt_c | Economizer set point value (needs AXB) (default 45) | °F | Write | |
| AV | 54 | economizer_water_temp_an | Economizer water temperature that is being read (needs AXB) | °F | Read | |
| AV | 55 | eff_occ_an | Effective occupancy of the unit | Read | 1=Occupied; 2=Unoccupied; 3=Temp Occ; 4=Standby; 5=Occ Sensor | |
| AV | 56 | est_line_voltage_an_a | Estimated line voltage to the unit | V | Read | |
| AV | 57 | est_line_voltage_an_b | Estimated line voltage to the unit | V | Read | |
| AV | 58 | entering_wtr_temp_an_a | Value of the EWT input (needs AXB) | °F | Read | |
| AV | 59 | entering_wtr_temp_an_b | Value of the EWT input (needs AXB) | °F | Read | |
| AV | 60 | factory_dip_sw_ovrd_c_a | Internal use; do not map to BAS (default 32767) | Write | ||
| AV | 61 | factory_dip_sw_ovrd_c_b | Internal use; do not map to BAS (default 32767) | Write | ||
| AV | 62 | fan_current_an_a | Amp draw of the fan (needs AXB) | A | Read | |
| AV | 63 | fan_current_an_b | Amp draw of the fan (needs AXB) | A | Read | |
| AV | 64 | fan_power_an_a | Fan power for circuit A or B | W | Read | |
| AV | 65 | fan_power_an_b | Fan power for circuit A or B | W | Read | |
| AV | 66 | filter_alarm_hours_c | Filter alarm hours (default 1000) | Write | ||
| AV | 67 | filter_hours_an | Number of fan run hours since the last filter alarm reset | hr | Read | |
| AV | 68 | fp1_setpoint_an_a | FP1 freeze detection limit (coax temp) for circuit A | °F | Read | |
| AV | 69 | fp1_setpoint_an_b | FP1 freeze detection limit (coax temp) for circuit B | °F | Read | |
| AV | 70 | he_hr_an_a | Heat of rejection/extraction for circuit A or B (needs AXB) | Btu/hr | Read | |
| AV | 71 | he_hr_an_b | Heat of rejection/extraction for circuit A or B (needs AXB) | Btu/hr | Read | |
| AV | 72 | hgt_subcooling_an_a | Subcooling value for circuit A or B when operating in heating (needs AXB) | °F | Read | |
| AV | 73 | hgt_subcooling_an_b | Subcooling value for circuit A or B when operating in heating (needs AXB) | °F | Read | |
| AV | 74 | humidity_an | Humidity value of the zone sensor | %rh | Read | |
| AV | 75 | humidity_c | BAS override of the space humidity value if desired (default 0) | %rh | Write | |
| AV | 76 | liq_line_temp_an_a | Heating liquid line temperature for circuit A or B (needs AXB) | °F | Read | |
| AV | 77 | liq_line_temp_an_b | Heating liquid line temperature for circuit A or B (needs AXB) | °F | Read | |
| AV | 78 | lo_stat_reg_an_a | Internal use; do not map to BAS | Read | ||
| AV | 79 | lo_stat_reg_an_b | Internal use; do not map to BAS | Read | ||
| AV | 80 | lockouts_enumerated_an_a | Circuit A alarm code (see alarm table) | Read | 0=Normal; 1=E1 Input fault; 2=E2 High pressure; 3=E3 Low pressure; 4=E4 Freeze detection FP2; 5=E5 Freeze detection FP1; 6=E6 Loss of charge; 7=E7 Condensate overflow; 8=E8 Over/under voltage; 9=E9 Airflow monitoring (future); 10=E10 Compressor monitoring; 11=E11 FP1 sensor error; 12=E12 Refrigeration monitoring (future); 13=E13 Non-critical AXB sensor error (future); 14=E14 Critical AXB sensor error (future); 15=E15 Hot water limit; 16=E16 Variable speed pump; 18=E18 Non-critical comm error; 19=E19 Critical comm error; 20=E20 UPC-ABC critical comm error; 30=E30 Zone sensor loss of comm | |
| AV | 81 | lockouts_enumerated_an_b | Circuit B alarm code (see alarm table) | Read | 0=Normal; 1=E1 Input fault; 2=E2 High pressure; 3=E3 Low pressure; 4=E4 Freeze detection FP2; 5=E5 Freeze detection FP1; 6=E6 Loss of charge; 7=E7 Condensate overflow; 8=E8 Over/under voltage; 9=E9 Airflow monitoring (future); 10=E10 Compressor monitoring; 11=E11 FP1 sensor error; 12=E12 Refrigeration monitoring (future); 13=E13 Non-critical AXB sensor error (future); 14=E14 Critical AXB sensor error (future); 15=E15 Hot water limit; 16=E16 Variable speed pump; 18=E18 Non-critical comm error; 19=E19 Critical comm error; 20=E20 UPC-ABC critical comm error; 30=E30 Zone sensor loss of comm | |
| AV | 82 | loop_pressure_an_a | Loop pressure for circuit A or B (needs AXB) | psi | Read | |
| AV | 83 | loop_pressure_an_b | Loop pressure for circuit A or B (needs AXB) | psi | Read | |
| AV | 84 | lvg_wtr_temp_an_a | Value of the LWT Input on circuit A or B (needs AXB) | °F | Read | |
| AV | 85 | lvg_wtr_temp_an_b | Value of the LWT Input on circuit A or B (needs AXB) | °F | Read | |
| AV | 86 | measured_line_voltage_c | Calibrates the line voltage reading (default 230) | V | Write | |
| AV | 87 | mode_st_an | Current operating mode (numeric) | Read | 1=Standby; 2=Fan Only; 3=Cooling Stage 1; 4=Cooling Stage 2; 5=Hot Gas Reheat; 6=Heating Stage 1; 7=Heating Stage 2; 8=Emergency Heat; 9=Auxiliary Heat; 10=Emergency Shutdown; 11=Load Shed; 12=ABC A Lock-Out; 13=Test Mode; 14=Economizer Mode; 15=ABC B Lock-Out; 16=Full Cool W/Economizer; 17=Dehumidification Mode; 18=1/2 Capacity W/Lock-Out; 19=Full Lockout Condition; 20=Clg 1 W/Economizer | |
| AV | 88 | network_loop_temp_c | BAS-written loop temperature for the economizer (default 0) | °F | Write | |
| AV | 89 | oat_an | Outdoor air temperature if the BAS is sending a value to AV-90 | °F | Read | |
| AV | 90 | oat_c | BAS-written outdoor air temperature (not used in control) (default 0) | °F | Write | |
| AV | 91 | occ_dehum_setpt_c | Occupied dehumidify set point (default 53) | %rh | Write | |
| AV | 92 | occ_man_cmd_an_c | Occupancy command (used when BV 101 = AV) (default 1) | Write | ||
| AV | 93 | rem_setpt_span_c | Space temperature set point span (default 5) | °F | Write | |
| AV | 94 | sat_evap_temp_an_a | Saturated evaporator temperature for circuit A or B (needs AXB) | °F | Read | |
| AV | 95 | sat_evap_temp_an_b | Saturated evaporator temperature for circuit A or B (needs AXB) | °F | Read | |
| AV | 96 | clg_adj_an | Effective cooling setpoint adjust (same as sensor offset) | °F | Write | |
| AV | 97 | eff_clg_sp_an | Effective cooling set point | °F | Write | |
| AV | 98 | eff_htg_sp_an | Effective heating set point | °F | Write | |
| AV | 99 | htg_adj_an | Effective heating setpoint adjust (same as sensor offset) | °F | Write | |
| AVmin | 100 | occ_clg_sp_c | Occupied cooling set point | °F | Write | |
| AVmin | 101 | occ_htg_sp_c | Occupied heating set point | °F | Write | |
| AV | 102 | unocc_clg_sp_c | Unoccupied cooling set point | °F | Write | |
| AV | 103 | unocc_htg_sp_c | Unoccupied heating set point | °F | Write | |
| AV | 104 | standby_cool_c | Standby cooling set point (default 76) | °F | Write | |
| AV | 105 | standby_heat_c | Standby heating set point (default 68) | °F | Write | |
| AV | 106 | suction_press_an_a | Suction pressure of circuit A or B (needs AXB) | psi | Read | |
| AV | 107 | suction_press_an_b | Suction pressure of circuit A or B (needs AXB) | psi | Read | |
| AV | 108 | suct_temp_an_a | Suction temperature of circuit A or B (needs AXB) | °F | Read | |
| AV | 109 | suct_temp_an_b | Suction temperature of circuit A or B (needs AXB) | °F | Read | |
| AV | 110 | super_heat_an_a | Superheat of circuit A or B (needs AXB) | °F | Read | |
| AV | 111 | super_heat_an_b | Superheat of circuit A or B (needs AXB) | °F | Read | |
| AV | 112 | sw_part_no_an_a | Internal use; do not map to BAS | Read | ||
| AV | 113 | sw_part_no_an_b | Internal use; do not map to BAS | Read | ||
| AV | 114 | temp_occ_time_an | Amount of time left in temporary occupancy only while in Temp Occ | m/sec | Read | |
| AV | 115 | test_md_pwd_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 116 | total_capacity_an_a | Calculated value for circuit A or B's total capacity (needs AXB) | Btu/hr | Read | |
| AV | 117 | total_capacity_an_b | Calculated value for circuit A or B's total capacity (needs AXB) | Btu/hr | Read | |
| AV | 118 | total_power_an_a | Calculated total watt usage for circuit A or B (needs AXB) | W | Read | |
| AV | 119 | total_power_an_b | Calculated total watt usage for circuit A or B (needs AXB) | W | Read | |
| AV | 120 | total_amps_an_a | Calculated total amp draw for circuit A or B (needs AXB) | A | Read | |
| AV | 121 | total_amps_an_b | Calculated total amp draw for circuit A or B (needs AXB) | A | Read | |
| AV | 122 | tstat_ovrd_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 123 | universal_input_an_a | Raw count value of the universal input (needs AXB) | Read | ||
| AV | 124 | universal_input_an_b | Raw count value of the universal input (needs AXB) | Read | ||
| AV | 125 | unocc_dehum_setpt_c | (default 75) | %rh | Write | |
| AV | 126 | var_spd_pmp_output_an_a | Operating % of the output for circuit A or B (needs AXB) | % | Read | |
| AV | 127 | var_spd_pmp_output_an_b | Operating % of the output for circuit A or B (needs AXB) | % | Read | |
| AV | 128 | voc_an | Parts per million of volatile organic compounds in the space | ppm | Read | |
| AV | 129 | voc_c | BAS-written VOC value, for display only (default 0) | ppm | Write | |
| AV | 130 | water_flow_an_a | GPM flow rate of circuit A or B (needs AXB) | gpm | Read | |
| AV | 131 | water_flow_an_b | GPM flow rate of circuit A or B (needs AXB) | gpm | Read | |
| AV | 132 | zone_temp_ovrd_c | BAS override of zone temperature (default 0) | °F | Write | |
| AVmin | 133 | zone_temp_an | Zone Temp as read by the zone sensors | °F | Read | |
| AV | 134 | zone_temp_adj_c | Zone temperature calibration offset (default 0) | °F | Write | |
| AV | 135 | m409_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 136 | m417_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 137 | m421_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 138 | m453_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 139 | m449_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 140 | m445_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 141 | m433_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 142 | m429_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 143 | m425_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 144 | m488_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 145 | m494_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 146 | m495_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 147 | m496_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 148 | m497_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 149 | m498_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 150 | m441_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 151 | m500_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 152 | m501_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 154 | m555_c | Internal use; do not map to BAS (default 120) | Write | ||
| AV | 155 | m558_an | Internal use; do not map to BAS | Read | ||
| AV | 156 | m2006_1_an | Internal use; do not map to BAS | Read | ||
| AV | 157 | m557_c | Internal use; do not map to BAS (default 1) | seconds | Write | |
| AV | 158 | m563_c | Internal use; do not map to BAS (default 0) | seconds | Write | |
| AV | 159 | m567_c | Internal use; do not map to BAS (default 76) | seconds | Write | |
| AV | 160 | m560_an | Internal use; do not map to BAS | Read | ||
| AV | 161 | m2011_an | Internal use; do not map to BAS | Read | ||
| AV | 162 | m569_c | Internal use; do not map to BAS (default 120) | seconds | Write | |
| AV | 163 | m571_c | Internal use; do not map to BAS (default 0) | seconds | Write | |
| AV | 164 | m545_an | Internal use; do not map to BAS | Read | ||
| AV | 165 | m1999_an | Internal use; do not map to BAS | Read | ||
| AV | 166 | m535_an | Internal use; do not map to BAS | Read | ||
| AV | 167 | m2014_an | Internal use; do not map to BAS | Read | ||
| AV | 168 | m574_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 169 | m576_an | Internal use; do not map to BAS | Read | ||
| AV | 170 | m2015_an | Internal use; do not map to BAS | Read | ||
| AV | 171 | m579_c | Internal use; do not map to BAS (default 1) | Write | ||
| AV | 172 | m578_an | Internal use; do not map to BAS | Read | ||
| AV | 173 | m2024_an | Internal use; do not map to BAS | Read | ||
| AV | 174 | m582_an | Internal use; do not map to BAS | Read | ||
| AV | 175 | m2025_an | Internal use; do not map to BAS | Read | ||
| AV | 176 | m584_an | Internal use; do not map to BAS | Read | ||
| AV | 177 | m2029_an | Internal use; do not map to BAS | Read | ||
| AV | 178 | m586_an | Internal use; do not map to BAS | Read | ||
| AV | 179 | m2033_an | Internal use; do not map to BAS | Read | ||
| AV | 180 | m588_an | Internal use; do not map to BAS | Read | ||
| AV | 181 | m2037_an | Internal use; do not map to BAS | Read | ||
| AV | 182 | m590_an | Internal use; do not map to BAS | Read | ||
| AV | 183 | m2041_an | Internal use; do not map to BAS | Read | ||
| AV | 184 | m592_an | Internal use; do not map to BAS | Read | ||
| AV | 185 | m2045_an | Internal use; do not map to BAS | Read | ||
| AV | 186 | m594_an | Internal use; do not map to BAS | Read | ||
| AV | 187 | m2049_an | Internal use; do not map to BAS | Read | ||
| AV | 188 | m598_c | Internal use; do not map to BAS (default 32767) | Write | ||
| AV | 189 | m599_an | Internal use; do not map to BAS | Read | ||
| AV | 190 | m2055_an | Internal use; do not map to BAS | Read | ||
| AV | 191 | m596_c | Internal use; do not map to BAS (default 60) | seconds | Write | |
| AV | 192 | m547_an | Internal use; do not map to BAS | Read | ||
| AV | 193 | m2001_an | Internal use; do not map to BAS | Read | ||
| AV | 194 | r5_c | Internal use; do not map to BAS (default 240) | Write | ||
| AV | 195 | m549_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 196 | m551_c | Internal use; do not map to BAS (default 0) | Write | ||
| AV | 197 | m553_c | Internal use; do not map to BAS (default 120) | Write | ||
| AV | 198 | axb_ao1_c_a | BAS command for the analog output 1 on AXB "A" (default 0) | % | Write | |
| AV | 199 | axb_ao1_c_b | BAS command for the analog output 1 on AXB "B" (default 0) | % | Write | |
| BV | 1 | abc_modbus_comm_alarm_st_a | Modbus link status between the ABC A and the UPC | Read | Inactive=Communication Normal; Active=Communication Lost | |
| BV | 2 | abc_modbus_comm_alarm_st_b | Modbus link status between ABC B and the UPC | Read | Inactive=Communication Normal; Active=Communication Lost | |
| BV | 3 | acc1_st_a | Status of the ACC-1 output on ABC A | Read | Inactive=Off; Active=On | |
| BV | 4 | acc1_st_b | Status of the ACC-1 output ABC B | Read | Inactive=Off; Active=On | |
| BV | 5 | add_device_enable_c | Add communicating devices to the Aurora Control Boards (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 6 | alarm_reset_cmd_st | Commanded status of the alarm reset command | Read | Inactive=Off; Active=On | |
| BVmin | 7 | alarm_reset_c | BAS command for the alarm reset (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 8 | alm_rht_hdw_st_a | Status of the ABC A or B's alarm/reheat output | Read | Inactive=Off; Active=On | |
| BV | 9 | alm_rht_hdw_st_b | Status of the ABC A or B's alarm/reheat output | Read | Inactive=Off; Active=On | |
| BV | 10 | aux_heat_cmd_st | Status of the aux heat command | Read | Inactive=Off; Active=On | |
| BV | 11 | aux_heat_ena_c | EH-1 output control: network or aux heat PID (default Active) | Write | Inactive=Network EH; Active=Aux Heat | |
| BV | 12 | axb_enable_c_a | With BV 5, adds the AXB to ABC A or B (default Inactive) | Write | Inactive=No AXB; Active=AXB Present | |
| BV | 13 | axb_enable_c_b | With BV 5, adds the AXB to ABC A or B (default Inactive) | Write | Inactive=No AXB; Active=AXB Present | |
| BV | 14 | brine_selection_c | Water or anti-freeze, for performance calculations (default Inactive) | Write | Inactive=Water; Active=Anti-Freeze | |
| BV | 15 | cc_op_cfg_st_a | Internal use; do not map to BAS | Read | ||
| BV | 16 | cc_op_cfg_st_b | Internal use; do not map to BAS | Read | ||
| BV | 17 | clear_faults_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 18 | high_capacity_st_a | Internal use; do not map to BAS | Read | ||
| BV | 20 | compressor_st_a | Status of the ABC A or B's output for the compressor operation | Read | Inactive=Off; Active=On | |
| BV | 21 | compressor_st_b | Status of the ABC A or B's output for the compressor operation | Read | Inactive=Off; Active=On | |
| BV | 22 | condensate_st_a | Status of the condensate input on ABC A or B | Read | Inactive=Normal; Active=Alarm | |
| BV | 23 | condensate_st_b | Status of the condensate input on ABC A or B | Read | Inactive=Normal; Active=Alarm | |
| BV | 24 | sw2_1_c_a | Selects the position of dip SW2-1 on ABC A (default Inactive) | Write | Inactive=15°; Active=30° | |
| BV | 25 | sw2_1_c_b | Selects the position of dip SW2-1 on ABC B (default Active) | Write | Inactive=15°; Active=30° | |
| BV | 26 | sw2_2_c_a | Internal use; do not map to BAS (default Active) | Write | Inactive=Not Used; Active=Not Used | |
| BV | 27 | sw2_2_c_b | Internal use; do not map to BAS (default Active) | Write | Inactive=Not Used; Active=Not Used | |
| BV | 28 | sw2_3_c_a | Selects the position of dip SW1-3 on ABC A (default Active) | Write | Inactive=Cooling; Active=Heating | |
| BV | 29 | sw2_3_c_b | Selects the position of dip SW1-3 on ABC B (default Active) | Write | Inactive=Cooling; Active=Heating | |
| BV | 30 | sw2_4_c_a | No effect on ABC A ACC1 output | Write | ||
| BV | 31 | sw2_4_c_b | ACC1 mode for circuit B, with the other dip switch (see table) (default Active) | Write | ||
| BV | 32 | sw2_5_c_a | No effect on ABC A ACC1 output | Write | ||
| BV | 33 | sw2_5_c_b | ACC1 mode for circuit B, with the other dip switch (see table) (default Inactive) | Write | ||
| BV | 34 | sw2_6_c_a | Selects the position of dip SW1-6 on ABC A | Write | Inactive=Dual Capacity; Active=Single Capacity | |
| BV | 35 | sw2_6_c_b | Selects the position of dip SW1-6 on ABC B | Write | Inactive=Dual Capacity; Active=Single Capacity | |
| BV | 36 | sw2_7_c_a | Selects the position of dip SW1-7 (default Active) | Write | Inactive=Pulsed; Active=Continuous | |
| BV | 37 | sw2_7_c_b | Selects the position of dip SW1-7 (default Active) | Write | Inactive=Pulsed; Active=Continuous | |
| BV | 38 | sw2-8_c_a | Selects the position of dip SW1-8 | Write | Inactive=Reheat; Active=Normal | |
| BV | 39 | sw2-8_c_b | Selects the position of dip SW1-8 | Write | Inactive=Reheat; Active=Normal | |
| BV | 40 | dh_cmd_st | Status of the dehumidification command | Read | Inactive=Off; Active=On | |
| BV | 41 | dh_disable_c | Enables/disables dehumidification (default Inactive) | Write | Inactive=DH Disabled; Active=DH Enabled | |
| BV | 42 | dehum_hdw_st_a | Status of DH hardware input on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 43 | dehum_hdw_st_b | Status of DH hardware input on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 44 | dip_sw_ovrd_ena_c_a | Enables BAS dip switch overrides on ABC A (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 45 | dip_sw_ovrd_ena_c_b | Enables BAS dip switch overrides on ABC B (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 46 | dipswitchovrdrelease_c_a | Releases the dip switch overrides on ABC A (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 47 | dipswitchovrdrelease_c_b | Releases the dip switch overrides on ABC B (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 48 | dirty_filter_alarm_st | Alarm associated with the dirty filter timer | Read | Inactive=Normal; Active=Change Filter | |
| BV | 49 | economizer_ena_c | Enable the economizer control feature of the program (default Inactive) | Write | Inactive=Disabled; Active=Enabled | |
| BV | 50 | eh_1_st | Status of the E.H.-1 output on ABC A | Read | Inactive=Off; Active=On | |
| BV | 51 | eh_3_st | Status of the E.H.-3 output on ABC B | Read | Inactive=Off; Active=On | |
| BV | 52 | eh1_ovrd_c | BAS command for the E.H.-1 output relay on ABC A (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 53 | eh2_mode_c | Selects how the E.H.-2 output on ABC A is controlled (default Active) | Write | Inactive=Aux Heat; Active=Network EH | |
| BV | 54 | eh_2_st | Status of the E.H.-2 output on ABC A | Read | Inactive=Off; Active=On | |
| BV | 55 | eh_4_st | Status of the E.H.-4 output on ABC B | Read | Inactive=Off; Active=On | |
| BV | 56 | eh2_ovrd_c | BAS command for the E.H.-2 output relay on ABC A (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 57 | eh3_mode_c | Selects how the E.H.-3 output is controlled (default Active) | Write | Inactive=Aux Heat; Active=Network EH | |
| BV | 58 | eh3_ovrd_c | BAS command for the E.H.-3 output relay on ABC B (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 59 | eh4_mode_c | Selects how the E.H.-4 output is controlled (default Active) | Write | Inactive=Aux Heat; Active=Network EH | |
| BV | 60 | eh4_ovrd_c | BAS command for the E.H.-4 output relay on ABC B (default Inactive) | Write | Inactive=Off; Active=On | |
| BVmin | 61 | e_stop_c | Network emergency shutdown command (default Inactive) | Write | Inactive=Normal Operation; Active=Shutdown | |
| BV | 62 | es_hdw_st_a | Status of the emergency shutdown hardware input on ABC A or B | Read | Inactive=Normal; Active=Shutdown | |
| BV | 63 | es_hdw_st_b | Status of the emergency shutdown hardware input on ABC A or B | Read | Inactive=Normal; Active=Shutdown | |
| BV | 64 | factory_test_ena_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 65 | fan_operation_c | Selects either cycled or continuous operation of the fan (default Active) | Write | Inactive=Cycled; Active=Continuous | |
| BV | 66 | fan_st_a | Output status of the ABC A or B's fan output | Read | Inactive=Off; Active=On | |
| BV | 67 | fan_st_b | Output status of the ABC A or B's fan output | Read | Inactive=Off; Active=On | |
| BV | 68 | filter_alm_reset_c | Reset the dirty filter alarm after the filter has been changed (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 69 | fp1_lim_st_a | Current freeze detection set point of ABC A | Read | Inactive=15°; Active=30° | |
| BV | 70 | fp1_lim_st_b | Current freeze detection set point of ABC B | Read | Inactive=15°; Active=30° | |
| BV | 71 | g_cmd_st | Status of the UPC fan command to the unit | Read | Inactive=Off; Active=On | |
| BV | 72 | g_hdw_fan_proving_input_st_a | Status of the "G" hardware input on ABC A | Read | Inactive=Off; Active=On | |
| BV | 73 | g_hdw_fan_proving_input_st_b | Status of the "G" hardware input on ABC B | Read | Inactive=Off; Active=On | |
| BV | 74 | heat_cool_st | Reversing valve command the UPC sends to both ABCs | Read | Inactive=Heating; Active=Cooling | |
| BV | 75 | high_press_hdw_st_a | Status of the high pressure hardware input on ABC A and B | Read | Inactive=Open; Active=Closed | |
| BV | 76 | high_press_hdw_st_b | Status of the high pressure hardware input on ABC A and B | Read | Inactive=Open; Active=Closed | |
| BV | 77 | internal_external_scheduling_st | Schedule the unit is following (internal or external) | Read | Inactive=Internal; Active=External | |
| BV | 78 | lead_lag_ena_c | Enables/disables the compressor lead lag control (default Active) | Write | Inactive=Off; Active=On | |
| BV | 79 | load_shed_c | Enables/disables load shed (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 80 | loadshed_st_a | Status of the loadshed command from the UPC to ABC A and B | Read | Inactive=Normal; Active=Load Shed | |
| BV | 81 | loadshed_st_b | Status of the loadshed command from the UPC to ABC A and B | Read | Inactive=Normal; Active=Load Shed | |
| BV | 82 | lockout__st_a | Status of the alarm output on ABC A | Read | Inactive=Normal; Active=Lockout | |
| BV | 83 | lockout__st_b | Status of the alarm output on ABC B | Read | Inactive=Normal; Active=Lockout | |
| BV | 84 | lockout_cfg_st_a | Internal use; do not map to BAS | Read | ||
| BV | 85 | lockout_cfg_st_b | Internal use; do not map to BAS | Read | ||
| BV | 86 | lockout_hdw_st_a | Status of the alarm hardwired output relay for ABC A and B | Read | Inactive=Normal; Active=Lockout | |
| BV | 87 | lockout_hdw_st_b | Status of the alarm hardwired output relay for ABC A and B | Read | Inactive=Normal; Active=Lockout | |
| BV | 88 | loop_temp_select_c | Selects which temperature input is used for the economizer temperature (default Inactive) | Write | Inactive=Sensor; Active=Network | |
| BV | 89 | low_press_hdw_st_a | Status of the low pressure switch hardware input on ABC A and B | Read | Inactive=Open; Active=Closed | |
| BV | 90 | low_press_hdw_st_b | Status of the low pressure switch hardware input on ABC A and B | Read | Inactive=Open; Active=Closed | |
| BV | 91 | load_shed_hdw_st_a | Status of the load shed hardware input on ABC A and B | Read | Inactive=Normal; Active=Load Shed | |
| BV | 92 | load_shed_hdw_st_b | Status of the load shed hardware input on ABC A and B | Read | Inactive=Normal; Active=Load Shed | |
| BV | 93 | network_dh_c | Issues a dehumidification call to the unit (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 94 | network_g_c | BAS control of the (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 95 | network_o_c | BAS control of the (default Inactive) | Write | Inactive=Heating; Active=Cooling | |
| BV | 96 | network_w_c | BAS control of the EH-1 output on ABC A (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 97 | network_y1_c | BAS compressor call for (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 98 | network_y2_c | BAS compressor call for (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 99 | o_hdw_occ_sensor_input_st_a | Occupancy sensor input (O terminal), ABC A | Read | Inactive=Off; Active=On | |
| BV | 100 | o_hdw_occ_sensor_input_st_b | Occupancy sensor input (O terminal), ABC B | Read | Inactive=Off; Active=On | |
| BV | 101 | occ_cmd_av-msv_select_c | Selects which point (AV-92 or MSV-9) is used for commanding occupancy (default Inactive) | Write | Inactive=MSV; Active=AV | |
| BV | 102 | occ_sensor_enable_c | Enables the occupancy sensor on the ABC \"O\" input (default Inactive) | Write | Inactive=Disabled; Active=Enabled | |
| BV | 103 | pid_aux_hgt_st | Internal use; do not map to BAS | Read | ||
| BV | 104 | pid_y2_an | Internal use; do not map to BAS | Read | ||
| BV | 105 | r800_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 106 | r400_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 107 | r803_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 108 | r812_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 109 | r827_c_a | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 110 | reheat_cfg_st_a | Position of the D SW1-8 on ABC A | Read | Inactive=Reheat; Active=Normal | |
| BV | 111 | reheat_cfg_st_b | Position of the D SW1-8 on ABC B | Read | Inactive=Reheat; Active=Normal | |
| BV | 112 | rev_vlv_st_a | Status of both the reversing valve outputs on both ABC control boards | Read | Inactive=Heat; Active=Cool | |
| BV | 113 | rev_vlv_st_b | Status of both the reversing valve outputs on both ABC control boards | Read | Inactive=Heat; Active=Cool | |
| BV | 114 | rv_setup_st_a | Default position of the reversing valve | Read | Inactive=Cooling; Active=Heating | |
| BV | 115 | rv_setup_st_b | Default position of the reversing valve | Read | Inactive=Cooling; Active=Heating | |
| BVmin | 116 | schedule_selector_c | Selects between the internal or external schedule (default Active) | Write | Inactive=Internal; Active=External | |
| BV | 117 | sw1_test_cfg_st_a | Status of the SW1 configuration button on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 118 | sw1_test_cfg_st_b | Status of the SW1 configuration button on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 119 | sw_2_4_st_a | Status of the SW2-4 dipswitch | Read | ||
| BV | 120 | sw_2_4_st_b | Status of the SW2-4 dipswitch | Read | ||
| BV | 121 | sw_2_5_st_a | Status of the SW2-5 dipswitch | Read | ||
| BV | 122 | sw_2_5_st_b | Status of the SW2-5 dipswitch | Read | ||
| BV | 123 | temp_occ_dis_c | Disable temporary occupancy capabilities (default Active) | Write | Inactive=Disabled; Active=Enabled | |
| BV | 124 | temp_occ_st | Status of the temporary occupancy input | Read | Inactive=Normal; Active=Temp Occ | |
| BV | 125 | test_mode_ena_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 126 | test_mode_hdw_st_a | Internal use; do not map to BAS | Read | ||
| BV | 127 | test_mode_hdw_st_b | Internal use; do not map to BAS | Read | ||
| BV | 128 | w_hdw_dirty_filter_input_st_a | Status of the "W" hardware input on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 129 | w_hdw_dirty_filter_input_st_b | Status of the "W" hardware input on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 130 | y1_cmd_st | Status of the "Y1" command to ABC A from the UPC | Read | Inactive=Off; Active=On | |
| BV | 131 | y1_hdw_comp_proving_input_st_a | Status of the "Y1" hardware input on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 132 | y1_hdw_comp_proving_input_st_b | Status of the "Y1" hardware input on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 133 | y2_cmd_st | Status of the "Y2" command to the ABC A from the UPC | Read | Inactive=Off; Active=On | |
| BV | 134 | y2_hdw_vlv_end_sw_input_st_a | Status of the "Y2" hardware input on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 135 | y2_hdw_vlv_end_sw_input_st_b | Status of the "Y2" hardware input on ABC A or B | Read | Inactive=Off; Active=On | |
| BV | 136 | zone_temp_selector_c | Selects which zone temp input to operate from (default Inactive) | Write | Inactive=Sensor; Active=BAS | |
| BV | 137 | r10400_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 138 | r10800_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 139 | r10812_c | Internal use; do not map to BAS (default Inactive) | Write | ||
| BV | 140 | Archive_Now_c | Force the UPC to archive the current configuration (default Inactive) | Write | Inactive=Off; Active=On | |
| MV | 1 | blower_type_select_c | Internal use; do not map to BAS (default 1) | Write | ||
| MV | 2 | effect_occup_st | Effective occupancy of the unit | Read | 1=Occupied; 2=Unoccupied; 3=Temp Occ; 4=Standby | |
| MV | 3 | energy_monitor_select_c_a | Selects a method of energy monitoring (needs AXB) (default 1) | Write | 1=Off; 2=Compressor Monitoring; 3=Energy Monitoring | |
| MV | 4 | energy_monitor_select_c_b | Selects a method of energy monitoring (needs AXB) (default 1) | Write | 1=Off; 2=Compressor Monitoring; 3=Energy Monitoring | |
| MV | 5 | flow_meter_select_c_a | Selects the size of the flow meter (needs AXB) (default 1) | Write | 1=None; 2=Small 3/4"; 3=Large 1" | |
| MVmin | 6 | lockout_enumerated_st_a | Alarm code for the ABC (see alarm table) | Read | 1=Normal; 2=E1 Input fault; 3=E2 High pressure; 4=E3 Low pressure; 5=E4 Freeze detection FP2; 6=E5 Freeze detection FP1; 7=E6 Loss of charge; 8=E7 Condensate overflow; 9=E8 Over/under voltage; 10=E9 Airflow monitoring (future); 11=E10 Compressor monitoring; 12=E11 FP1 sensor error; 13=E12 Refrigeration monitoring (future); 14=E13 Non-critical AXB sensor error (future); 15=E14 Critical AXB sensor error (future); 16=E15 Hot water limit; 17=E16 Variable speed pump; 18=E30 Zone sensor loss of comm; 19=E18 Non-critical comm error; 20=E19 Critical comm error or E20 UPC-ABC critical comm error | |
| MVmin | 7 | lockout_enumerated_st_b | Alarm code for the ABC (see alarm table) | Read | 1=Normal; 2=E1 Input fault; 3=E2 High pressure; 4=E3 Low pressure; 5=E4 Freeze detection FP2; 6=E5 Freeze detection FP1; 7=E6 Loss of charge; 8=E7 Condensate overflow; 9=E8 Over/under voltage; 10=E9 Airflow monitoring (future); 11=E10 Compressor monitoring; 12=E11 FP1 sensor error; 13=E12 Refrigeration monitoring (future); 14=E13 Non-critical AXB sensor error (future); 15=E14 Critical AXB sensor error (future); 16=E15 Hot water limit; 17=E16 Variable speed pump; 18=E30 Zone sensor loss of comm; 19=E18 Non-critical comm error; 20=E19 Critical comm error or E20 UPC-ABC critical comm error | |
| MVmin | 8 | mode_st | Current operating mode of the unit | Read | 1=Standby; 2=Fan Only; 3=Cooling Stage 1; 4=Cooling Stage 2; 5=Hot Gas Reheat; 6=Heating Stage 1; 7=Heating Stage 2; 8=Emergency Heat; 9=Auxiliary Heat; 10=Emergency Shutdown; 11=Load Shed; 12=ABC A Lock-Out; 13=Test Mode; 14=Economizer Mode; 15=ABC B Lock-Out; 16=Full Cool W/Economizer; 17=Dehumidification Mode; 18=1/2 Capacity W/Lock-Out; 19=Full Lockout Condition; 20=Clg 1 W/Economizer | |
| MVmin | 9 | occ_man_cmd_c | BAS command for the units occupancy (default 1) | Write | 1=Occupied; 2=Unoccupied; 3=Temp Occ; 4=Standby; 5=Occ Sensor | |
| MV | 10 | phase_selection_c | Selects the supply power phase (needs AXB) (default 1) | Write | 1=Single Phase; 2=Three Phase | |
| MV | 11 | flow_meter_select_c_b | Selects the size of the flow meter (needs AXB) (default 1) | Write | 1=None; 2=Small 3/4"; 3=Large 1" |
No points match these filters.
Integration notes
- Object names are the sheet's reference names; several display names are just 'Set point'.
- Many points are marked 'do not map' in the source and are listed only for completeness.
- AV 153 and BV 19 are not in the source.
- The AV and MSV alarm points use different numbering: the AV value equals the E-code, the MSV value is one higher.
- Transport and network settings come from the Aurora UPC Application and Troubleshooting Guide (AG1568EW), which is written for the single-compressor UPC.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aurora UPC, Dual Compressor Water-Source Heat Pump and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump
How many BACnet points does the WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump have?
This list has 348 BACnet objects: 198 analog values, 139 binary values, 11 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump BACnet points are writable?
142 of the 348 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump BACnet documentation?
The source is Aurora UPC BACnet Points List For Dual Compressor WSHP (PL1500EW), revision 2016-10, published free by WaterFurnace at https://www.waterfurnace.com/literature/aurora/pl1500ew.pdf.
What are the minimum BACnet points to integrate the WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump?
Start with MV 9 occ_man_cmd_c (Occupied/unoccupied/temp occ/standby command); BV 116 schedule_selector_c (Must be External for BAS occupancy commands); BV 61 e_stop_c (Network emergency shutdown); AV 100 occ_clg_sp_c (Occupied cooling setpoint); AV 101 occ_htg_sp_c (Occupied heating setpoint); BV 7 alarm_reset_c (Reset manual-reset alarms (On, then back to Off)); AV 133 zone_temp_an (Space temperature (sensor or BAS override)); MV 8 mode_st (Current operating mode); MV 6 lockout_enumerated_st_a (Circuit A alarm code (see alarm table)); MV 7 lockout_enumerated_st_b (Circuit B alarm code (see alarm table)).
How do I enable BMS control of the WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump?
BV 116 schedule_selector_c picks the internal schedule (Mon-Fri 7:30-17:00 EST) or external BAS commands; the sheet lists External as the default. Occupancy commands go to MSV 9, or to AV 92 after BV 101 is set to AV. BV 61 e_stop_c shuts the unit down. BV 94-98 send G, O, W, Y1 (ABC A) and Y2 (ABC B) calls directly.
Can the BMS supply sensor values to the WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump?
AV 132 zone_temp_ovrd_c replaces the zone sensor once BV 136 zone_temp_selector_c is set to BAS. AV 75 humidity_c and AV 27 co2_c accept BAS values. AV 88 network_loop_temp_c feeds the economizer when BV 88 is set to Network. AV 90 oat_c is shown but not used in control.
How do I check these points on the real Aurora UPC, Dual Compressor Water-Source Heat Pump?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More WaterFurnace BACnet points lists
- Water-to-water heat pump controller
WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps
WaterFurnace NXW and SKW dual-scroll water-to-water heat pumps (including header rack arrangements) with the Aurora HydroLink controller.
Also known as: PL2500EW, HydroLink, NXW, SKW, WCHDM, HYDWWB01 - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Dual Compressor Rooftop Unit with Economizer
WaterFurnace dual-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer
WaterFurnace single-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump
WaterFurnace single-compressor water-to-air heat pumps with the Aurora controls and the Aurora UPC protocol converter.
Also known as: AG1569EW, Aurora Universal Protocol Converter, Aurora UPC, UPCSWASTD01-01 - Water-source heat pump controller
WaterFurnace Aurora UPC, Variable Speed Water-Source Heat Pump
WaterFurnace variable speed water-to-air heat pumps with Aurora controls and the Aurora UPC.
Also known as: PL1700EW, Aurora Universal Protocol Converter, Aurora UPC variable speed - Water-source heat pump controller
WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace commercial dual-compressor water-to-air heat pumps fitted with the FX10 DDC controller.
Also known as: PRODCWA-05, PRODCWA, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Envision single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWWE-01, PROSSWWE, Envision Water-to-Water, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton
WaterFurnace Envision 1 to 6 ton water-to-air heat pumps with the DDC controller option.
Also known as: Envision BACnet Variables, Envision BACnet Variables with BI, Envision 1-6 Ton - Water-to-water heat pump / reversible chiller controller
WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)
WaterFurnace dual-compressor reversible chiller (water-to-water) heat pumps with the FX10 controller.
Also known as: PRODCWWE-06B, PRODCWWE-07B, PRODCWWE-08B, PRODCWWE - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace single-compressor water-to-air heat pumps without hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PROFXENV-00, PROFXENV, Envision FX10, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace single-compressor water-to-air heat pumps with hot gas reheat and the FX10 DDC controller.
Also known as: PROFXENV-RH-00, PROFXENV-RH, Envision hot gas reheat, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec dual-compressor water-to-water heat pumps with the FX10 DDC controller and expansion board.
Also known as: PRODCWW-02, PRODCWW, Versatec Dual Compressor, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Versatec Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWW-03, PROSSWW, Versatec Water-to-Water, WaterFurnace FX10
Source: Aurora UPC BACnet Points List For Dual Compressor WSHP · PL1500EW · rev. 2016-10. Object names, instances and units are reproduced as published; descriptions are our own.