WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump BACnet points list
Updated 28 October 2026
BACnet objects of the Aurora Universal Protocol Converter (UPC) on a single-compressor water-source heat pump, software version 1.01. The UPC sits on the Aurora Base Controller (ABC) and exposes zone temperature, setpoints, occupancy, fan, compressor and dip-switch points over BACnet MS/TP. Points marked as needing the AXB board only report with that board and its sensors fitted.
This page lists 201 BACnet objects for the WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump — 55 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.
- Manufacturer
- WaterFurnace
- Model
- Aurora UPC, Single Compressor Water-Source Heat Pump
- Equipment
- Water-source heat pump controller
- Equipment type
- Heat pumps
- BACnet objects
- 201 (55 writable)
- Transport
- BACnet MS/TP
- Firmware
- UPC software version 1.01
- Also known as
- AG1569EW, Aurora Universal Protocol Converter, Aurora UPC, UPCSWASTD01-01
BMS integration notes: WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump
Set BV 54 to External, then command occupancy on MSV 1 and let the UPC hold its occupied, unoccupied and standby setpoints (AV 5-10). Read MSV 11 for the operating mode and MSV 8 for the lockout code. The BAS can also act as the thermostat with BV 44-48 (G, O, W, Y1, Y2).
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 1 | occ_man_cmd_c | Occupied/unoccupied/temp occ/standby command | Write |
| BV 54 | schedule_selector_c | Must be External for BAS occupancy commands | Write |
| BV 25 | e_stop_c | Network emergency shutdown | Write |
| AV 5 | occ_clg_sp_c | Occupied cooling setpoint | Write |
| AV 6 | occ_htg_sp_c | Occupied heating setpoint | Write |
| BV 5 | alarm_reset_c | Reset manual-reset alarms (On, then back to Off) | Write |
| AV 1 | zone_temp_an | Space temperature (sensor or BAS override) | Read |
| MV 11 | mode_st | Current operating mode | Read |
| MV 9 | compressor_status_st | Compressor output: off, low or high | Read |
| MV 8 | lockout_enumerated_st | Active alarm code (see alarm table) | Read |
Enable & remote start
The UPC runs its own internal weekday schedule until BV 54 schedule_selector_c is set to External (Active). Occupancy commands then go to MSV 1, or to AV 42 after BV 50 is set to AV. BV 25 e_stop_c shuts the unit down; BV 44-48 send G, O, W, Y1 and Y2 calls directly.
Sensors & values from the BMS
AV 4 zone_temp_ovrd_c replaces the zone sensor once BV 55 zone_temp_selector_c is set to BAS. AV 17 humidity_c, AV 22 co2_c and AV 24 voc_c take BAS values when no sensor is connected, and AV 26 oat_c takes an outdoor air temperature.
Network setup
- Port 1a is the BAS port: EIA-485 for BACnet MS/TP (or N2), set by DIP switches, with baud 9600, 19.2k, 38.4k or 76.8k. It ships set to BACnet at 38,400 baud.
- Port 1a can instead be jumpered for ARC156 (BACnet over ARCNET at 156 kbps). A LonWorks plug-in card uses port 1b and disables port 1a.
- The MAC address is set on two rotary switches (tens and ones), 1 from the factory and 99 at most. The UPC only reads a new address after a power cycle.
- The device instance is built from the network number and the MAC: network 7000 with MAC 12 gives 7012.
- Wiring: 22 or 24 AWG shielded twisted pair, daisy-chained, polarity-sensitive (Net+, Net-, shield). About 30 devices and 2,000 ft per trunk; every MAC on a trunk must be unique.
Watch out for
- Dip switch overrides (BV 11-18) only reach the ABC while BV 22 is enabled. Record the physical switch settings first, and a slow-flashing yellow LED on the ABC means a switch is overridden.
- Alarm reset: command BV 5 On, then back to Off. Loss-of-communication and over/under-voltage alarms reset themselves and cannot be reset from the network.
- Zone sensor warm/cool adjust (AV 15, default 5 F) only shifts the setpoints in occupied or temporary occupied mode.
- Points shown with * in the source need the AXB board and its sensors.
WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AVmin | 1 | zone_temp_an | Zone temperature if sensor is present or if overridden by the BAS | °F | Read | |
| AV | 2 | zone_temp_adj_c | Zone temp adjust value (default 0) | °F | Write | |
| AV | 3 | active_setpt_an | Set point that is controlling the call for the compressor | °F | Read | |
| AV | 4 | zone_temp_ovrd_c | BAS override of the zone temp sensor reading (default 0) | °F | Write | |
| AVmin | 5 | occ_clg_sp_c | Occupied cooling set point (default 76) | °F | Write | |
| AVmin | 6 | occ_htg_sp_c | Occupied heating set point (default 70) | °F | Write | |
| AV | 7 | unocc_clg_sp_c | Unoccupied cooling set point (default 85) | °F | Write | |
| AV | 8 | unocc_htg_sp_c | Unoccupied heating set point (default 60) | °F | Write | |
| AV | 9 | standby_cool_c | Standby cooling set point (default 76) | °F | Write | |
| AV | 10 | standby_heat_c | Standby heating set point (default 68) | °F | Write | |
| AV | 11 | eff_clg_sp_an | Effective cooling set point | °F | Read | |
| AV | 12 | eff_htg_sp_an | Effective heating set point | °F | Read | |
| AV | 13 | clg_adj_an | Cooling set point shift value | °F | Read | |
| AV | 14 | htg_adj_an | Heating set point shift value | °F | Read | |
| AV | 15 | rem_setpt_span_c | Warm/cool adjust span of the zone sensor (default 5) | °F | Write | |
| AV | 16 | humidity_an | Humidity sensor reading if sensor is present | %rh | Read | |
| AV | 17 | humidity_c | BAS override of the humidity input if no sensor is connected (default 0) | %rh | Write | |
| AV | 18 | occ_dehum_setpt_c | Sets the occupied dehumidify set point (default 53) | %rh | Write | |
| AV | 19 | unocc_dehum_setpt_c | Sets the unoccupied dehumidify set point (default 75) | %rh | Write | |
| AV | 20 | dehum_diff_c | Sets the differential for humidity set point (default 5) | %rh | Write | |
| AV | 21 | co2_an | Space CO2 reading if sensor is present | ppm | Read | |
| AV | 22 | co2_c | BAS override of space CO2 if no sensor is present (default 0) | ppm | Write | |
| AV | 23 | voc_an | Space VOC (volatile organic compounds) if sensor is present | ppm | Read | |
| AV | 24 | voc_c | BAS override of space VOC if no sensor is connected (default 0) | ppm | Write | |
| AV | 25 | oat_an | Outside air temperature | °F | Read | |
| AV | 26 | oat_c | BAS override of the outside air temperature (default 0) | °F | Write | |
| AV | 27 | axb_spare_ana_input_an | Spare analog input on the AXB (needs AXB) | °F | Read | |
| AV | 28 | lvg_wtr_temp_an | Leaving water temperature (needs AXB) | °F | Read | |
| AV | 29 | liq_line_temp_an | Liquid line temperature (needs AXB) | °F | Read | |
| AV | 30 | abc_lat_an | Leaving air temperature on the ABC FP2 input | °F | Read | |
| AV | 31 | coax_temp_an | Coax temperature read by the FP1 sensor | °F | Read | |
| AV | 32 | fp1_setpoint_an | FP1 freeze detection limit temperature (coax temp) | °F | Read | |
| AV | 33 | ecm_pwm_an | Current ECM blower operating percentage | % | Read | |
| AV | 34 | ecm_sw_speed_an | ECM blower speed step, 1-12 | % | Read | |
| AV | 35 | ecm_override_c | BAS override of the ecm blower, select from virtual switches 1-12 (default 0) | % | Write | |
| AV | 36 | fan_low_c | Sets the low speed fan value (default 2) | Write | ||
| AV | 37 | fan_medium_c | Sets the medium speed fan value (default 7) | Write | ||
| AV | 38 | fan_high_c | Sets the high speed fan value (default 9) | Write | ||
| AV | 39 | fan_aux_heat_c | Sets the Aux Heat speed fan value (default 9) | Write | ||
| AV | 40 | clg_cfm_offset_ana_c | Sets the blower CFM to improve passive dehumidification (default 1) | Write | 1=HGT CFM = CLG CFM; 2=- 5% ClG CFM; 3=-10% CLG CFM; 4=-15%CLG CFM; 5=+5% CLG CFM | |
| AV | 41 | temp_occ_time_an | Amount of time left in temporary occupancy only while in Temp Occ | m/sec | Read | |
| AV | 42 | occ_man_cmd_ana_c | Occupancy command (used when BV 50 = AV) (default 1) | Write | 1=Occupied; 2=Unoccupied; 3=Temp Occ; 4=Standby | |
| AV | 43 | eff_occ_an | Effective occupancy | Read | 1=Occupied; 2=Unoccupied; 3=Temp Occ; 4=Standby | |
| AV | 44 | lockouts_enumerated_an | Current lockout alarm code (see alarm table) | Read | 1=Normal; 2=E1 Input fault; 3=E2 High pressure; 4=E3 Low pressure; 5=E4 Not used; 6=E5 Freeze detection FP1; 7=E6 Loss of charge; 8=E7 Condensate overflow; 9=E8 Over/under voltage; 10=E9 Airflow monitoring (future); 11=E10 Compressor monitoring; 12=E11 FP1 sensor error; 13=E12 Refrigeration monitoring (future); 14=E13 Non-critical AXB sensor error (future); 15=E14 Critical AXB sensor error (future); 16=E15 Hot water limit; 17=E16 Variable speed pump; 19=E18 Non-critical comm error; 20=E19 UPC loss of comm to ABC; 30=E30 Zone sensor loss of comm | |
| AV | 45 | lo_stat_reg_an | Internal use; do not map to BAS | Read | ||
| AV | 46 | control_voltage_an | ABC's low voltage control value | V | Read | |
| AV | 47 | est_line_voltage_an | Estimated line voltage to the unit | V | Read | |
| AV | 48 | mode_st_an | Current operating mode (numeric) | Read | 1=Standby; 2=Fan Only; 3=Cool Stage 1; 4=Cool Stage 2; 5=Hot Gas Reheat; 6=Heat Stage 1; 7=Heat Stage 2; 8=Emergency Heat; 9=Auxiliary Heat; 10=Emergency Shutdown; 11=Load Shed; 12=Unit In Lock Out; 13=Test Mode | |
| AV | 49 | water_flow_an | Calculated GPM thru the heat exchanger (needs AXB) | gpm | Read | |
| AV | 50 | total_power_an | Total power consumption (needs AXB) | W | Read | |
| AV | 51 | total_capacity_an | Total BTU operating capacity (needs AXB) | Btu/hr | Read | |
| AV | 52 | super_heat_an | Calculated super-heat (needs AXB) | °F | Read | |
| AV | 53 | suct_temp_an | Measured suction temperature (needs AXB) | °F | Read | |
| AV | 54 | suction_press_an | Measured suction pressure (needs AXB) | psi | Read | |
| AV | 55 | he_hr_an | Calculated heat of extraction/rejection (needs AXB) | Btu/hr | Read | |
| AV | 56 | fan_power_an | Calculated fan power consumption (needs AXB) | W | Read | |
| AV | 57 | fan_current_an | Measured fan current (needs AXB) | A | Read | |
| AV | 58 | entering_wtr_temp_an | Measured entering water temperature (needs AXB) | °F | Read | |
| AV | 59 | dischg_press_an | Compressor discharge pressure (needs AXB) | psi | Read | |
| AV | 60 | compressor_power_an | Calculated compressor power consumption (needs AXB) | W | Read | |
| AV | 61 | acc1_delay_c | Sets the time delay of the ACC-1 output (default 90) | seconds | Write | |
| AV | 62 | measured_line_voltage_c | Calibrates the measured line voltage (default 0) | Write | ||
| AV | 63 | tstat_ovrd_c | Internal use; do not map to BAS | Read | ||
| AV | 64 | sw_part_no_an | Internal use; do not map to BAS | Read | ||
| AV | 65 | abc_fw_beta_an | Internal use; do not map to BAS | Read | ||
| AV | 66 | abc_fw_rev_an | Internal use; do not map to BAS | Read | ||
| AV | 67 | m540_c | Internal use; do not map to BAS | Read | ||
| AV | 68 | m555_c | Internal use; do not map to BAS | Read | ||
| AV | 69 | m558_an | Internal use; do not map to BAS | Read | ||
| AV | 70 | m557_c | Internal use; do not map to BAS | Read | ||
| AV | 71 | m563_c | Internal use; do not map to BAS | Read | ||
| AV | 72 | m565_c | Internal use; do not map to BAS | Read | ||
| AV | 73 | m567_c | Internal use; do not map to BAS | Read | ||
| AV | 74 | m560_an | Internal use; do not map to BAS | Read | ||
| AV | 75 | m569_c | Internal use; do not map to BAS | Read | ||
| AV | 76 | m571_c | Internal use; do not map to BAS | Read | ||
| AV | 77 | m545_an | Internal use; do not map to BAS | Read | ||
| AV | 78 | m535_an | Internal use; do not map to BAS | Read | ||
| AV | 79 | m574_c | Internal use; do not map to BAS | Read | ||
| AV | 80 | m576_an | Internal use; do not map to BAS | Read | ||
| AV | 81 | m579_c | Internal use; do not map to BAS | Read | ||
| AV | 82 | m578_an | Internal use; do not map to BAS | Read | ||
| AV | 83 | m582_an | Internal use; do not map to BAS | Read | ||
| AV | 84 | m584_an | Internal use; do not map to BAS | Read | ||
| AV | 85 | m586_an | Internal use; do not map to BAS | Read | ||
| AV | 86 | m588_an | Internal use; do not map to BAS | Read | ||
| AV | 87 | m590_an | Internal use; do not map to BAS | Read | ||
| AV | 88 | m592_an | Internal use; do not map to BAS | Read | ||
| AV | 89 | m594_an | Internal use; do not map to BAS | Read | ||
| AV | 90 | m598_c | Internal use; do not map to BAS | Read | ||
| AV | 91 | m599_an | Internal use; do not map to BAS | Read | ||
| AV | 92 | m596_c | Internal use; do not map to BAS | Read | ||
| AV | 93 | m547_an | Internal use; do not map to BAS | Read | ||
| AV | 94 | r5_c | Internal use; do not map to BAS | Read | ||
| AV | 95 | m549_c | Internal use; do not map to BAS | Read | ||
| AV | 96 | m551_c | Internal use; do not map to BAS | Read | ||
| AV | 97 | m553_c | Internal use; do not map to BAS | Read | ||
| AV | 98 | test_md_pwd_c | Internal use; do not map to BAS | Read | ||
| AV | 99 | m401_c | Internal use; do not map to BAS | Read | ||
| AV | 100 | m405_c | Internal use; do not map to BAS | Read | ||
| AV | 101 | m409_c | Internal use; do not map to BAS | Read | ||
| AV | 102 | m413_c | Internal use; do not map to BAS | Read | ||
| AV | 103 | m417_c | Internal use; do not map to BAS | Read | ||
| AV | 104 | m421_c | Internal use; do not map to BAS | Read | ||
| AV | 105 | m425_c | Internal use; do not map to BAS | Read | ||
| AV | 106 | m429_c | Internal use; do not map to BAS | Read | ||
| AV | 107 | m433_c | Internal use; do not map to BAS | Read | ||
| AV | 108 | m441_c | Internal use; do not map to BAS | Read | ||
| AV | 109 | m445_c | Internal use; do not map to BAS | Read | ||
| AV | 110 | m449_c | Internal use; do not map to BAS | Read | ||
| AV | 111 | m453_c | Internal use; do not map to BAS | Read | ||
| AV | 112 | m488_c | Internal use; do not map to BAS | Read | ||
| AV | 113 | m494_c | Internal use; do not map to BAS | Read | ||
| AV | 114 | m495_c | Internal use; do not map to BAS | Read | ||
| AV | 115 | m496_c | Internal use; do not map to BAS | Read | ||
| AV | 116 | m497_c | Internal use; do not map to BAS | Read | ||
| AV | 117 | m498_c | Internal use; do not map to BAS | Read | ||
| AV | 118 | m500_c | Internal use; do not map to BAS | Read | ||
| AV | 119 | m501_c | Internal use; do not map to BAS | Read | ||
| BV | 1 | abc_modbus_comm_alarm | Modbus link status between the ABC and the UPC | Read | Inactive=Communication Normal; Active=Communication Lost | |
| BV | 2 | acc1_st | Status of the ACC-1 output | Read | Inactive=Off; Active=On | |
| BV | 3 | alm_rht_hdw_st | Status of the ABC's alarm/reheat output | Read | Inactive=Off; Active=On | |
| BV | 4 | alarm_reset_cmd_st | Commanded status of the alarm reset command | Read | Inactive=Off; Active=On | |
| BVmin | 5 | alarm_reset_c | Alarm reset: write On, then back to Off (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 6 | aux_heat_ena_c | Electric heat 1 control: network or aux heat PID (default Inactive) | Write | Inactive=Network EH; Active=Aux Heat | |
| BV | 7 | aux_heat_cmd_st | Status of the aux heat command | Read | Inactive=Off; Active=On | |
| BV | 8 | cc_op_cfg_st | Dip SW2-6 position: dual or single capacity (factory set) | Read | Inactive=Dual Capacity; Active=Single Capacity | |
| BV | 9 | clear_faults_c | Internal use; do not map to BAS | Read | ||
| BV | 10 | condensate_st | Internal use; do not map to BAS | Read | ||
| BV | 11 | sw2_1_c | Dip SW2-1 override: freeze detection setpoint (default Active) | Write | Inactive=15°; Active=30° | |
| BV | 12 | sw2_2_c | Not used (default Active) | Write | ||
| BV | 13 | sw2_3_c | Dip SW2-3 override: default reversing valve position (default Active) | Write | Inactive=Cooling; Active=Heating | |
| BV | 14 | sw2_4_c | Dip SW2-4 override; with SW2-5 sets the ACC1 mode (default Active) | Write | ||
| BV | 15 | sw2_5_c | Dip SW2-5 override; with SW2-4 sets the ACC1 mode (default Inactive) | Write | ||
| BV | 16 | sw2_6_c | Dip SW2-6 override: dual or single capacity (factory set) (default Inactive) | Write | Inactive=Dual Capacity; Active=Single Capacity | |
| BV | 17 | sw2_7_c | Dip SW2-7 override: pulsed or continuous alarm output (default Active) | Write | Inactive=Pulsed; Active=Continuous | |
| BV | 18 | sw2-8_c | Dip SW2-8 override: reheat or normal (factory set) (default Active) | Write | Inactive=Reheat; Active=Normal | |
| BV | 19 | dh_cmd_st | Status of the dehumidification command | Read | Inactive=Off; Active=On | |
| BV | 20 | dh_disable_c | Enables/disables dehumidification (default Active) | Write | Inactive=DH Disabled; Active=DH Enabled | |
| BV | 21 | dehum_hdw_st | Status of the DH hardware input | Read | Inactive=Off; Active=On | |
| BV | 22 | dip_sw_ovrd_ena_c | Enables BAS dip switch overrides (BV 11-18) (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 23 | eh_1_st | Status of the electric heat 1 output | Read | Inactive=Off; Active=On | |
| BV | 24 | eh_2_st | Status of the electric heat 2 output | Read | Inactive=Off; Active=On | |
| BVmin | 25 | e_stop_c | Network emergency shutdown command (default Inactive) | Write | Inactive=Normal Operation; Active=Shutdown | |
| BV | 26 | es_hdw_st | Status of the emergency shutdown hardware input | Read | Inactive=Normal; Active=Shutdown | |
| BV | 27 | factory_test_ena_c | Internal use; do not map to BAS | Read | ||
| BV | 28 | fan_operation_c | Selects either cycled or continuous operation of the fan (default Active) | Write | Inactive=Cycled; Active=Continuous | |
| BV | 29 | fan_st | Current status of the fan output | Read | Inactive=Off; Active=On | |
| BV | 30 | fp1_lim_st | Current freeze detection set point | Read | Inactive=15°; Active=30° | |
| BV | 31 | eh1_ovrd_c | Network control of electric heat 1 output relay (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 32 | g_cmd_st | Status of the network "G" command | Read | Inactive=Off; Active=On | |
| BV | 33 | g_hdw_fan_proving_input_st | Status of the "G" hardware input | Read | Inactive=Off; Active=On | |
| BV | 34 | heat_cool_st | Status of the network "O" command | Read | Inactive=Off; Active=On | |
| BV | 35 | high_press_hdw_st | Status of the high pressure hardware input | Read | Inactive=Off; Active=On | |
| BV | 36 | internal_external_scheduling_st | Selected schedule that the UPC is operating on | Read | Inactive=Internal; Active=External | |
| BV | 37 | load_shed_c | Enables/disables load shed (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 38 | lockout__st | Status of the lockout alarm output | Read | Inactive=Normal; Active=Lockout | |
| BV | 39 | lockout_cfg_st | Internal use; do not map to BAS | Read | ||
| BV | 40 | lockout_hdw_st | Status of the relay for the ABC's Lockout output | Read | Inactive=Normal; Active=Lockout | |
| BV | 41 | low_press_hdw_st | Status of the low pressure switch hardware input | Read | Inactive=Open; Active=Closed | |
| BV | 42 | load_shed_hdw_st | Status of the load shed hardware input | Read | Inactive=Normal; Active=Load Shed | |
| BV | 43 | network_dh_c | Enables/disables dehumidification (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 44 | network_g_c | Network control of the fan (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 45 | network_o_c | Network control of the reversing valve (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 46 | network_w_c | Network control of electric heat output (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 47 | network_y1_c | Network control of the Y1 output (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 48 | network_y2_c | Network control of the Y2 output (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 49 | o_hdw_occ_sensor_input_st | Status of the "O" hardware input | Read | Inactive=Off; Active=On | |
| BV | 50 | occ_cmd_av-msv_select_c | Selects either a "MSV" or "AV" to command the occupancy input (default Inactive) | Write | Inactive=MSV; Active=AV | |
| BV | 51 | reheat_cfg_st | Status of the dip switch used to select reheat or non-reheat operation | Read | Inactive=Reheat; Active=Normal | |
| BV | 52 | rev_vlv_st | Status of the reversing valve output | Read | Inactive=Heat; Active=Cool | |
| BV | 53 | rv_setup_st | Default position of reversing valve that is set by BV-13 | Read | Inactive=Cooling; Active=Heating | |
| BVmin | 54 | schedule_selector_c | Selects the internal schedule or external schedule (default Inactive) | Write | Inactive=Internal; Active=External | |
| BV | 55 | zone_temp_selector_c | Selects the zone sensor input (default Inactive) | Write | Inactive=Sensor; Active=BAS | |
| BV | 56 | sw1_test_cfg_st | Status of the SW2 dip switch override point | Read | Inactive=Off; Active=On | |
| BV | 57 | sw_2_4_st | Status of the SW2-4 dipswitch | Read | Inactive=Off; Active=On | |
| BV | 58 | sw_2_5_st | Status of the SW2-5 dipswitch | Read | Inactive=Off; Active=On | |
| BV | 59 | temp_occ_dis_c | Control to disable temporary occupancy (default Active) | Write | Inactive=Disabled; Active=Enabled | |
| BV | 60 | temp_occ_st | Status of the temporary occupancy input | Read | Inactive=Normal; Active=Temp Occ | |
| BV | 61 | test_mode_ena_c | Internal use; do not map to BAS | Read | ||
| BV | 62 | test_mode_hdw_st | Internal use; do not map to BAS | Read | ||
| BV | 63 | w_hdw_dirty_filter_input_st | Status of the "W" hardware input | Read | Inactive=Off; Active=On | |
| BV | 64 | y1_cmd_st | Status of the "Y1" input to the ABC from the UPC | Read | Inactive=Off; Active=On | |
| BV | 65 | y1_hdw_comp_proving_input_st | Status of the "Y1" hardware input, used as a compressor proving input | Read | Inactive=Off; Active=On | |
| BV | 66 | y2_cmd_st | Status of the "Y2" input to the ABC from the UPC | Read | Inactive=Off; Active=On | |
| BV | 67 | y2_hdw_vlv_end_sw_input_st | Status of the "Y2" hardware input | Read | Inactive=Off; Active=On | |
| BV | 68 | m372_c | Internal use; do not map to BAS | Read | ||
| BV | 69 | m373_c | Internal use; do not map to BAS | Read | ||
| BV | 70 | m374_c | Internal use; do not map to BAS | Read | ||
| BV | 71 | m375_c | Internal use; do not map to BAS | Read | ||
| BV | 72 | m376_c | Internal use; do not map to BAS | Read | ||
| BV | 73 | m377_c | Internal use; do not map to BAS | Read | ||
| BV | 74 | eh2_ovrd_c | Network control of the electric heat 2 output relay (default Inactive) | Write | Inactive=Off; Active=On | |
| BV | 75 | eh2_mode_c | EH2 output: network-controlled or aux heat (default Active) | Write | Inactive=Aux_Heat; Active=Network_EH | |
| BV | 76 | loadshed_st | Status of the load shed input | Read | Inactive=Normal; Active=Load Shed | |
| MVmin | 1 | occ_man_cmd_c | Occupancy command (used when BV 50 = MSV) (default 1) | Write | 1=Occupied; 2=Unoccupied; 3=Temp Occ; 4=Standby | |
| MV | 7 | clg_cfm_offset_msv_c | Selects the cooling CFM reduction value (default 1) | Write | 1=HGT CFM = CLG CFM; 2=-5% CLG CFM; 3=-10% CLG CFM; 4=-15% CLG CFM; 5=+5% CLG CFM | |
| MVmin | 8 | lockout_enumerated_st | Current lockout alarm code (see alarm table) | Read | 1=Normal; 2=E1 Input fault; 3=E2 High pressure; 4=E3 Low pressure; 5=E4 Not used; 6=E5 Freeze detection FP1; 7=E6 Loss of charge; 8=E7 Condensate overflow; 9=E8 Over/under voltage; 10=E9 Airflow monitoring (future); 11=E10 Compressor monitoring; 12=E11 FP1 sensor error; 13=E12 Refrigeration monitoring (future); 14=E13 Non-critical AXB sensor error (future); 15=E14 Critical AXB sensor error (future); 16=E15 Hot water limit; 17=E16 Variable speed pump; 19=E18 Non-critical comm error; 20=E19 UPC loss of comm to ABC | |
| MVmin | 9 | compressor_status_st | Capacity of the compressor output relay | Read | 1=Off; 2=Low; 3=High | |
| MV | 10 | effect_occup_st | Effective occupancy status | Read | 1=Occupied; 2=Unoccupied; 3=Temp Occ; 4=Standby | |
| MVmin | 11 | mode_st | Current operating mode of the unit | Read | 1=Standby; 2=Fan Only; 3=Cool Stage 1; 4=Cool Stage 2; 5=Hot Gas Reheat; 6=Heat Stage 1; 7=Heat Stage 2; 8=Emergency Heat; 9=Auxiliary Heat; 10=Emergency Shutdown; 11=Load Shed; 12=Unit In Lock Out; 13=Test Mode |
No points match these filters.
Integration notes
- Object names are the sheet's reference names; its display names (several just 'Set point') are not the BACnet object names.
- Many points are marked 'do not map' in the source and are listed only for completeness.
- The same PDF also carries N2 and LonWorks lists; only the BACnet list is captured here.
- Multistate value numbers jump from MSV 1 to MSV 7 in the source; MSV 2-6 are not listed.
- Alarm code meanings come from the alarm table in the Aurora UPC Application and Troubleshooting Guide (AG1568EW).
- Transport and network settings come from AG1568EW; the points list itself does not state them.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aurora UPC, Single Compressor Water-Source Heat Pump and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump
How many BACnet points does the WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump have?
This list has 201 BACnet objects: 119 analog values, 76 binary values, 6 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump BACnet points are writable?
55 of the 201 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump BACnet documentation?
The source is Aurora UPC Points List (BACnet Points for Single Compressor WSHP) (AG1569EW), revision 2014-07, published free by WaterFurnace at https://www.waterfurnace.com/literature/aurora/ag1569aw.pdf.
What are the minimum BACnet points to integrate the WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump?
Start with MV 1 occ_man_cmd_c (Occupied/unoccupied/temp occ/standby command); BV 54 schedule_selector_c (Must be External for BAS occupancy commands); BV 25 e_stop_c (Network emergency shutdown); AV 5 occ_clg_sp_c (Occupied cooling setpoint); AV 6 occ_htg_sp_c (Occupied heating setpoint); BV 5 alarm_reset_c (Reset manual-reset alarms (On, then back to Off)); AV 1 zone_temp_an (Space temperature (sensor or BAS override)); MV 11 mode_st (Current operating mode); MV 9 compressor_status_st (Compressor output: off, low or high); MV 8 lockout_enumerated_st (Active alarm code (see alarm table)).
How do I enable BMS control of the WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump?
The UPC runs its own internal weekday schedule until BV 54 schedule_selector_c is set to External (Active). Occupancy commands then go to MSV 1, or to AV 42 after BV 50 is set to AV. BV 25 e_stop_c shuts the unit down; BV 44-48 send G, O, W, Y1 and Y2 calls directly.
Can the BMS supply sensor values to the WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump?
AV 4 zone_temp_ovrd_c replaces the zone sensor once BV 55 zone_temp_selector_c is set to BAS. AV 17 humidity_c, AV 22 co2_c and AV 24 voc_c take BAS values when no sensor is connected, and AV 26 oat_c takes an outdoor air temperature.
How do I check these points on the real Aurora UPC, Single Compressor Water-Source Heat Pump?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More WaterFurnace BACnet points lists
- Water-to-water heat pump controller
WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps
WaterFurnace NXW and SKW dual-scroll water-to-water heat pumps (including header rack arrangements) with the Aurora HydroLink controller.
Also known as: PL2500EW, HydroLink, NXW, SKW, WCHDM, HYDWWB01 - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Dual Compressor Rooftop Unit with Economizer
WaterFurnace dual-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump
WaterFurnace dual-compressor water-to-air heat pumps with two Aurora Base Controllers (ABC A and B) and the Aurora UPC.
Also known as: PL1500EW, Aurora Universal Protocol Converter, Aurora UPC dual compressor - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer
WaterFurnace single-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Variable Speed Water-Source Heat Pump
WaterFurnace variable speed water-to-air heat pumps with Aurora controls and the Aurora UPC.
Also known as: PL1700EW, Aurora Universal Protocol Converter, Aurora UPC variable speed - Water-source heat pump controller
WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace commercial dual-compressor water-to-air heat pumps fitted with the FX10 DDC controller.
Also known as: PRODCWA-05, PRODCWA, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Envision single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWWE-01, PROSSWWE, Envision Water-to-Water, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton
WaterFurnace Envision 1 to 6 ton water-to-air heat pumps with the DDC controller option.
Also known as: Envision BACnet Variables, Envision BACnet Variables with BI, Envision 1-6 Ton - Water-to-water heat pump / reversible chiller controller
WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)
WaterFurnace dual-compressor reversible chiller (water-to-water) heat pumps with the FX10 controller.
Also known as: PRODCWWE-06B, PRODCWWE-07B, PRODCWWE-08B, PRODCWWE - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace single-compressor water-to-air heat pumps without hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PROFXENV-00, PROFXENV, Envision FX10, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace single-compressor water-to-air heat pumps with hot gas reheat and the FX10 DDC controller.
Also known as: PROFXENV-RH-00, PROFXENV-RH, Envision hot gas reheat, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec dual-compressor water-to-water heat pumps with the FX10 DDC controller and expansion board.
Also known as: PRODCWW-02, PRODCWW, Versatec Dual Compressor, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Versatec Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWW-03, PROSSWW, Versatec Water-to-Water, WaterFurnace FX10
Source: Aurora UPC Points List (BACnet Points for Single Compressor WSHP) · AG1569EW · rev. 2014-07. Object names, instances and units are reproduced as published; descriptions are our own.