Water-cooled screw chiller / heat pump controller · BACnet points list

WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller BACnet points list

Updated 6 November 2026

Short answer

BACnet objects of the Aurora HydroLink2 controller on the TruClimate 700 single screw chiller. The list covers system enable, emergency shutdown, cold and hot water setpoints with on/off offsets, network capacity and valve positions, evaporator and condenser water temperatures and limits, compressor refrigerant and drive data, bypass and isolation valve control, and model and serial number registers.

This page lists 202 BACnet objects for the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller — 134 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.

Manufacturer
WaterFurnace
Model
Aurora HydroLink2 for TruClimate 700 Single Screw Chiller
Equipment
Water-cooled screw chiller / heat pump controller
Equipment type
Chillers
BACnet objects
202 (134 writable)
Transport
—
Firmware
HydroLink2 Single Screw BACnet objects version 1.00
Also known as
HydroLink2 Single Screw, TruClimate 700, HydroLink2
Source document
HydroLink2 Single Screw BACnet Objects · rev. Version 1.00
Download CSV 202 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WaterFurnace’s current documentation and the live device before use. Not official WaterFurnace information. Terms of use.

BMS integration notes: WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller

Integration in brief

Keep BV 37 Enabled and set BV 36 to Network while the BAS is in control. Pick the control method on MV 2 (setpoint, network, setpoint with enable) and the operating mode on MV 501, then write the cold and hot water setpoints AV 500/501. Watch MV 0 status, MV 1 mode and the evaporator leaving water temperature.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 37SystemEnable_cSystem enable; compressor stays off when DisabledCommand
BV 36NetworkControl_cSet to Network while the BAS has controlCommand
BV 2EmShutdown_cNetwork emergency shutdownCommand
MV 501OperationMode_cOperating mode: cooling, heating, free cooling, off...Command
AV 500ColdWaterSP_cCold water setpointCommand
AV 501HotWaterSP_cHot water setpointCommand
BV 33AlarmReset_cAlarm reset; return to Normal after the lockout clearsCommand
MV 1UnitMode_stCurrent operating modeRead
AV 18EvapLvgWaterTemp_stEvaporator leaving water temperatureRead
MV 0SystemStatus_stOverall status: normal, alarm, shutdown, load shed...Read

Enable & remote start

BV 37 SystemEnable_c must be Enabled for the compressor to run, and the BAS sets BV 36 NetworkControl_c to Network when it takes control. MV 2 picks setpoint (AV 500/501), network or setpoint-with-enable control; MV 501 sets the operating mode. BV 2 EmShutdown_c forces an emergency shutdown.

Sensors & values from the BMS

AV 506/507 take BAS cold and hot water control temperatures when MV 502/503 are set to option 4 (Network). AV 508 and AV 510-515 take network loop temperatures; BV 503 switches the geothermal loop values between local and network.

Watch out for

WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

202 of 202 shown
Type
AnalogBinaryMulti-state
Access
Show
WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller BACnet Points List
DescriptionStates
AV5CompADischPressure_stCompressor A discharge pressurepsigRead
AV6CompASuctPressure_stCompressor A suction pressurepsigRead
AV8CondLvgWaterTemp_stSource heat exchanger leaving water temperature°FRead
AV9CondEntWaterTemp_stSource heat exchanger entering water temperature°FRead
AV11CompASuctLineTemp_stCompressor A suction line temperature°FRead
AVmin18EvapLvgWaterTemp_stEvaporator heat exchanger leaving water temperature°FRead
AV19EvapEntWaterTemp_stEvaporator heat exchanger entering water temperature°FRead
AV37EvapLWTLowAlarmLimit_cEvaporator leaving low water temperature alarm limit (default 0°F)°FCommand
AV38EvapEWTHighAlarmLimit_cEvaporator entering high water temperature alarm limit (default 200°F)°FCommand
AV39EvapEWTLowAlarmLimit_cEvaporator entering low water temperature alarm limit (default 0°F)°FCommand
AV40EvapLWTHighAlarmLimit_cEvaporator leaving high water temperature alarm limit (default 200°F)°FCommand
AV41EvapLvgWaterHighTempFaultLimit_cEvaporator leaving high water temperature fault limit (default 200°F)°FCommand
AV42EvapEntWaterCalib_cCalibration offset for the entering evaporator water temperature sensor (default 0 Δ°F)Δ°FCommand
AV43EvapEntWaterLowTempFaultLimit_cCondensor entering low water temperature fault limit (default 0°F)°FCommand
AV44EvapEntWaterHighTempFaultLimit_cEvaporator entering high water temperature fault limit (default 200°F)°FCommand
AV45EvapLeavingWaterCalib_cCalibration offset for the leaving condensor water temperature sensor (default 0 Δ°F)Δ°FCommand
AV46EvapLvgWaterLowTempFaultLimit_cEvaporator leaving low water temperature fault limit (default 0°F)°FCommand
AV47CondLWTLowAlarmLimit_cCondensor leaving low water temperature alarm limit (default 0°F)°FCommand
AV48CondEWTHighAlarmLimit_cCondensor entering high water temperature alarm limit (default 200°F)°FCommand
AV49CondEWTLowAlarmLimit_cCondensor entering low water temperature alarm limit (default 0°F)°FCommand
AV50CondLWTHighAlarmLimit_cCondensor leaving high water temperature alarm limit (default 200°F)°FCommand
AV51SlowValveTimer_cDelay for water valves to open before compressor start (default 60 sec)secCommand
AV52CompPowerFactorAdjust_cAdjustment of the compressor power factor (default 0.88)Command
AV53MeasuredLineVoltageCal_cCalibrates the line voltage calculation (default 480 V)VCommand
AV55ABCALockoutStatusAna_stMost recent fault code for compressorRead
AV56ABCA_FP2_stCompressor FP2 temperature value°FRead
AV57ABCA_FP1_stCompressor FP1 temperature value°FRead
AV60FP2LimitOverride_cFP2 Setpoint Over-ride (default -0.1°F)°FCommand
AV61FP1LimitOverride_cFP1 Setpoint Over-ride (default -0.1°F)°FCommand
AV63CompressorHoursA_stCompressor operating hourshrRead
AV64SaturatedEvapTempA_stCompressor saturated evaporator temperature°FRead
AV65SaturatedCondTempA_stCompressor saturated condenser temperature°FRead
AV66SuperheatA_stCompressor superheat value°FRead
AV67SubcoolingA_stCompressor subcooling value°FRead
AV68EEVPositionA_stCompressor EEV position%Read
AV76ABCAAlarmStatusAna_stNumeric Fault code of most recent fault detected by ABC ARead
AV79Do Not Map - FACTORY USE ONLY!!!Internal use; do not map to BASCommand
AV80EEVStartPos_cEEV Start BAC (default 0.5)%Command
AV81EEVMoveToPos_cEEV Move to BAC (default 0.5)%Command
AV200ABCFirmwareRevision_stCurrent ABC Firmware revisionRead
AV201AXBFirmwareRevision_stCurrent AXB Firmware revisionRead
AV202VSDFirmwareRevision_stCurrent VSD Firmware revisionRead
AV203ABC_DIPSwitchSettings_stABC Dip switch settingsRead
AV204AXB_DIPswitchSettings_stAXB Dip switch settingsRead
AV210ModelNumber1-2_cModel number 1-2 settingsCommand
AV211ModelNumber3-4_cModel number 3-4 settingsCommand
AV212ModelNumber5-6_cModel number 5-6 settingsCommand
AV213ModelNumber7-8_cModel number 7-8 settingsCommand
AV214ModelNumber9-10_cModel number 9-10 settingsCommand
AV215ModelNumber11-12_cModel number 11-12 settingsCommand
AV216ModelNumber13-14_cModel number 13-14 settingsCommand
AV217ModelNumber15-16_cModel number 15-16 settingsCommand
AV218ModelNumber17-18_cModel number 17-18 settingsCommand
AV219ModelNumber19-20_cModel number 19-20 settingsCommand
AV220ModelNumber21-22_cModel number 21-22 settingsCommand
AV221ModelNumber23-24_cModel number 23-24 settingsCommand
AV222ModelNumber25-26_cModel number 25-26 settingsCommand
AV223SerialNumber1-2_cSerial number 1-2 settingsCommand
AV224SerialNumber3-4_cSerial number 3-4 settingsCommand
AV225SerialNumber5-6_cSerial number 5-6 settingsCommand
AV226SerialNumber7-8_cSerial number 7-8 settingsCommand
AV227SerialNumber9-10_cSerial number 9-10 settingsCommand
AV302CurrentCompPct_stCurrent variable speed compressor operating percentage%Read
AV303CurrentCompRPM_stCurrent variable speed compressor operating speedRPMRead
AV304MinCompPct_stMinimum variable speed compressor operating percentage from drive%Read
AV305MaxCompPct_stMaximum variable speed compressor operating percentage from drive%Read
AV307NetVarSpdPct_cTarget compressor capacity, network control (default 0)%Command
AV308VarSpdOverride_cManual override value for variable speed compressor capacity (default 0)%Command
AV309VSCompHours_stVariable speed compressor operating hourshrRead
AV312VSCompPower_stVariable speed compressor powerkWRead
AV327CompAMinPct_cMinimum compressor operating capacity setting (default 0.25)%Command
AV328CompAMaxPct_cMaximum compressor operating capacity setting (default 1)%Command
AV332RampingStep_cRamping step size for variable capacity systems (default 0.05)%Command
AV333RampingRate_cRamping rate for variable capacity systems (default 1.0 sec)secCommand
AV340CondValvePosA_stCurrent position of the isolation valve for the condensor heat exchanger%Read
AV341EvapValvePosA_stCurrent position of the isolation valve for the evaporator heat exchanger%Read
AV348MaxCondIsoVlvPos_cMaximum open position of the condenser isolation valve(s) (default 1)%Command
AV349MinCondIsoVlvPos_cMinimum open position of the condenser isolation valve(s) (default 0.5)%Command
AV350MaxEvapIsoVlvPos_cMaximum open position of the evaporator isolation valve(s) (default 1)%Command
AV351MinEvapIsoVlvPos_cMinimum open position of the evaporator isolation valve(s) (default 0.5)%Command
AV352CondTargDTHtg_cTarget condenser Delta T for heating mode operation (default 20 Δ°F)Δ°FCommand
AV353EvapTargDTHtg_cTarget evaporator Delta T for heating mode operation (default 20 Δ°F)Δ°FCommand
AV354NetEvapPos_cNetwork evaporator position (default 1)%Command
AV355NetCondPos_cNetwork condensor position (default 1)%Command
AV356NetEvap3wayPos_cNetwork evaporator 3way position (default 1)%Command
AV357NetCond3wayPos_cNetwork condensor 3way position (default 1)%Command
AV375EvapOffPos_cEvaporator off position (default 0)%Command
AV376CondOffPos_cCondensor off position (default 0)%Command
AVmin500ColdWaterSP_cCold water setpoint (default 50°F)°FCommand
AVmin501HotWaterSP_cHot water setpoint (default 80°F)°FCommand
AV502ColdDeltaOn_cOffset above cold water setpoint to start cooling (default 3 Δ°F)Δ°FCommand
AV503ColdDeltaOff_cOffset below cold water setpoint to stop cooling (default 3 Δ°F)Δ°FCommand
AV504HotDeltaOn_cOffset below hot water setpoint to start heating (default 3 Δ°F)Δ°FCommand
AV505HotDeltaOff_cOffset above hot water setpoint to stop heating (default 3 Δ°F)Δ°FCommand
AV506CW_NetworkTemp_cNetwork supplied cold water temperature value for setpoint control with network temperature°FCommand
AV507HW_NetworkTemp_cNetwork supplied hot water temperature value for setpoint control with network temperature°FCommand
AV508Geo_NetworkTemp_cNetwork supplied geothermal loop temperature°FCommand
AV509UnitOffsetTemp_cGlobal offset for heating and cooling demands (default 0°F)°FCommand
AV510NetColdInTemp_cNetwork supplied cold water in temperature value°FCommand
AV511NetColdOutTemp_cNetwork supplied cold water out temperature value°FCommand
AV512NetHotInTemp_cNetwork supplied hot water in temperature value°FCommand
AV513NetHotOutTemp_cNetwork supplied hot water out temperature value°FCommand
AV514NetGeoInTemp_cNetwork supplied geo water in temperature value°FCommand
AV515NetGeoOutTemp_cNetwork supplied geo water out temperature values°FCommand
AV516MaxHotBypass_cMaximum open position for hot loop bypass valve (default 1)%Command
AV517MaxColdBypass_cMaximum open position for cold loop bypass valve (default 1)%Command
AV518MaxGeoBypass_cMaximum open position for geo loop bypass valve (default 1)%Command
AV519BypassValveOffset_cControl valve percent closed before its bypass valve opens (default 0.3)%Command
AV520MinLoadValvePos_cMinimum position the load control valves will modulate to during operation (default 0.1)%Command
AV521MinSourceValvePos_cMinimum position the source control valves will modulate to during operation (default 0.1)%Command
AV522NetColdBypass_cCold bypass valve position under network control (BV 501 Active) (default 1)%Command
AV523NetHotBypass_cHot bypass valve position under network control (BV 501 Active) (default 1)%Command
AV524NetGeoBypass_cGeo bypass valve position under network control (BV 501 Active) (default 1)%Command
AV528PropCool_cCooling PID proportional constant (default 2)Command
AV529IntCool_cCooling PID integral constant (default 0.3)Command
AV530DerivCool_cCooling PID derivative constant (default 0.1)Command
AV531CoolExecuteTime_cCooling PID execution time (default 5 sec)secCommand
AV532CoolRampTime_cCooling PID ramp time (min time for 0-100%) (default 15 min)minCommand
AV533PropHeat_cHeating PID proportional constant (default 2)Command
AV534IntHeat_cHeating PID integral constant (default 0.3)Command
AV535DerivHeat_cHeating PID derivative constant (default 0.1)Command
AV536HeatExecuteTime_cHeating PID execution time (default 5 sec)secCommand
AV537HeatRampTime_cHeating PID ramp time (min time for 0-100%) (default 15 min)minCommand
AV538LoadValveProp_cEvaporator valve PID proportional constant (default 2)Command
AV539LoadValveInt_cEvaporator valve PID integral constant (default 1)Command
AV540LoadValveExecute_cEvaporator valve PID execution time (default 0.5 sec)secCommand
AV541SourceValveProp_cCondensor valve PID proportional constant (default 2)Command
AV542CondValveInt_cCondensor valve PID integral constant (default 1)Command
AV543CondValveExecute_cCondensor valve PID execution time (default 0.5 sec)secCommand
AV544LoadInTemp_stEvaporator heat exchanger entering water temperature (same as AV:19)°FRead
AV545LoadOutTemp_stEvaporator heat exchanger leaving water temperature (same as AV:18)°FRead
AV546SourceInTemp_stCondensor heat exchanger entering water temperature (same as AV:9)°FRead
AV547SourceOutTemp_stCondensor heat exchanger leaving water temperature (same as AV:8)°FRead
AV548ColdHeaderInletTemp_stCold water loop inlet temperature measured by HydroLink controller°FRead
AV549ColdHeaderOutletTemp_stCold water loop outlet temperature measured by HydroLink controller°FRead
AV550HotHeaderInletTemp_stHot water loop inlet temperature measured by HydroLink controller°FRead
AV551HotHeaderOutletTemp_stHot water loop outlet temperature measured by HydroLink controller°FRead
AV552GeoHeaderInletTemp_stGeothermal loop water inlet temperature measured by HydroLink controller°FRead
AV553GeoHeaderOutletTemp_stGeothermal loop water outlet temperature measured by HydroLink controller°FRead
AV554ActiveColdWaterTemp_stActive cold water control temperature°FRead
AV555ActiveHotWaterTemp_stActive hot water control temperature°FRead
AV556ActiveGeoWaterTemp_stActive geothermal water temperature°FRead
AV557CurrentDemandPct_stCalculated PID operating demand percentage%Read
AV558Evap3WayValve_stCurrent position of 3-way evaporator control valve%Read
AV559Cond3WayValve_stCurrent position of 3-way condensor control valve%Read
AV560ColdBypassValve_stCurrent position of cold water loop bypass valve%Read
AV561HotBypassValve_stCurrent position of hot water loop bypass valve%Read
AV563ManEva3WayValvePct_cManually controlled position of 3-way evaporator control valve (default 0)%Command
AV564ManCond3WayValvePct_cManually controlled position of 3-way condensor control valve (default 0)%Command
AV565ManColdBypassValvePct_cManually controlled position of cold water loop bypass valve (default 0)%Command
AV566ManHotBypassValvePct_cManually controlled position of hot water loop bypass valve (default 0)%Command
AV567ManGeoBypassValvePct_cManually controlled position of geothermal water loop bypass valve (default 0)%Command
AV569ManEvapIsoValvePct_cManual evaporator isolation valve BAC (default 0)%Command
AV570ManCondIsoValvePct_cManual condensor isolation valve BAC (default 0)%Command
MVmin0SystemStatus_stCurrent overall system statusRead1=Normal, 2=Alarm, 3=Shutdown, 4=Load Shed, 5=ABC Communication Loss, 6=AXB Communication Loss, 7=Evap Entering Water Temp Alarm, 8=Evap Leaving Water Temp Alarm, 9=Cond Entering Water Temp Alarm, 10=Cond Leaving Water Temp Alarm, 11=Cold Water Sensor Fault, 12=Hot Water Sensor Fault, 13=Geo Water Sensor Fault
MVmin1UnitMode_stCurrent overall system operating modeRead1=Standby, 2=Compressor Cooling, 3=Compressors Heating, 4=Compressor Full Building, 5=Compressors Primary Cooling, 6=Compressors Primary Heating, 7=Free Cooling, 8=Emergency Shutdown, 9=Load Shed, 10=Lockout, 11=Test Mode, 12=Startup Delay, 13=Cond Flow Switch Fault, 14=Evap Flow Switch Fault, 15=Evap and Cond Flow Switch Fault
MV2TempControlMethod_cSelects temperature control method for non-header rack applications (default 1)Command1=Setpoint (uses AV:500 or AV:501 as setpoint), 2=Network, 3=Setpoint with Enable, 4=Niagara
MV5EnergyMonitorMode_cAurora controls energy monitoring modes selection (default 3)Command1=Off, 2=Compressor Monitoring, 3=Energy Monitoring
MV10ABCALockoutStatus_stEnumerated description of most recent fault detected by ABC ARead
MV12ABCAAlarmStatus_stEnumerated description of a currently active fault detected by ABC ARead
MV500HeaderRackType_cHeader rack selection value (default 1)Command1=No header, 3=4 Pipe Reversing, 4=6 Pipe Standard
MVmin501OperationMode_cOperating mode selection (default 8)Command1=Cooling only, 2=Heating only, 3=Auto full building, 4=Full building, 5=Primary cooling, 6=Primary heating, 7=Free Cooling, 99=System off
MV502ColdWaterSelect_cSelects cold water control temperature (default 1)Command1=Heat Exchanger Out, 2=Cold Water Out, 3=Cold Water In, 4=Network (AV:506)
MV503HotWaterSelect_cSelects hot water control temperature (default 1)Command1=Heat Exchanger Out, 2=Hot Water Out, 3=Hot Water In, 4=Network (AV:507)
BVmin2EmShutdown_cEnable/disable Emergency ShutdownCommandInactive=Normal, Active=Shutdown
BV4LoadShedA_cEnable/disable Load Shed on Compressor ACommandInactive=Inactive, Active=Active
BV5EnableManualOverride_cEnable/disable Manual Override of Y1, Y2, O/B logic outputsCommandInactive=Disabled, Active=Enabled
BV9TestModeCommand_cEnable/disable the test mode of the Aurora control systemCommandInactive=Normal, Active=Test Mode
BV10PowerPhaseSelect_cSingle or three phase power for power calculationsCommandInactive=Single Phase, Active=Three Phase
BV11ABCA_HDW_ALM_stStatus of ABC A alarm outputReadInactive=Off, Active=On
BV12ABCA_HDW_Y1_stStatus of ABC A physical Y1 inputReadInactive=Off, Active=On
BV13ABCA_HDW_Y2_stStatus of ABC A physical Y2 inputReadInactive=Off, Active=On
BV14ABCA_HDW_OB_stStatus of ABC A physical O/B inputReadInactive=Off, Active=On
BV15ABCA_HDW_ES_stStatus of ABC A physical emergency shutdown inputReadInactive=Normal, Active=Shutdown
BV16ABCA_HDW_LPS_stStatus of ABC A physical low pressure switch inputReadInactive=Open, Active=Closed
BV17ABCA_HDW_HPS_stStatus of ABC A physical high pressure switch inputReadInactive=Open, Active=Closed
BV18ABCA_HDW_LS_stStatus of ABC A physical load shed inputReadInactive=Inactive, Active=Active
BV19ABCA_HDW_CC_stStatus of ABC A compressor outputReadInactive=Off, Active=On
BV20ABCA_HDW_RV_stStatus of ABC A reversing valve outputReadInactive=Off, Active=On
BV21ABCA_HDW_ACC_stStatus of ABC A accessory relay outputReadInactive=Off, Active=On
BVmin33AlarmReset_cAlarm reset command to clear lockout conditionCommandInactive=Normal, Active=Reset
BVmin36NetworkControl_cIndication that system is under network controlCommandInactive=Normal, Active=Network
BVmin37SystemEnable_cEnables (True) or Disables (False) system operationCommandInactive=Disabled, Active=Enabled
BV38CondFlowSw_stCondenser loop flow switch (On = flow)ReadInactive=Off, Active=On
BV39EvapFlowSw_stEvaporator loop flow switch (On = flow)ReadInactive=Off, Active=On
BV45Do Not Map - FACTORY USE ONLY!!!Internal use; do not map to BASCommandInactive=False, Active=True
BV46SystemSave_cSave AllCommandInactive=Normal, Active=Save
BV47ClrFaults_cClr Faults BACCommandInactive=Normal, Active=Save
BV304CondHPCEnable_cEnable condenser head pressure control (envelope protection)CommandInactive=Inactive, Active=Active
BV305EvapMOPEnable_cEnable evaporator maximum pressure control (envelope protection)CommandInactive=Inactive, Active=Active
BV307CondHtgDeltaEnable_cEnable delta control, condenser isolation valve, heatingCommandInactive=Inactive, Active=Active
BV309EvapHtgDeltaEnable_cEnable delta control, evaporator isolation valve, heatingCommandInactive=Inactive, Active=Active
BV310NetIsoCtrl_cDelta control variable, condenser isolation valve, coolingCommandInactive=False, Active=True
BV311Net3wayCtrl_cDelta control variable, condenser isolation valve, heatingCommandInactive=False, Active=True
BV501NetBypassCtrl_cLocal or network control of bypass valvesCommandInactive=Inactive, Active=Active
BV502Man3wayValveCtrl_cManual 3way valve controlCommandInactive=Inactive, Active=Active
BV503GeoWaterSelect_cSelection between Local (False) and Network (True) geothermal loop temperature valuesCommandInactive=Local, Active=Network
BV504ManBypassValves_cManual Bypass valve control BACCommandInactive=Inactive, Active=Active
BV507CWSensorFault_stIndication that the currently selected cold water control temperature is invalidReadInactive=False, Active=True
BV508HWSensorFault_stIndication that the currently selected hot water control temperature is invalidReadInactive=False, Active=True
BV509TempSensorFault_stSelected cold or hot water control temperature is invalidReadInactive=False, Active=True
BV510ManIsoValves_cManual control value for isolation valvesCommandInactive=Inactive, Active=Active
Object ID lookup: WaterFurnace Aurora HydroLink2 TruClimate 700 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aurora HydroLink2 for TruClimate 700 Single Screw Chiller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller

How many BACnet points does the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller have?

This list has 202 BACnet objects: 154 analog values, 38 binary values, 10 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller BACnet points are writable?

134 of the 202 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller BACnet documentation?

The source is HydroLink2 Single Screw BACnet Objects, revision Version 1.00, published free by WaterFurnace at https://www.waterfurnace.com/literature/aurora/HydroLink2-BACnet-Objects-Single%20Screw-Version-1.00.xlsx.

What are the minimum BACnet points to integrate the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller?

Start with BV 37 SystemEnable_c (System enable; compressor stays off when Disabled); BV 36 NetworkControl_c (Set to Network while the BAS has control); BV 2 EmShutdown_c (Network emergency shutdown); MV 501 OperationMode_c (Operating mode: cooling, heating, free cooling, off); AV 500 ColdWaterSP_c (Cold water setpoint); AV 501 HotWaterSP_c (Hot water setpoint); BV 33 AlarmReset_c (Alarm reset; return to Normal after the lockout clears); MV 1 UnitMode_st (Current operating mode); AV 18 EvapLvgWaterTemp_st (Evaporator leaving water temperature); MV 0 SystemStatus_st (Overall status: normal, alarm, shutdown, load shed).

How do I enable BMS control of the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller?

BV 37 SystemEnable_c must be Enabled for the compressor to run, and the BAS sets BV 36 NetworkControl_c to Network when it takes control. MV 2 picks setpoint (AV 500/501), network or setpoint-with-enable control; MV 501 sets the operating mode. BV 2 EmShutdown_c forces an emergency shutdown.

Can the BMS supply sensor values to the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller?

AV 506/507 take BAS cold and hot water control temperatures when MV 502/503 are set to option 4 (Network). AV 508 and AV 510-515 take network loop temperatures; BV 503 switches the geothermal loop values between local and network.

How do I check these points on the real Aurora HydroLink2 for TruClimate 700 Single Screw Chiller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WaterFurnace BACnet points lists