Water-to-water heat pump controller · BACnet points list

WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps BACnet points list

Updated 28 October 2026

Short answer

BACnet objects of the Aurora HydroLink controller for NXW/SKW dual-compressor water-to-water heat pumps, software version 1.03. It covers setpoint, aquastat or network control of both compressors, load and source water temperatures and limits, refrigerant data per compressor, and header rack valve and loop control. Each point is marked for the configurations it applies to.

This page lists 213 BACnet objects for the WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps — 118 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.

Manufacturer
WaterFurnace
Model
Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps
Equipment
Water-to-water heat pump controller
Equipment type
Heat pumps
BACnet objects
213 (118 writable)
Transport
—
Firmware
HydroLink software version 1.03
Also known as
PL2500EW, HydroLink, NXW, SKW, WCHDM, HYDWWB01
Source document
Aurora HydroLink BACnet Points List For NXW/SKW · PL2500EW · rev. 2018-02
Download CSV 213 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps

Integration in brief

For units without a header rack, pick the control method on MSV 2 (aquastat, setpoint, network or setpoint with enable). In setpoint mode the HydroLink holds AV 22/23 against the input chosen on MSV 3; in network mode the BAS calls compressor A on BV 35 and B on BV 34. BV 37 must stay Enabled, and the BAS should set BV 36 to Network while it has control.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 37SystemEnable_cSystem enable; compressors stay off when DisabledCommand
BV 36NetworkControl_cSet to Network while the BAS has controlCommand
BV 2EmShutdown_cNetwork emergency shutdownCommand
BV 1Mode_cCool or heat (non-header-rack units)Command
AV 22CoolingSetpoint_cCooling setpoint, setpoint control modeCommand
AV 23HeatingSetpoint_cHeating setpoint, setpoint control modeCommand
BV 33AlarmReset_cAlarm reset; return to Normal after the lockout clearsCommand
MV 1UnitMode_stCurrent operating modeRead
AV 1ControlTemp_stControl temperature (input chosen on MSV 3)Read
MV 0SystemStatus_stOverall status: normal, alarm, shutdown, load shed...Read

Enable & remote start

BV 37 SystemEnable_c (default Enabled) must be Enabled, or the compressor outputs stay off except under manual override. The BAS should set BV 36 NetworkControl_c to Network when it takes control; many local commands and settings then stop working. With MSV 2 = 3 (Network), BV 35 and BV 34 call compressors A and B; BV 1 picks cool or heat. BV 2 EmShutdown_c forces an emergency shutdown.

Sensors & values from the BMS

AV 62 NetworkTemperature_c is the BAS-supplied control temperature for setpoint control on a network temperature (MSV 3 option 4, which the sheet labels AV 12). Header rack units take BAS cold, hot and geo loop temperatures on AV 506-508; values written to AV 510-515 take priority over the measured header temperatures. BV 503 switches the geothermal loop temperatures to network values.

Watch out for

WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

213 of 213 shown
Type
AnalogBinaryMulti-state
Access
Show
WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps BACnet Points List
DescriptionStates
AV0ActiveTempSetpt_stActive setpoint value for control logic°FRead
AVmin1ControlTemp_stSelected temperature value for setpoint control°FRead
AV2AXBA_HotWaterTemp_stHWT input on AXB-A, free for field use°FRead
AV3CompACurrentT1_stCompressor A T1 currentARead
AV4CompACurrentT2_stCompressor A T2 currentARead
AV5CompADischPressure_stCompressor A discharge pressurepsigRead
AV6CompASuctPressure_stCompressor A suction pressurepsigRead
AV7SourceWaterFlow_stSource heat exchanger water flow rategal/minRead
AV8SrcLvgWaterTemp_stSource heat exchanger leaving water temperature°FRead
AV9SrcEntWaterTemp_stSource heat exchanger entering water temperature°FRead
AV10AXBA_LvgAirTempInput_stLeaving air temperature input on AXB-A, free for field use°FRead
AV11CompASuctLineTemp_stCompressor A suction line temperature°FRead
AV12RemoteTempInput_stHWT input on AXB-B, remote temperature control on some configurations°FRead
AV13CompBCurrentT1_stCompressor B T1 currentARead
AV14CompBCurrentT2_stCompressor B T2 currentARead
AV15CompBDischPressure_stCompressor B discharge pressurepsigRead
AV16CompBSuctPressure_stCompressor B suction pressurepsigRead
AV17LoadWaterFlow_stLoad heat exchanger water flow rategal/minRead
AV18LoadLvgWaterTemp_stLoad heat exchanger leaving water temperature°FRead
AV19LoadEntWaterTemp_stLoad heat exchanger entering water temperature°FRead
AV20AXBB_LvgAirTemp_stLeaving air temperature input on AXB-B, free for field use°FRead
AV21CompBSuctLineTemp_stCompressor B suction line temperature°FRead
AVmin22CoolingSetpoint_cCooling set point used for set point control mode (default 50°F)°FCommand
AVmin23HeatingSetpoint_cHeating set point used for set point control mode (default 80°F)°FCommand
AV24PIDExecuteTime_cPID execution time used for set point control mode (default 15 sec)secCommand
AV25CoolingDifferential_cDistance from cooling setpoint where the lead compressor starts (default 2.5 Δ°F)Δ°FCommand
AV26HeatingDifferential_cDistance from heating setpoint where the lead compressor startsΔ°FCommand
AV27DervConst_cPID Derivative used for set point control mode (default 0)Command
AV28PropConst_cPID Proportional constant used for set point control mode (default 8)Command
AV29IntConst_cPID Integral constant used for set point control mode (default 0.2)Command
AV30RemoteTempSensorOffset_cCalibration offset for the remote temperature sensor (default 0 Δ°F)Δ°FCommand
AV31LoadLvgWaterHighTempFaultLimit_cLoad leaving high water temperature fault limit (default 200°F)°FCommand
AV32LoadEntWaterCalib_cCalibration offset for the entering load water temperature sensor (default 0 Δ°F)Δ°FCommand
AV33LoadEntWaterLowTempFaultLimit_cLoad entering low water temperature fault limit (default 0°F)°FCommand
AV34LoadEntWaterHighTempFaultLimit_cLoad entering high water temperature fault limit (default 200°F)°FCommand
AV35LoadLeavingWaterCalib_cCalibration offset for the leaving load water temperature sensor (default 0 Δ°F)Δ°FCommand
AV36LoadLvgWaterLowTempFaultLimit_cLoad leaving low water temperature fault limit (default 0°F)°FCommand
AV37LoadLWTLowAlarmLimit_cLoad leaving low water temperature alarm limit (default 0°F)°FCommand
AV38LoadEWTHighAlarmLimit_cLoad entering high water temperature alarm limit (default 200°F)°FCommand
AV39LoadEWTLowAlarmLimit_cLoad entering low water temperature alarm limit (default 0°F)°FCommand
AV40LoadLWTHighAlarmLimit_cLoad leaving high water temperature alarm limit (default 200°F)°FCommand
AV41SrcLvgWaterHighTempFaultLimit_cSource leaving high water temperature fault limit (default 200°F)°FCommand
AV42SrcEntWaterCalib_cCalibration offset for the entering source water temperature sensor (default 0 Δ°F)Δ°FCommand
AV43SrcEntWaterLowTempFaultLimit_cSource entering low water temperature fault limit (default 0°F)°FCommand
AV44SrcEntWaterHighTempFaultLimit_cSource entering high water temperature fault limit (default 200°F)°FCommand
AV45SrcLeavingWaterCalib_cCalibration offset for the leaving source water temperature sensor (default 0 Δ°F)Δ°FCommand
AV46SrcLvgWaterLowTempFaultLimit_cSource leaving low water temperature fault limit (default 0°F)°FCommand
AV47SrcLWTLowAlarmLimit_cSource leaving low water temperature alarm limit (default 0°F)°FCommand
AV48SrcEWTHighAlarmLimit_cSource entering high water temperature alarm limit (default 200°F)°FCommand
AV49SrcEWTLowAlarmLimit_cSource entering low water temperature alarm limit (default 0°F)°FCommand
AV50SrcLWTHighAlarmLimit_cSource leaving high water temperature alarm limit (default 200°F)°FCommand
AV51SlowValveTimer_cDelay for water valves to open before compressor start (default 60 sec)secCommand
AV52CompPowerFactorAdjust_cAdjustment of the compressor power factor (default 0.88)Command
AV53MeasuredLineVoltageCal_cCalibrates the line voltage calculation (default 480 V)VCommand
AV54ABCBLockoutStatusAna_stMost recent fault code, compressor BRead
AV55ABCALockoutStatusAna_stMost recent fault code, compressor ARead
AV56ABCA_FP2_stCompressor A FP2 temperature value°FRead
AV57ABCA_FP1_stCompressor A FP1 temperature value°FRead
AV58ABCB_FP2_stCompressor B FP2 temperature value°FRead
AV59ABCB_FP1_stCompressor B FP1 temperature value°FRead
AV60FP2LimitOverride_cFP2 limit override (15-30 F) when ABC DIP-2 is set to 15 (default -0.1°F)°FCommand
AV61FP1LimitOverride_cFP1 limit override (15-30 F) when ABC DIP-1 is set to 15 (default -0.1°F)°FCommand
AV62NetworkTemperature_cBAS temperature for setpoint control on network temperature°FCommand
AV63CompressorHoursA_stCompressor A operating hourshrRead
AV64SaturatedEvapTempA_stCompressor A saturated evaporator temperature°FRead
AV65SaturatedCondTempA_stCompressor A saturated condenser temperature°FRead
AV66SuperheatA_stCompressor A superheat value°FRead
AV67SubcoolingA_stCompressor A subcooling value°FRead
AV68EEVPositionA_stCompressor A EEV position%Read
AV69CompressorHoursB_stCompressor B operating hourshrRead
AV70SaturatedEvapTempB_stCompressor B saturated evaporator temperature°FRead
AV71SaturatedCondTempB_stCompressor B saturated condenser temperature°FRead
AV72SuperheatB_stCompressor B superheat value°FRead
AV73SubcoolingB_stCompressor B subcooling value°FRead
AV74EEVPositionB_stCompressor B EEV position%Read
AV500ColdWaterSP_cCold water setpoint for header rack applications (default 50°F)°FCommand
AV501HotWaterSP_cHot water setpoint for header rack applications (default 80°F)°FCommand
AV502ColdDeltaOn_cOffset above cold water setpoint that starts cooling (default 3 Δ°F)Δ°FCommand
AV503ColdDeltaOff_cOffset below cold water setpoint that stops cooling (default 3 Δ°F)Δ°FCommand
AV504HotDeltaOn_cOffset from hot water setpoint that starts heating (default 3 Δ°F)Δ°FCommand
AV505HotDeltaOff_cOffset above hot water setpoint that stops heating (default 3 Δ°F)Δ°FCommand
AV506CW_NetworkTemp_cBAS cold water temperature for network setpoint control (header rack)°FCommand
AV507HW_NetworkTemp_cBAS hot water temperature for network setpoint control (header rack)°FCommand
AV508Geo_NetworkTemp_cBAS geothermal loop temperature (header rack)°FCommand
AV509UnitOffsetTemp_cGlobal offset of all header rack on/off points (default 0°F)°FCommand
AV510NetColdInTemp_cBAS cold water in temperature; overrides the sensor (header rack)°FCommand
AV511NetColdOutTemp_cBAS cold water out temperature; overrides the sensor (header rack)°FCommand
AV512NetHotInTemp_cBAS hot water in temperature; overrides the sensor (header rack)°FCommand
AV513NetHotOutTemp_cBAS hot water out temperature; overrides the sensor (header rack)°FCommand
AV514NetGeoInTemp_cBAS geo water in temperature; overrides the sensor (header rack)°FCommand
AV515NetGeoOutTemp_cBAS geo water out temperature; overrides the sensor (header rack)°FCommand
AV516MaxHotBypass_cMaximum open position for hot loop bypass valve (default 100%)%Command
AV517MaxColdBypass_cMaximum open position for cold loop bypass valve (default 100%)%Command
AV518MaxGeoBypass_cMaximum open position for geo loop bypass valve (default 100%)%Command
AV519BypassValveOffset_cValve % closed before its bypass valve starts to open (default 30%)%Command
AV520MinLoadValvePos_cMinimum position of the load control valves (default 10%)%Command
AV521MinSourceValvePos_cMinimum position of the source control valves (default 10%)%Command
AV522NetColdBypass_cCold bypass valve position under network control (BV 501 Active)%Command
AV523NetHotBypass_cHot bypass valve position under network control (BV 501 Active)%Command
AV524NetGeoBypass_cGeo bypass valve position under network control (BV 501 Active)%Command
AV525Y1ActiveY2Time_cTime the first compressor must run before the second may start (default 300 sec)secCommand
AV526Y2ActiveCapacity_cPID demand % at which the second compressor may start (default 50%)%Command
AV527Y2ActiveOffset_cDemand % below the start point that stops the second compressor (default 5%)%Command
AV528PropCool_cCooling PID proportional constant used for header rack applications (default 2)Command
AV529IntCool_cCooling PID integral constant used for header rack applications (default 0.3)Command
AV530DerivCool_cCooling PID derivative constant used for header rack applications (default 0.1)Command
AV531CoolExecuteTime_cCooling PID execution time used for header rack applications (default 5 sec)secCommand
AV532CoolRampTime_cCooling PID ramp time, 0-100% (header rack) (default 15 min)minCommand
AV533PropHeat_cHeating PID proportional constant used for header rack applications (default 2)Command
AV534IntHeat_cHeating PID integral constant used for header rack applications (default 0.3)Command
AV535DerivHeat_cHeating PID derivative constant used for header rack applications (default 0.1)Command
AV536HeatExecuteTime_cHeating PID execution time used for header rack applications (default 5 sec)secCommand
AV537HeatRampTime_cHeating PID ramp time, 0-100% (header rack) (default 15 min)minCommand
AV538LoadValveProp_cLoad valve PID proportional constant used for header rack applications (default 2)Command
AV539LoadValveInt_cLoad valve PID integral constant used for header rack applications (default 1)Command
AV540LoadValveExecute_cLoad valve PID execution time used for header rack applications (default 0.5 sec)secCommand
AV541SourceValveProp_cSource valve PID proportional constant used for header rack applications (default 2)Command
AV542SourceValveInt_cSource valve PID integral constant used for header rack applications (default 1)Command
AV543SourceValveExecute_cSource valve PID execution time used for header rack applications (default 0.5 sec)secCommand
AV544LoadInTemp_stLoad entering water temperature, header rack (same as AV 19)°FRead
AV545LoadOutTemp_stLoad leaving water temperature, header rack (same as AV 18)°FRead
AV546SourceInTemp_stSource entering water temperature, header rack (same as AV 9)°FRead
AV547SourceOutTemp_stSource leaving water temperature, header rack (same as AV 8)°FRead
AV548ColdHeaderInletTemp_stCold water loop inlet temperature measured by HydroLink controller°FRead
AV549ColdHeaderOutletTemp_stCold water loop outlet temperature measured by HydroLink controller°FRead
AV550HotHeaderInletTemp_stHot water loop inlet temperature measured by HydroLink controller°FRead
AV551HotHeaderOutletTemp_stHot water loop outlet temperature measured by HydroLink controller°FRead
AV552GeoHeaderInletTemp_stGeothermal loop water inlet temperature measured by HydroLink controller°FRead
AV553GeoHeaderOutletTemp_stGeothermal loop water outlet temperature measured by HydroLink controller°FRead
AV554ActiveColdWaterTemp_stActive cold water control temperature for header rack applications°FRead
AV555ActiveHotWaterTemp_stActive hot water control temperature for header rack applications°FRead
AV556ActiveGeoWaterTemp_stActive geothermal water temperature for header rack applications°FRead
AV557CurrentDemandPct_stCalculated PID operating demand percentage%Read
AV558Load3WayValve_stCurrent position of 3-way load control valve%Read
AV559Source3WayValve_stCurrent position of 3-way source control valve%Read
AV560ColdBypassValve_stCurrent position of cold water loop bypass valve%Read
AV561HotBypassValve_stCurrent position of hot water loop bypass valve%Read
AV562GeoBypassValve_stCurrent position of geothermal loop bypass valve%Read
AV563ManLoad3WayValvePct_cManual 3-way load valve position (BV 502 Active) (default 0%)%Command
AV564ManSource3WayValvePct_cManual 3-way source valve position (BV 502 Active) (default 0%)%Command
AV565ManColdBypassValvePct_cManual cold bypass valve position (BV 502 Active) (default 0%)%Command
AV566ManHotBypassValvePct_cManual hot bypass valve position (BV 502 Active) (default 0%)%Command
AV567ManGeoBypassValvePct_cManual geo bypass valve position (BV 502 Active) (default 0%)%Command
AV568HeaderModeNum_cHeader rack mode, numeric (used when BV 511 = Numeric) (default 99)Command0=Off with Isolation valves open; 1=Cooling only; 2=Heating only; 3=Auto full building; 4=Full building; 5=Primary cooling; 6=Primary heating; 99=System off
BV0LeadLagEnable_cEnables internal compressor lead/lag (default Enabled)CommandInactive=Disabled; Active=Enabled
BVmin1Mode_cCool or heat mode for non-header-rack units (default Cool)CommandInactive=Cool; Active=Heat
BVmin2EmShutdown_cNetwork emergency shutdown command (default Normal)CommandInactive=Normal; Active=Shutdown
BV3LoadShedB_cLoad shed for compressor B (default Inactive)CommandInactive=Inactive; Active=Active
BV4LoadShedA_cLoad shed for compressor A (default Inactive)CommandInactive=Inactive; Active=Active
BV5EnableManualOverride_cEnables manual override of Y1, Y2 and O/B outputs (default Disabled)CommandInactive=Disabled; Active=Enabled
BV6ABCA_Y1Override_cManual compressor A call (needs BV 5 enabled) (default Off)CommandInactive=Off; Active=On
BV7ABCB_Y1Override_cManual compressor B call (needs BV 5 enabled) (default Off)CommandInactive=Off; Active=On
BV8ABC_OBOverride_cManual reversing valve command (needs BV 5 enabled) (default Cool)CommandInactive=Cool; Active=Heat
BV9TestModeCommand_cPuts the Aurora controls in test mode (default Normal)CommandInactive=Normal; Active=Test Mode
BV10PowerPhaseSelect_cSingle or three phase, for power calculations (default Three Phase)CommandInactive=Single Phase; Active=Three Phase
BV11ABCA_HDW_ALM_stStatus of ABC A alarm outputReadInactive=Off; Active=On
BV12ABCA_HDW_Y1_stStatus of ABC A physical Y1 inputReadInactive=Off; Active=On
BV13ABCA_HDW_Y2_stStatus of ABC A physical Y2 inputReadInactive=Off; Active=On
BV14ABCA_HDW_OB_stStatus of ABC A physical O/B inputReadInactive=Off; Active=On
BV15ABCA_HDW_ES_stStatus of ABC A physical emergency shutdown inputReadInactive=Normal; Active=Shutdown
BV16ABCA_HDW_LPS_stStatus of ABC A physical low pressure switch inputReadInactive=Open; Active=Closed
BV17ABCA_HDW_HPS_stStatus of ABC A physical high pressure switch inputReadInactive=Open; Active=Closed
BV18ABCA_HDW_LS_stStatus of ABC A physical load shed inputReadInactive=Inactive; Active=Active
BV19ABCA_HDW_CC_stStatus of ABC A compressor outputReadInactive=Off; Active=On
BV20ABCA_HDW_RV_stStatus of ABC A reversing valve outputReadInactive=Off; Active=On
BV21ABCA_HDW_ACC_stStatus of ABC A accessory relay outputReadInactive=Off; Active=On
BV22ABCB_HDW_ALM_stStatus of ABC B alarm outputReadInactive=Off; Active=On
BV23ABCB_HDW_Y1_stStatus of ABC B physical Y1 inputReadInactive=Off; Active=On
BV24ABCB_HDW_Y2_stStatus of ABC B physical Y2 inputReadInactive=Off; Active=On
BV25ABCB_HDW_OB_stStatus of ABC B physical O/B inputReadInactive=Off; Active=On
BV26ABCB_HDW_ES_stStatus of ABC B physical emergency shutdown inputReadInactive=Normal; Active=Shutdown
BV27ABCB_HDW_LPS_stStatus of ABC B physical low pressure switch inputReadInactive=Open; Active=Closed
BV28ABCB_HDW_HPS_stStatus of ABC B physical high pressure switch inputReadInactive=Open; Active=Closed
BV29ABCB_HDW_LS_stStatus of ABC B physical load shed inputReadInactive=Inactive; Active=Active
BV30ABCB_HDW_CC_stStatus of ABC B compressor outputReadInactive=Off; Active=On
BV31ABCB_HDW_RV_stStatus of ABC B reversing valve outputReadInactive=Off; Active=On
BV32ABCB_HDW_ACC_stStatus of ABC B accessory relay outputReadInactive=Off; Active=On
BVmin33AlarmReset_cAlarm reset; return to Normal once the lockout clears (default Normal)CommandInactive=Normal; Active=Reset
BV34NetworkY2Command_cNetwork call for compressor B (MSV 2 = Network) (default Off)CommandInactive=Off; Active=On
BV35NetworkY1Command_cNetwork call for compressor A (MSV 2 = Network) (default Off)CommandInactive=Off; Active=On
BVmin36NetworkControl_cSet by the BAS while it has network control (default Normal)CommandInactive=Normal; Active=Network
BVmin37SystemEnable_cSystem enable; compressors stay off when disabled (default Enabled)CommandInactive=Disabled; Active=Enabled
BV38CompASourceFlowSw_stSource loop flow switch, compressor A (On = flow)ReadInactive=Off; Active=On
BV39CompALoadFlowSw_stLoad loop flow switch, compressor A (On = flow)ReadInactive=Off; Active=On
BV40CompBSourceFlowSw_stSource loop flow switch, compressor B (On = flow)ReadInactive=Off; Active=On
BV41CompBLoadFlowSw_stLoad loop flow switch, compressor B (On = flow)ReadInactive=Off; Active=On
BV500SystemControl_cSetpoint or Aquastat control (some header rack applications) (default Setpoint)CommandInactive=Setpoint; Active=Aquastat
BV501NetBypassCtrl_cLocal or network control of bypass valves (default Inactive)CommandInactive=Inactive; Active=Active
BV502HeaderRackManCtrl_cManual control of all header rack valves (default Inactive)CommandInactive=Inactive; Active=Active
BV503GeoWaterSelect_cLocal or network geothermal loop temperatures (default Local)CommandInactive=Local; Active=Network
BV504HeaderY1output_stStatus of header rack Y1 compressor demand logical outputReadInactive=FALSE; Active=TRUE
BV505HeaderY2output_stStatus of header rack Y2 compressor demand logical outputReadInactive=FALSE; Active=TRUE
BV506HeaderHeatOutput_stStatus of header rack heat/cool B demand logical outputReadInactive=FALSE; Active=TRUE
BV507CWSensorFault_stSelected cold water control temperature is invalidReadInactive=FALSE; Active=TRUE
BV508HWSensorFault_stSelected hot water control temperature is invalidReadInactive=FALSE; Active=TRUE
BV509TempSensorFault_stSelected cold or hot water control temperature is invalidReadInactive=FALSE; Active=TRUE
BV510ManIsoValves_cManual isolation valve command (used when BV 502 is Active) (default Inactive)CommandInactive=Inactive; Active=Active
BV511HeaderModeSelect_cHeader rack mode source: numeric AV 568 or enumerated MSV 501 (default Enumerated)CommandInactive=Enumerated; Active=Numeric
MVmin0SystemStatus_stOverall system statusRead1=Normal; 2=Alarm; 3=Shutdown; 4=Load Shed A; 5=Load Shed B; 6=Load Shed A & B; 7=AXB A Communication Loss; 8=AXB B Communication Loss; 9=AXB A & B Communication Loss; 10=ABC A Communication Loss; 11=ABC B Communication Loss; 12=ABC A & B Communication Loss; 13=ABC A & ABC B DIP Switch Mismatch; 14=Load Entering Water Temperature Alarm; 15=Load Leaving Water Temperature Alarm; 16=Source Entering Water Temperature Alarm
MVmin1UnitMode_stOverall operating modeRead1=Standby; 3=Single Compressor Cooling; 4=Both Compressors Cooling; 6=Single Compressor Heating; 7=Both Compressors Heating; 10=Emergency Shutdown; 11=Load Shed; 12=Lockout A; 13=Test Mode; 15=Lockout B; 18=Single Compressor w/Lockout; 19=Full Lockout; 31=Source Flow Switch Fault; 32=Load Flow Switch Fault; 33=Load & Source Flow Switch Fault
MV2TempControlMethod_cTemperature control method (non-header-rack) (default 1)Command1=AquaStat (uses Y1 & Y2 inputs on ABC A); 2=Setpoint (uses either AV:22 or AV:23 as setpoint); 3=Network (uses BV:34 & BV:35); 4=Setpoint w/Enable (uses either AV:22 or AV:23 as setpoint and ABC B Y2 input as enable)
MV3ControlTempInput_cControl temperature input (non-header-rack) (default 2)Command1=Leaving Water (AV:18 Leaving load water temp); 2=Entering Water (AV:19 Entering load water temp); 3=Remote Temp (AXB B - HWT); 4=Network Temp (AV:12)
MV4BrineFactorLoad_cAurora controls brine selection factor for load loop (default 1)Command1=Water; 2=Brine
MV5EnergyMonitorMode_cAurora controls energy monitoring modes selection (default 3)Command1=Off; 2=Compressor Monitoring; 3=Energy Monitoring
MV6BrineFactorSource_cAurora controls brine selection factor for source loop (default 1)Command1=Water; 2=Brine
MV7LoadFlowMeterSelect_cLoad loop flow meter selection (default 1)Command1=None; 2=3/4", 19mm; 3=1", 25.4mm; 4=2", 50.8mm; 5=2.5", 63.5mm; 6=1.25", 31.8mm
MV8SrcFlowMeterSelect_cSource loop flow meter selection (default 1)Command1=None; 2=3/4", 19mm; 3=1", 25.4mm; 4=2", 50.8mm; 5=2.5", 63.5mm; 6=1.25", 31.8mm
MV9ABCBLockoutStatus_stMost recent fault on ABC BRead1=Normal; 2=E1-Input Error; 3=E2-High Pressure; 4=E3-Low Pressure; 5=E4-Freeze Protection 2; 6=E5-Freeze Protection 1; 7=E6-Loss of Charge; 8=E7-Condensate; 9=E8-Over/Under Voltage; 11=E10-Compressor Monitor; 14=E13-AXB Sensor Error - Non Critical; 15=E14-AXB Sensor Error - Critical; 17=E16-Variable Speed Pump Error; 19=E18-Non Critical Comm Error; 20=E19-Critical Comm Error; 21=E20-Loss of Communications; 22=E21-Low Loop Pressure; 24=E23-HA1 Fault; 25=E24-HA2 Fault; 27=E26-Entering Source Water Low Limit; 28=E27-Entering Source Water High Limit; 29=E28-Leaving Source Water Low Limit; 30=E29-Leaving Source Water High Limit; 32=E31-Source Flow
MV10ABCALockoutStatus_stMost recent fault on ABC ARead1=Normal; 2=E1-Input Error; 3=E2-High Pressure; 4=E3-Low Pressure; 5=E4-Freeze Protection 2; 6=E5-Freeze Protection 1; 7=E6-Loss of Charge; 8=E7-Condensate; 9=E8-Over/Under Voltage; 11=E10-Compressor Monitor; 14=E13-AXB Sensor Error - Non Critical; 15=E14-AXB Sensor Error - Critical; 17=E16-Variable Speed Pump Error; 19=E18-Non Critical Comm Error; 20=E19-Critical Comm Error; 21=E20-Loss of Communications; 22=E21-Low Loop Pressure; 24=E23-HA1 Fault; 25=E24-HA2 Fault; 27=E26-Entering Source Water Low Limit; 28=E27-Entering Source Water High Limit; 29=E28-Leaving Source Water Low Limit; 30=E29-Leaving Source Water High Limit; 32=E31-Source Flow
MV500HeaderRackType_cHeader rack selection value (default 1)Command1=No header; 2=4 Pipe Standard; 3=4 Pipe Reversing; 4=6 Pipe Standard; 5=6 Pipe Dedicated Source
MV501HeaderMode_cHeader rack mode, enumerated (used when BV 511 = Enumerated) (default 8)Command1=Off with Isolation valves open; 2=Cooling only; 3=Heating only; 4=Auto full building; 5=Full building; 6=Primary cooling; 7=Primary heating; 8=System off
MV502ColdWaterSelect_cCold water control temperature for header rack (default 1)Command1=Heat Exchanger Out; 2=Cold Water Out; 3=Cold Water In; 4=Network (AV:506)
MV503HotWaterSelect_cHot water control temperature for header rack (default 1)Command1=Heat Exchanger Out; 2=Hot Water Out; 3=Hot Water In; 4=Network (AV:507)

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps

How many BACnet points does the WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps have?

This list has 213 BACnet objects: 144 analog values, 54 binary values, 15 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps BACnet points are writable?

118 of the 213 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps BACnet documentation?

The source is Aurora HydroLink BACnet Points List For NXW/SKW (PL2500EW), revision 2018-02, published free by WaterFurnace at https://www.waterfurnace.com/literature/aurora/pl2500ew.pdf.

What are the minimum BACnet points to integrate the WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps?

Start with BV 37 SystemEnable_c (System enable; compressors stay off when Disabled); BV 36 NetworkControl_c (Set to Network while the BAS has control); BV 2 EmShutdown_c (Network emergency shutdown); BV 1 Mode_c (Cool or heat (non-header-rack units)); AV 22 CoolingSetpoint_c (Cooling setpoint, setpoint control mode); AV 23 HeatingSetpoint_c (Heating setpoint, setpoint control mode); BV 33 AlarmReset_c (Alarm reset; return to Normal after the lockout clears); MV 1 UnitMode_st (Current operating mode); AV 1 ControlTemp_st (Control temperature (input chosen on MSV 3)); MV 0 SystemStatus_st (Overall status: normal, alarm, shutdown, load shed).

How do I enable BMS control of the WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps?

BV 37 SystemEnable_c (default Enabled) must be Enabled, or the compressor outputs stay off except under manual override. The BAS should set BV 36 NetworkControl_c to Network when it takes control; many local commands and settings then stop working. With MSV 2 = 3 (Network), BV 35 and BV 34 call compressors A and B; BV 1 picks cool or heat. BV 2 EmShutdown_c forces an emergency shutdown.

Can the BMS supply sensor values to the WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps?

AV 62 NetworkTemperature_c is the BAS-supplied control temperature for setpoint control on a network temperature (MSV 3 option 4, which the sheet labels AV 12). Header rack units take BAS cold, hot and geo loop temperatures on AV 506-508; values written to AV 510-515 take priority over the measured header temperatures. BV 503 switches the geothermal loop temperatures to network values.

How do I check these points on the real Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WaterFurnace BACnet points lists

Source: Aurora HydroLink BACnet Points List For NXW/SKW · PL2500EW · rev. 2018-02. Object names, instances and units are reproduced as published; descriptions are our own.