Water-cooled screw chiller / heat pump controller · BACnet points list
WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller BACnet points list
Updated 6 November 2026
BACnet objects of the Aurora HydroLink2 controller on the TruClimate 700 single screw chiller. The list covers system enable, emergency shutdown, cold and hot water setpoints with on/off offsets, network capacity and valve positions, evaporator and condenser water temperatures and limits, compressor refrigerant and drive data, bypass and isolation valve control, and model and serial number registers.
This page lists 202 BACnet objects for the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller — 134 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.
- Manufacturer
- WaterFurnace
- Model
- Aurora HydroLink2 for TruClimate 700 Single Screw Chiller
- Equipment
- Water-cooled screw chiller / heat pump controller
- Equipment type
- Chillers
- BACnet objects
- 202 (134 writable)
- Transport
- —
- Firmware
- HydroLink2 Single Screw BACnet objects version 1.00
- Also known as
- HydroLink2 Single Screw, TruClimate 700, HydroLink2
- Source document
- HydroLink2 Single Screw BACnet Objects · rev. Version 1.00
Reference only, provided as-is: verify against WaterFurnace’s current documentation and the live device before use. Not official WaterFurnace information. Terms of use.
BMS integration notes: WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller
Keep BV 37 Enabled and set BV 36 to Network while the BAS is in control. Pick the control method on MV 2 (setpoint, network, setpoint with enable) and the operating mode on MV 501, then write the cold and hot water setpoints AV 500/501. Watch MV 0 status, MV 1 mode and the evaporator leaving water temperature.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 37 | SystemEnable_c | System enable; compressor stays off when Disabled | Command |
| BV 36 | NetworkControl_c | Set to Network while the BAS has control | Command |
| BV 2 | EmShutdown_c | Network emergency shutdown | Command |
| MV 501 | OperationMode_c | Operating mode: cooling, heating, free cooling, off... | Command |
| AV 500 | ColdWaterSP_c | Cold water setpoint | Command |
| AV 501 | HotWaterSP_c | Hot water setpoint | Command |
| BV 33 | AlarmReset_c | Alarm reset; return to Normal after the lockout clears | Command |
| MV 1 | UnitMode_st | Current operating mode | Read |
| AV 18 | EvapLvgWaterTemp_st | Evaporator leaving water temperature | Read |
| MV 0 | SystemStatus_st | Overall status: normal, alarm, shutdown, load shed... | Read |
Enable & remote start
BV 37 SystemEnable_c must be Enabled for the compressor to run, and the BAS sets BV 36 NetworkControl_c to Network when it takes control. MV 2 picks setpoint (AV 500/501), network or setpoint-with-enable control; MV 501 sets the operating mode. BV 2 EmShutdown_c forces an emergency shutdown.
Sensors & values from the BMS
AV 506/507 take BAS cold and hot water control temperatures when MV 502/503 are set to option 4 (Network). AV 508 and AV 510-515 take network loop temperatures; BV 503 switches the geothermal loop values between local and network.
Watch out for
- AV 307 NetVarSpdPct_c sets compressor capacity under network control; AV 327/328 hold the minimum and maximum capacity.
- BV 5 EnableManualOverride_c enables manual output overrides; normal logic keeps running underneath.
- Model and serial number registers (AV 210-227) are writable; don't write them from the BMS.
- Clear BV 33 AlarmReset_c back to Normal once the lockout condition is gone.
WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 5 | CompADischPressure_st | Compressor A discharge pressure | psig | Read | |
| AV | 6 | CompASuctPressure_st | Compressor A suction pressure | psig | Read | |
| AV | 8 | CondLvgWaterTemp_st | Source heat exchanger leaving water temperature | °F | Read | |
| AV | 9 | CondEntWaterTemp_st | Source heat exchanger entering water temperature | °F | Read | |
| AV | 11 | CompASuctLineTemp_st | Compressor A suction line temperature | °F | Read | |
| AVmin | 18 | EvapLvgWaterTemp_st | Evaporator heat exchanger leaving water temperature | °F | Read | |
| AV | 19 | EvapEntWaterTemp_st | Evaporator heat exchanger entering water temperature | °F | Read | |
| AV | 37 | EvapLWTLowAlarmLimit_c | Evaporator leaving low water temperature alarm limit (default 0°F) | °F | Command | |
| AV | 38 | EvapEWTHighAlarmLimit_c | Evaporator entering high water temperature alarm limit (default 200°F) | °F | Command | |
| AV | 39 | EvapEWTLowAlarmLimit_c | Evaporator entering low water temperature alarm limit (default 0°F) | °F | Command | |
| AV | 40 | EvapLWTHighAlarmLimit_c | Evaporator leaving high water temperature alarm limit (default 200°F) | °F | Command | |
| AV | 41 | EvapLvgWaterHighTempFaultLimit_c | Evaporator leaving high water temperature fault limit (default 200°F) | °F | Command | |
| AV | 42 | EvapEntWaterCalib_c | Calibration offset for the entering evaporator water temperature sensor (default 0 Δ°F) | Δ°F | Command | |
| AV | 43 | EvapEntWaterLowTempFaultLimit_c | Condensor entering low water temperature fault limit (default 0°F) | °F | Command | |
| AV | 44 | EvapEntWaterHighTempFaultLimit_c | Evaporator entering high water temperature fault limit (default 200°F) | °F | Command | |
| AV | 45 | EvapLeavingWaterCalib_c | Calibration offset for the leaving condensor water temperature sensor (default 0 Δ°F) | Δ°F | Command | |
| AV | 46 | EvapLvgWaterLowTempFaultLimit_c | Evaporator leaving low water temperature fault limit (default 0°F) | °F | Command | |
| AV | 47 | CondLWTLowAlarmLimit_c | Condensor leaving low water temperature alarm limit (default 0°F) | °F | Command | |
| AV | 48 | CondEWTHighAlarmLimit_c | Condensor entering high water temperature alarm limit (default 200°F) | °F | Command | |
| AV | 49 | CondEWTLowAlarmLimit_c | Condensor entering low water temperature alarm limit (default 0°F) | °F | Command | |
| AV | 50 | CondLWTHighAlarmLimit_c | Condensor leaving high water temperature alarm limit (default 200°F) | °F | Command | |
| AV | 51 | SlowValveTimer_c | Delay for water valves to open before compressor start (default 60 sec) | sec | Command | |
| AV | 52 | CompPowerFactorAdjust_c | Adjustment of the compressor power factor (default 0.88) | Command | ||
| AV | 53 | MeasuredLineVoltageCal_c | Calibrates the line voltage calculation (default 480 V) | V | Command | |
| AV | 55 | ABCALockoutStatusAna_st | Most recent fault code for compressor | Read | ||
| AV | 56 | ABCA_FP2_st | Compressor FP2 temperature value | °F | Read | |
| AV | 57 | ABCA_FP1_st | Compressor FP1 temperature value | °F | Read | |
| AV | 60 | FP2LimitOverride_c | FP2 Setpoint Over-ride (default -0.1°F) | °F | Command | |
| AV | 61 | FP1LimitOverride_c | FP1 Setpoint Over-ride (default -0.1°F) | °F | Command | |
| AV | 63 | CompressorHoursA_st | Compressor operating hours | hr | Read | |
| AV | 64 | SaturatedEvapTempA_st | Compressor saturated evaporator temperature | °F | Read | |
| AV | 65 | SaturatedCondTempA_st | Compressor saturated condenser temperature | °F | Read | |
| AV | 66 | SuperheatA_st | Compressor superheat value | °F | Read | |
| AV | 67 | SubcoolingA_st | Compressor subcooling value | °F | Read | |
| AV | 68 | EEVPositionA_st | Compressor EEV position | % | Read | |
| AV | 76 | ABCAAlarmStatusAna_st | Numeric Fault code of most recent fault detected by ABC A | Read | ||
| AV | 79 | Do Not Map - FACTORY USE ONLY!!! | Internal use; do not map to BAS | Command | ||
| AV | 80 | EEVStartPos_c | EEV Start BAC (default 0.5) | % | Command | |
| AV | 81 | EEVMoveToPos_c | EEV Move to BAC (default 0.5) | % | Command | |
| AV | 200 | ABCFirmwareRevision_st | Current ABC Firmware revision | Read | ||
| AV | 201 | AXBFirmwareRevision_st | Current AXB Firmware revision | Read | ||
| AV | 202 | VSDFirmwareRevision_st | Current VSD Firmware revision | Read | ||
| AV | 203 | ABC_DIPSwitchSettings_st | ABC Dip switch settings | Read | ||
| AV | 204 | AXB_DIPswitchSettings_st | AXB Dip switch settings | Read | ||
| AV | 210 | ModelNumber1-2_c | Model number 1-2 settings | Command | ||
| AV | 211 | ModelNumber3-4_c | Model number 3-4 settings | Command | ||
| AV | 212 | ModelNumber5-6_c | Model number 5-6 settings | Command | ||
| AV | 213 | ModelNumber7-8_c | Model number 7-8 settings | Command | ||
| AV | 214 | ModelNumber9-10_c | Model number 9-10 settings | Command | ||
| AV | 215 | ModelNumber11-12_c | Model number 11-12 settings | Command | ||
| AV | 216 | ModelNumber13-14_c | Model number 13-14 settings | Command | ||
| AV | 217 | ModelNumber15-16_c | Model number 15-16 settings | Command | ||
| AV | 218 | ModelNumber17-18_c | Model number 17-18 settings | Command | ||
| AV | 219 | ModelNumber19-20_c | Model number 19-20 settings | Command | ||
| AV | 220 | ModelNumber21-22_c | Model number 21-22 settings | Command | ||
| AV | 221 | ModelNumber23-24_c | Model number 23-24 settings | Command | ||
| AV | 222 | ModelNumber25-26_c | Model number 25-26 settings | Command | ||
| AV | 223 | SerialNumber1-2_c | Serial number 1-2 settings | Command | ||
| AV | 224 | SerialNumber3-4_c | Serial number 3-4 settings | Command | ||
| AV | 225 | SerialNumber5-6_c | Serial number 5-6 settings | Command | ||
| AV | 226 | SerialNumber7-8_c | Serial number 7-8 settings | Command | ||
| AV | 227 | SerialNumber9-10_c | Serial number 9-10 settings | Command | ||
| AV | 302 | CurrentCompPct_st | Current variable speed compressor operating percentage | % | Read | |
| AV | 303 | CurrentCompRPM_st | Current variable speed compressor operating speed | RPM | Read | |
| AV | 304 | MinCompPct_st | Minimum variable speed compressor operating percentage from drive | % | Read | |
| AV | 305 | MaxCompPct_st | Maximum variable speed compressor operating percentage from drive | % | Read | |
| AV | 307 | NetVarSpdPct_c | Target compressor capacity, network control (default 0) | % | Command | |
| AV | 308 | VarSpdOverride_c | Manual override value for variable speed compressor capacity (default 0) | % | Command | |
| AV | 309 | VSCompHours_st | Variable speed compressor operating hours | hr | Read | |
| AV | 312 | VSCompPower_st | Variable speed compressor power | kW | Read | |
| AV | 327 | CompAMinPct_c | Minimum compressor operating capacity setting (default 0.25) | % | Command | |
| AV | 328 | CompAMaxPct_c | Maximum compressor operating capacity setting (default 1) | % | Command | |
| AV | 332 | RampingStep_c | Ramping step size for variable capacity systems (default 0.05) | % | Command | |
| AV | 333 | RampingRate_c | Ramping rate for variable capacity systems (default 1.0 sec) | sec | Command | |
| AV | 340 | CondValvePosA_st | Current position of the isolation valve for the condensor heat exchanger | % | Read | |
| AV | 341 | EvapValvePosA_st | Current position of the isolation valve for the evaporator heat exchanger | % | Read | |
| AV | 348 | MaxCondIsoVlvPos_c | Maximum open position of the condenser isolation valve(s) (default 1) | % | Command | |
| AV | 349 | MinCondIsoVlvPos_c | Minimum open position of the condenser isolation valve(s) (default 0.5) | % | Command | |
| AV | 350 | MaxEvapIsoVlvPos_c | Maximum open position of the evaporator isolation valve(s) (default 1) | % | Command | |
| AV | 351 | MinEvapIsoVlvPos_c | Minimum open position of the evaporator isolation valve(s) (default 0.5) | % | Command | |
| AV | 352 | CondTargDTHtg_c | Target condenser Delta T for heating mode operation (default 20 Δ°F) | Δ°F | Command | |
| AV | 353 | EvapTargDTHtg_c | Target evaporator Delta T for heating mode operation (default 20 Δ°F) | Δ°F | Command | |
| AV | 354 | NetEvapPos_c | Network evaporator position (default 1) | % | Command | |
| AV | 355 | NetCondPos_c | Network condensor position (default 1) | % | Command | |
| AV | 356 | NetEvap3wayPos_c | Network evaporator 3way position (default 1) | % | Command | |
| AV | 357 | NetCond3wayPos_c | Network condensor 3way position (default 1) | % | Command | |
| AV | 375 | EvapOffPos_c | Evaporator off position (default 0) | % | Command | |
| AV | 376 | CondOffPos_c | Condensor off position (default 0) | % | Command | |
| AVmin | 500 | ColdWaterSP_c | Cold water setpoint (default 50°F) | °F | Command | |
| AVmin | 501 | HotWaterSP_c | Hot water setpoint (default 80°F) | °F | Command | |
| AV | 502 | ColdDeltaOn_c | Offset above cold water setpoint to start cooling (default 3 Δ°F) | Δ°F | Command | |
| AV | 503 | ColdDeltaOff_c | Offset below cold water setpoint to stop cooling (default 3 Δ°F) | Δ°F | Command | |
| AV | 504 | HotDeltaOn_c | Offset below hot water setpoint to start heating (default 3 Δ°F) | Δ°F | Command | |
| AV | 505 | HotDeltaOff_c | Offset above hot water setpoint to stop heating (default 3 Δ°F) | Δ°F | Command | |
| AV | 506 | CW_NetworkTemp_c | Network supplied cold water temperature value for setpoint control with network temperature | °F | Command | |
| AV | 507 | HW_NetworkTemp_c | Network supplied hot water temperature value for setpoint control with network temperature | °F | Command | |
| AV | 508 | Geo_NetworkTemp_c | Network supplied geothermal loop temperature | °F | Command | |
| AV | 509 | UnitOffsetTemp_c | Global offset for heating and cooling demands (default 0°F) | °F | Command | |
| AV | 510 | NetColdInTemp_c | Network supplied cold water in temperature value | °F | Command | |
| AV | 511 | NetColdOutTemp_c | Network supplied cold water out temperature value | °F | Command | |
| AV | 512 | NetHotInTemp_c | Network supplied hot water in temperature value | °F | Command | |
| AV | 513 | NetHotOutTemp_c | Network supplied hot water out temperature value | °F | Command | |
| AV | 514 | NetGeoInTemp_c | Network supplied geo water in temperature value | °F | Command | |
| AV | 515 | NetGeoOutTemp_c | Network supplied geo water out temperature values | °F | Command | |
| AV | 516 | MaxHotBypass_c | Maximum open position for hot loop bypass valve (default 1) | % | Command | |
| AV | 517 | MaxColdBypass_c | Maximum open position for cold loop bypass valve (default 1) | % | Command | |
| AV | 518 | MaxGeoBypass_c | Maximum open position for geo loop bypass valve (default 1) | % | Command | |
| AV | 519 | BypassValveOffset_c | Control valve percent closed before its bypass valve opens (default 0.3) | % | Command | |
| AV | 520 | MinLoadValvePos_c | Minimum position the load control valves will modulate to during operation (default 0.1) | % | Command | |
| AV | 521 | MinSourceValvePos_c | Minimum position the source control valves will modulate to during operation (default 0.1) | % | Command | |
| AV | 522 | NetColdBypass_c | Cold bypass valve position under network control (BV 501 Active) (default 1) | % | Command | |
| AV | 523 | NetHotBypass_c | Hot bypass valve position under network control (BV 501 Active) (default 1) | % | Command | |
| AV | 524 | NetGeoBypass_c | Geo bypass valve position under network control (BV 501 Active) (default 1) | % | Command | |
| AV | 528 | PropCool_c | Cooling PID proportional constant (default 2) | Command | ||
| AV | 529 | IntCool_c | Cooling PID integral constant (default 0.3) | Command | ||
| AV | 530 | DerivCool_c | Cooling PID derivative constant (default 0.1) | Command | ||
| AV | 531 | CoolExecuteTime_c | Cooling PID execution time (default 5 sec) | sec | Command | |
| AV | 532 | CoolRampTime_c | Cooling PID ramp time (min time for 0-100%) (default 15 min) | min | Command | |
| AV | 533 | PropHeat_c | Heating PID proportional constant (default 2) | Command | ||
| AV | 534 | IntHeat_c | Heating PID integral constant (default 0.3) | Command | ||
| AV | 535 | DerivHeat_c | Heating PID derivative constant (default 0.1) | Command | ||
| AV | 536 | HeatExecuteTime_c | Heating PID execution time (default 5 sec) | sec | Command | |
| AV | 537 | HeatRampTime_c | Heating PID ramp time (min time for 0-100%) (default 15 min) | min | Command | |
| AV | 538 | LoadValveProp_c | Evaporator valve PID proportional constant (default 2) | Command | ||
| AV | 539 | LoadValveInt_c | Evaporator valve PID integral constant (default 1) | Command | ||
| AV | 540 | LoadValveExecute_c | Evaporator valve PID execution time (default 0.5 sec) | sec | Command | |
| AV | 541 | SourceValveProp_c | Condensor valve PID proportional constant (default 2) | Command | ||
| AV | 542 | CondValveInt_c | Condensor valve PID integral constant (default 1) | Command | ||
| AV | 543 | CondValveExecute_c | Condensor valve PID execution time (default 0.5 sec) | sec | Command | |
| AV | 544 | LoadInTemp_st | Evaporator heat exchanger entering water temperature (same as AV:19) | °F | Read | |
| AV | 545 | LoadOutTemp_st | Evaporator heat exchanger leaving water temperature (same as AV:18) | °F | Read | |
| AV | 546 | SourceInTemp_st | Condensor heat exchanger entering water temperature (same as AV:9) | °F | Read | |
| AV | 547 | SourceOutTemp_st | Condensor heat exchanger leaving water temperature (same as AV:8) | °F | Read | |
| AV | 548 | ColdHeaderInletTemp_st | Cold water loop inlet temperature measured by HydroLink controller | °F | Read | |
| AV | 549 | ColdHeaderOutletTemp_st | Cold water loop outlet temperature measured by HydroLink controller | °F | Read | |
| AV | 550 | HotHeaderInletTemp_st | Hot water loop inlet temperature measured by HydroLink controller | °F | Read | |
| AV | 551 | HotHeaderOutletTemp_st | Hot water loop outlet temperature measured by HydroLink controller | °F | Read | |
| AV | 552 | GeoHeaderInletTemp_st | Geothermal loop water inlet temperature measured by HydroLink controller | °F | Read | |
| AV | 553 | GeoHeaderOutletTemp_st | Geothermal loop water outlet temperature measured by HydroLink controller | °F | Read | |
| AV | 554 | ActiveColdWaterTemp_st | Active cold water control temperature | °F | Read | |
| AV | 555 | ActiveHotWaterTemp_st | Active hot water control temperature | °F | Read | |
| AV | 556 | ActiveGeoWaterTemp_st | Active geothermal water temperature | °F | Read | |
| AV | 557 | CurrentDemandPct_st | Calculated PID operating demand percentage | % | Read | |
| AV | 558 | Evap3WayValve_st | Current position of 3-way evaporator control valve | % | Read | |
| AV | 559 | Cond3WayValve_st | Current position of 3-way condensor control valve | % | Read | |
| AV | 560 | ColdBypassValve_st | Current position of cold water loop bypass valve | % | Read | |
| AV | 561 | HotBypassValve_st | Current position of hot water loop bypass valve | % | Read | |
| AV | 563 | ManEva3WayValvePct_c | Manually controlled position of 3-way evaporator control valve (default 0) | % | Command | |
| AV | 564 | ManCond3WayValvePct_c | Manually controlled position of 3-way condensor control valve (default 0) | % | Command | |
| AV | 565 | ManColdBypassValvePct_c | Manually controlled position of cold water loop bypass valve (default 0) | % | Command | |
| AV | 566 | ManHotBypassValvePct_c | Manually controlled position of hot water loop bypass valve (default 0) | % | Command | |
| AV | 567 | ManGeoBypassValvePct_c | Manually controlled position of geothermal water loop bypass valve (default 0) | % | Command | |
| AV | 569 | ManEvapIsoValvePct_c | Manual evaporator isolation valve BAC (default 0) | % | Command | |
| AV | 570 | ManCondIsoValvePct_c | Manual condensor isolation valve BAC (default 0) | % | Command | |
| MVmin | 0 | SystemStatus_st | Current overall system status | Read | 1=Normal, 2=Alarm, 3=Shutdown, 4=Load Shed, 5=ABC Communication Loss, 6=AXB Communication Loss, 7=Evap Entering Water Temp Alarm, 8=Evap Leaving Water Temp Alarm, 9=Cond Entering Water Temp Alarm, 10=Cond Leaving Water Temp Alarm, 11=Cold Water Sensor Fault, 12=Hot Water Sensor Fault, 13=Geo Water Sensor Fault | |
| MVmin | 1 | UnitMode_st | Current overall system operating mode | Read | 1=Standby, 2=Compressor Cooling, 3=Compressors Heating, 4=Compressor Full Building, 5=Compressors Primary Cooling, 6=Compressors Primary Heating, 7=Free Cooling, 8=Emergency Shutdown, 9=Load Shed, 10=Lockout, 11=Test Mode, 12=Startup Delay, 13=Cond Flow Switch Fault, 14=Evap Flow Switch Fault, 15=Evap and Cond Flow Switch Fault | |
| MV | 2 | TempControlMethod_c | Selects temperature control method for non-header rack applications (default 1) | Command | 1=Setpoint (uses AV:500 or AV:501 as setpoint), 2=Network, 3=Setpoint with Enable, 4=Niagara | |
| MV | 5 | EnergyMonitorMode_c | Aurora controls energy monitoring modes selection (default 3) | Command | 1=Off, 2=Compressor Monitoring, 3=Energy Monitoring | |
| MV | 10 | ABCALockoutStatus_st | Enumerated description of most recent fault detected by ABC A | Read | ||
| MV | 12 | ABCAAlarmStatus_st | Enumerated description of a currently active fault detected by ABC A | Read | ||
| MV | 500 | HeaderRackType_c | Header rack selection value (default 1) | Command | 1=No header, 3=4 Pipe Reversing, 4=6 Pipe Standard | |
| MVmin | 501 | OperationMode_c | Operating mode selection (default 8) | Command | 1=Cooling only, 2=Heating only, 3=Auto full building, 4=Full building, 5=Primary cooling, 6=Primary heating, 7=Free Cooling, 99=System off | |
| MV | 502 | ColdWaterSelect_c | Selects cold water control temperature (default 1) | Command | 1=Heat Exchanger Out, 2=Cold Water Out, 3=Cold Water In, 4=Network (AV:506) | |
| MV | 503 | HotWaterSelect_c | Selects hot water control temperature (default 1) | Command | 1=Heat Exchanger Out, 2=Hot Water Out, 3=Hot Water In, 4=Network (AV:507) | |
| BVmin | 2 | EmShutdown_c | Enable/disable Emergency Shutdown | Command | Inactive=Normal, Active=Shutdown | |
| BV | 4 | LoadShedA_c | Enable/disable Load Shed on Compressor A | Command | Inactive=Inactive, Active=Active | |
| BV | 5 | EnableManualOverride_c | Enable/disable Manual Override of Y1, Y2, O/B logic outputs | Command | Inactive=Disabled, Active=Enabled | |
| BV | 9 | TestModeCommand_c | Enable/disable the test mode of the Aurora control system | Command | Inactive=Normal, Active=Test Mode | |
| BV | 10 | PowerPhaseSelect_c | Single or three phase power for power calculations | Command | Inactive=Single Phase, Active=Three Phase | |
| BV | 11 | ABCA_HDW_ALM_st | Status of ABC A alarm output | Read | Inactive=Off, Active=On | |
| BV | 12 | ABCA_HDW_Y1_st | Status of ABC A physical Y1 input | Read | Inactive=Off, Active=On | |
| BV | 13 | ABCA_HDW_Y2_st | Status of ABC A physical Y2 input | Read | Inactive=Off, Active=On | |
| BV | 14 | ABCA_HDW_OB_st | Status of ABC A physical O/B input | Read | Inactive=Off, Active=On | |
| BV | 15 | ABCA_HDW_ES_st | Status of ABC A physical emergency shutdown input | Read | Inactive=Normal, Active=Shutdown | |
| BV | 16 | ABCA_HDW_LPS_st | Status of ABC A physical low pressure switch input | Read | Inactive=Open, Active=Closed | |
| BV | 17 | ABCA_HDW_HPS_st | Status of ABC A physical high pressure switch input | Read | Inactive=Open, Active=Closed | |
| BV | 18 | ABCA_HDW_LS_st | Status of ABC A physical load shed input | Read | Inactive=Inactive, Active=Active | |
| BV | 19 | ABCA_HDW_CC_st | Status of ABC A compressor output | Read | Inactive=Off, Active=On | |
| BV | 20 | ABCA_HDW_RV_st | Status of ABC A reversing valve output | Read | Inactive=Off, Active=On | |
| BV | 21 | ABCA_HDW_ACC_st | Status of ABC A accessory relay output | Read | Inactive=Off, Active=On | |
| BVmin | 33 | AlarmReset_c | Alarm reset command to clear lockout condition | Command | Inactive=Normal, Active=Reset | |
| BVmin | 36 | NetworkControl_c | Indication that system is under network control | Command | Inactive=Normal, Active=Network | |
| BVmin | 37 | SystemEnable_c | Enables (True) or Disables (False) system operation | Command | Inactive=Disabled, Active=Enabled | |
| BV | 38 | CondFlowSw_st | Condenser loop flow switch (On = flow) | Read | Inactive=Off, Active=On | |
| BV | 39 | EvapFlowSw_st | Evaporator loop flow switch (On = flow) | Read | Inactive=Off, Active=On | |
| BV | 45 | Do Not Map - FACTORY USE ONLY!!! | Internal use; do not map to BAS | Command | Inactive=False, Active=True | |
| BV | 46 | SystemSave_c | Save All | Command | Inactive=Normal, Active=Save | |
| BV | 47 | ClrFaults_c | Clr Faults BAC | Command | Inactive=Normal, Active=Save | |
| BV | 304 | CondHPCEnable_c | Enable condenser head pressure control (envelope protection) | Command | Inactive=Inactive, Active=Active | |
| BV | 305 | EvapMOPEnable_c | Enable evaporator maximum pressure control (envelope protection) | Command | Inactive=Inactive, Active=Active | |
| BV | 307 | CondHtgDeltaEnable_c | Enable delta control, condenser isolation valve, heating | Command | Inactive=Inactive, Active=Active | |
| BV | 309 | EvapHtgDeltaEnable_c | Enable delta control, evaporator isolation valve, heating | Command | Inactive=Inactive, Active=Active | |
| BV | 310 | NetIsoCtrl_c | Delta control variable, condenser isolation valve, cooling | Command | Inactive=False, Active=True | |
| BV | 311 | Net3wayCtrl_c | Delta control variable, condenser isolation valve, heating | Command | Inactive=False, Active=True | |
| BV | 501 | NetBypassCtrl_c | Local or network control of bypass valves | Command | Inactive=Inactive, Active=Active | |
| BV | 502 | Man3wayValveCtrl_c | Manual 3way valve control | Command | Inactive=Inactive, Active=Active | |
| BV | 503 | GeoWaterSelect_c | Selection between Local (False) and Network (True) geothermal loop temperature values | Command | Inactive=Local, Active=Network | |
| BV | 504 | ManBypassValves_c | Manual Bypass valve control BAC | Command | Inactive=Inactive, Active=Active | |
| BV | 507 | CWSensorFault_st | Indication that the currently selected cold water control temperature is invalid | Read | Inactive=False, Active=True | |
| BV | 508 | HWSensorFault_st | Indication that the currently selected hot water control temperature is invalid | Read | Inactive=False, Active=True | |
| BV | 509 | TempSensorFault_st | Selected cold or hot water control temperature is invalid | Read | Inactive=False, Active=True | |
| BV | 510 | ManIsoValves_c | Manual control value for isolation valves | Command | Inactive=Inactive, Active=Active |
No points match these filters.
Object ID lookup: WaterFurnace Aurora HydroLink2 TruClimate 700 point IDs by name
AV5CompADischPressure_stAV6CompASuctPressure_stAV8CondLvgWaterTemp_stAV9CondEntWaterTemp_stAV11CompASuctLineTemp_stAV18EvapLvgWaterTemp_stAV19EvapEntWaterTemp_stAV37EvapLWTLowAlarmLimit_cAV38EvapEWTHighAlarmLimit_cAV39EvapEWTLowAlarmLimit_cAV40EvapLWTHighAlarmLimit_cAV41EvapLvgWaterHighTempFaultLimit_cAV42EvapEntWaterCalib_cAV43EvapEntWaterLowTempFaultLimit_cAV44EvapEntWaterHighTempFaultLimit_cAV45EvapLeavingWaterCalib_cAV46EvapLvgWaterLowTempFaultLimit_cAV47CondLWTLowAlarmLimit_cAV48CondEWTHighAlarmLimit_cAV49CondEWTLowAlarmLimit_cAV50CondLWTHighAlarmLimit_cAV51SlowValveTimer_cAV52CompPowerFactorAdjust_cAV53MeasuredLineVoltageCal_cAV55ABCALockoutStatusAna_stAV56ABCA_FP2_stAV57ABCA_FP1_stAV60FP2LimitOverride_cAV61FP1LimitOverride_cAV63CompressorHoursA_stAV64SaturatedEvapTempA_stAV65SaturatedCondTempA_stAV66SuperheatA_stAV67SubcoolingA_stAV68EEVPositionA_stAV76ABCAAlarmStatusAna_stAV79Do Not Map - FACTORY USE ONLY!!!AV80EEVStartPos_cAV81EEVMoveToPos_cAV200ABCFirmwareRevision_stAV201AXBFirmwareRevision_stAV202VSDFirmwareRevision_stAV203ABC_DIPSwitchSettings_stAV204AXB_DIPswitchSettings_stAV210ModelNumber1-2_cAV211ModelNumber3-4_cAV212ModelNumber5-6_cAV213ModelNumber7-8_cAV214ModelNumber9-10_cAV215ModelNumber11-12_cAV216ModelNumber13-14_cAV217ModelNumber15-16_cAV218ModelNumber17-18_cAV219ModelNumber19-20_cAV220ModelNumber21-22_cAV221ModelNumber23-24_cAV222ModelNumber25-26_cAV223SerialNumber1-2_cAV224SerialNumber3-4_cAV225SerialNumber5-6_cAV226SerialNumber7-8_cAV227SerialNumber9-10_cAV302CurrentCompPct_stAV303CurrentCompRPM_stAV304MinCompPct_stAV305MaxCompPct_stAV307NetVarSpdPct_cAV308VarSpdOverride_cAV309VSCompHours_stAV312VSCompPower_stAV327CompAMinPct_cAV328CompAMaxPct_cAV332RampingStep_cAV333RampingRate_cAV340CondValvePosA_stAV341EvapValvePosA_stAV348MaxCondIsoVlvPos_cAV349MinCondIsoVlvPos_cAV350MaxEvapIsoVlvPos_cAV351MinEvapIsoVlvPos_cAV352CondTargDTHtg_cAV353EvapTargDTHtg_cAV354NetEvapPos_cAV355NetCondPos_cAV356NetEvap3wayPos_cAV357NetCond3wayPos_cAV375EvapOffPos_cAV376CondOffPos_cAV500ColdWaterSP_cAV501HotWaterSP_cAV502ColdDeltaOn_cAV503ColdDeltaOff_cAV504HotDeltaOn_cAV505HotDeltaOff_cAV506CW_NetworkTemp_cAV507HW_NetworkTemp_cAV508Geo_NetworkTemp_cAV509UnitOffsetTemp_cAV510NetColdInTemp_cAV511NetColdOutTemp_cAV512NetHotInTemp_cAV513NetHotOutTemp_cAV514NetGeoInTemp_cAV515NetGeoOutTemp_cAV516MaxHotBypass_cAV517MaxColdBypass_cAV518MaxGeoBypass_cAV519BypassValveOffset_cAV520MinLoadValvePos_cAV521MinSourceValvePos_cAV522NetColdBypass_cAV523NetHotBypass_cAV524NetGeoBypass_cAV528PropCool_cAV529IntCool_cAV530DerivCool_cAV531CoolExecuteTime_cAV532CoolRampTime_cAV533PropHeat_cAV534IntHeat_cAV535DerivHeat_cAV536HeatExecuteTime_cAV537HeatRampTime_cAV538LoadValveProp_cAV539LoadValveInt_cAV540LoadValveExecute_cAV541SourceValveProp_cAV542CondValveInt_cAV543CondValveExecute_cAV544LoadInTemp_stAV545LoadOutTemp_stAV546SourceInTemp_stAV547SourceOutTemp_stAV548ColdHeaderInletTemp_stAV549ColdHeaderOutletTemp_stAV550HotHeaderInletTemp_stAV551HotHeaderOutletTemp_stAV552GeoHeaderInletTemp_stAV553GeoHeaderOutletTemp_stAV554ActiveColdWaterTemp_stAV555ActiveHotWaterTemp_stAV556ActiveGeoWaterTemp_stAV557CurrentDemandPct_stAV558Evap3WayValve_stAV559Cond3WayValve_stAV560ColdBypassValve_stAV561HotBypassValve_stAV563ManEva3WayValvePct_cAV564ManCond3WayValvePct_cAV565ManColdBypassValvePct_cAV566ManHotBypassValvePct_cAV567ManGeoBypassValvePct_cAV569ManEvapIsoValvePct_cAV570ManCondIsoValvePct_cMV0SystemStatus_stMV1UnitMode_stMV2TempControlMethod_cMV5EnergyMonitorMode_cMV10ABCALockoutStatus_stMV12ABCAAlarmStatus_stMV500HeaderRackType_cMV501OperationMode_cMV502ColdWaterSelect_cMV503HotWaterSelect_cBV2EmShutdown_cBV4LoadShedA_cBV5EnableManualOverride_cBV9TestModeCommand_cBV10PowerPhaseSelect_cBV11ABCA_HDW_ALM_stBV12ABCA_HDW_Y1_stBV13ABCA_HDW_Y2_stBV14ABCA_HDW_OB_stBV15ABCA_HDW_ES_stBV16ABCA_HDW_LPS_stBV17ABCA_HDW_HPS_stBV18ABCA_HDW_LS_stBV19ABCA_HDW_CC_stBV20ABCA_HDW_RV_stBV21ABCA_HDW_ACC_stBV33AlarmReset_cBV36NetworkControl_cBV37SystemEnable_cBV38CondFlowSw_stBV39EvapFlowSw_stBV45Do Not Map - FACTORY USE ONLY!!!BV46SystemSave_cBV47ClrFaults_cBV304CondHPCEnable_cBV305EvapMOPEnable_cBV307CondHtgDeltaEnable_cBV309EvapHtgDeltaEnable_cBV310NetIsoCtrl_cBV311Net3wayCtrl_cBV501NetBypassCtrl_cBV502Man3wayValveCtrl_cBV503GeoWaterSelect_cBV504ManBypassValves_cBV507CWSensorFault_stBV508HWSensorFault_stBV509TempSensorFault_stBV510ManIsoValves_c
Integration notes
- Writable points are marked with the BACnet priorities they accept (in1, in4, in5, in8, in16) or 'Any Input'; they are shown here as commandable (C).
- Many object names carry over from the dual scroll HydroLink2 list, with 'Evap' and 'Cond' in place of 'Load' and 'Source'.
- AV 79 and BV 45 are printed with the name 'Do Not Map - FACTORY USE ONLY!!!'.
- MV 501 OperationMode_c is printed with default 8, which is not one of its listed states (1-7, 99).
- BV 310 NetIsoCtrl_c and BV 311 Net3wayCtrl_c carry descriptions copied from the delta-control rows; check their meaning on site.
- Valve position and capacity settings are printed as fractions (default 0.5 = 50 %) although the unit column says %. The sheet does not state the BACnet transport.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aurora HydroLink2 for TruClimate 700 Single Screw Chiller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller
How many BACnet points does the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller have?
This list has 202 BACnet objects: 154 analog values, 38 binary values, 10 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller BACnet points are writable?
134 of the 202 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller BACnet documentation?
The source is HydroLink2 Single Screw BACnet Objects, revision Version 1.00, published free by WaterFurnace at https://www.waterfurnace.com/literature/aurora/HydroLink2-BACnet-Objects-Single%20Screw-Version-1.00.xlsx.
What are the minimum BACnet points to integrate the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller?
Start with BV 37 SystemEnable_c (System enable; compressor stays off when Disabled); BV 36 NetworkControl_c (Set to Network while the BAS has control); BV 2 EmShutdown_c (Network emergency shutdown); MV 501 OperationMode_c (Operating mode: cooling, heating, free cooling, off); AV 500 ColdWaterSP_c (Cold water setpoint); AV 501 HotWaterSP_c (Hot water setpoint); BV 33 AlarmReset_c (Alarm reset; return to Normal after the lockout clears); MV 1 UnitMode_st (Current operating mode); AV 18 EvapLvgWaterTemp_st (Evaporator leaving water temperature); MV 0 SystemStatus_st (Overall status: normal, alarm, shutdown, load shed).
How do I enable BMS control of the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller?
BV 37 SystemEnable_c must be Enabled for the compressor to run, and the BAS sets BV 36 NetworkControl_c to Network when it takes control. MV 2 picks setpoint (AV 500/501), network or setpoint-with-enable control; MV 501 sets the operating mode. BV 2 EmShutdown_c forces an emergency shutdown.
Can the BMS supply sensor values to the WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller?
AV 506/507 take BAS cold and hot water control temperatures when MV 502/503 are set to option 4 (Network). AV 508 and AV 510-515 take network loop temperatures; BV 503 switches the geothermal loop values between local and network.
How do I check these points on the real Aurora HydroLink2 for TruClimate 700 Single Screw Chiller?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More WaterFurnace BACnet points lists
- Water-to-water heat pump controller
WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps
WaterFurnace NXW and SKW dual-scroll water-to-water heat pumps (including header rack arrangements) with the Aurora HydroLink controller.
Also known as: PL2500EW, HydroLink, NXW, SKW, WCHDM, HYDWWB01 - Modular chiller / water-to-water heat pump controller
WaterFurnace Aurora HydroLink2 for TruClimate 100 / TruClimate 500 Modular Chillers
WaterFurnace TruClimate 100 dual scroll (NXW) and TruClimate 500 modular chillers with the Aurora HydroLink2 controller, including 4-pipe and 6-pipe header rack builds and variable speed modules.
Also known as: HydroLink2, HydroLink 2, TruClimate 100, TruClimate 500, NXW, HydroLink2 BACnet Objects 3.04 - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Dual Compressor Rooftop Unit with Economizer
WaterFurnace dual-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump
WaterFurnace dual-compressor water-to-air heat pumps with two Aurora Base Controllers (ABC A and B) and the Aurora UPC.
Also known as: PL1500EW, Aurora Universal Protocol Converter, Aurora UPC dual compressor - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer
WaterFurnace single-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump
WaterFurnace single-compressor water-to-air heat pumps with the Aurora controls and the Aurora UPC protocol converter.
Also known as: AG1569EW, Aurora Universal Protocol Converter, Aurora UPC, UPCSWASTD01-01 - Water-source heat pump controller
WaterFurnace Aurora UPC, Variable Speed Water-Source Heat Pump
WaterFurnace variable speed water-to-air heat pumps with Aurora controls and the Aurora UPC.
Also known as: PL1700EW, Aurora Universal Protocol Converter, Aurora UPC variable speed - Water-source heat pump controller
WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace commercial dual-compressor water-to-air heat pumps fitted with the FX10 DDC controller.
Also known as: PRODCWA-05, PRODCWA, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Dual Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace dual-compressor water-to-air heat pumps with hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PRODCWA-RH-03, PRODCWA-RH, WaterFurnace dual compressor reheat FX10, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Envision single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWWE-01, PROSSWWE, Envision Water-to-Water, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton
WaterFurnace Envision 1 to 6 ton water-to-air heat pumps with the DDC controller option.
Also known as: Envision BACnet Variables, Envision BACnet Variables with BI, Envision 1-6 Ton - Geothermal heat pump zoning controller
WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet
WaterFurnace geothermal heat pumps with Aurora controls and the IntelliZone2 zoning system (up to 6 zones), read through the Aurora BACnet controller.
Also known as: IZ2, IntelliZone2, IntelliZone 2, Aurora IZ2 - Water-to-water heat pump / reversible chiller controller
WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)
WaterFurnace dual-compressor reversible chiller (water-to-water) heat pumps with the FX10 controller.
Also known as: PRODCWWE-06B, PRODCWWE-07B, PRODCWWE-08B, PRODCWWE - Water-source heat pump controller (console)
WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)
WaterFurnace single-compressor water-to-air console heat pumps fitted with the FX10 DDC controller.
Also known as: PROSSWAC-02, PROSSWAC, WaterFurnace console heat pump FX10, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace single-compressor water-to-air heat pumps without hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PROFXENV-00, PROFXENV, Envision FX10, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace single-compressor water-to-air heat pumps with hot gas reheat and the FX10 DDC controller.
Also known as: PROFXENV-RH-00, PROFXENV-RH, Envision hot gas reheat, WaterFurnace FX10 - Water-source DOAS controller with energy recovery
WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC)
WaterFurnace Versatec 700 indoor dedicated outdoor air systems: up to four variable speed water-source heat pump modules with an energy recovery wheel, economizers and DCV, on the Aurora UPC.
Also known as: Versatec 700, Versatec DOAS, WaterFurnace DOAS, DOAS BACnet Point List 1.00 - Water-to-water heat pump controller
WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec dual-compressor water-to-water heat pumps with the FX10 DDC controller and expansion board.
Also known as: PRODCWW-02, PRODCWW, Versatec Dual Compressor, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Versatec Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWW-03, PROSSWW, Versatec Water-to-Water, WaterFurnace FX10
Source: HydroLink2 Single Screw BACnet Objects · rev. Version 1.00. Object names, instances and units are reproduced as published; descriptions are our own.