- Home
- BACnet points lists
- WaterFurnace
- IntelliZone2 (IZ2) Zoning System, Aurora BACnet
Geothermal heat pump zoning controller · BACnet points list
WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet BACnet points list
Updated 6 November 2026
BACnet point list for a WaterFurnace heat pump running the IntelliZone2 zoning system. Besides the usual Aurora heat pump points (ABC inputs and outputs, ECM blower, VS pump, refrigerant and power data, humidity and DCV settings) it has a repeated block per zone 1-6 with zone temperature, BAS override, occupancy, setpoints, demand and damper limits. A large share of the rows are marked 'do not map to BAS'.
This page lists 546 BACnet objects for the WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet — 403 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WaterFurnace’s own free documentation, linked below.
- Manufacturer
- WaterFurnace
- Model
- IntelliZone2 (IZ2) Zoning System, Aurora BACnet
- Equipment
- Geothermal heat pump zoning controller
- Equipment type
- Heat pumps
- BACnet objects
- 546 (403 writable)
- Transport
- —
- Firmware
- Not stated
- Also known as
- IZ2, IntelliZone2, IntelliZone 2, Aurora IZ2
- Source document
- IZ2 BACnet Point List · rev. 2021-06-16
Reference only, provided as-is: verify against WaterFurnace’s current documentation and the live device before use. Not official WaterFurnace information. Terms of use.
BMS integration notes: WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet
Map the system points (emergency shutdown, alarm reset, mode, alarm value) once and then one zone block per active zone. Each zone takes a BAS occupancy signal and occupied heating/cooling setpoints, and reports its occupancy status and usable temperature. A zone temperature from the BAS needs BV 11x0 set to BAS and the value on AV 11x2.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 101 | em_shutdown_c | Emergency shutdown command | Write |
| BV 1106 | occ_man_cmd_bv_z1_c | Zone 1 occupancy from the BAS | Write |
| AV 1111 | occ_clg_setpt_z1_c | Zone 1 occupied cooling setpoint | Write |
| AV 1112 | occ_htg_setpt_z1_c | Zone 1 occupied heating setpoint | Write |
| BV 130 | alarm_reset_c | Alarm reset | Write |
| MV 100 | mode_msv | Unit operating mode | Read |
| AV 1110 | eff_occ_st_z1 | Zone 1 effective occupancy status | Read |
| AV 1100 | zone_temp_z1 | Zone 1 temperature in use | Read |
| BV 141 | alarm_hdw_stat_a | ABC alarm output status | Read |
| AV 119 | alarm_enum | Combined system alarm code | Read |
Enable & remote start
BV 101 em_shutdown_c shuts the unit down and BV 105 load_shed_c sheds load from the network. Occupancy can come from the BAS per zone (BV 11x6, MV 11x0 or AV 11x9, depending on BV 1000) or from the internal schedule; BV 502 picks internal or external schedule.
Sensors & values from the BMS
For a BAS zone temperature, set BV 11x0 (temp_selector) to BAS and write AV 11x2 (zone_temp_ovrd). AV 504, AV 506 and AV 508 accept BAS space humidity, CO2 and VOC values, and AV 606 a BAS outdoor air temperature (BV 1017 picks the OAT source).
Watch out for
- Many points are flagged 'do not map to BAS'; leave them alone.
- BV 318 gives the BAS write access to the ABC dip switch overrides; BV 398 takes it away.
- Zone points repeat per zone: zone n uses instances 1n00-1n99 (zone 1 = 1100s).
WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 102 | mode_av | Operating mode of the unit (numeric) (default 0) | Write | ||
| AV | 103 | man_ecm_speed_c | Internal use; do not map to BAS | Write | ||
| AV | 105 | man_vs_pump_a_c | Internal use; do not map to BAS | Write | ||
| AV | 109 | fp1_setpt_a | FP1 freeze detection limit (coax temp) (default 0) | Write | ||
| AV | 110 | fp2_setpt_a | FP2 freeze detection limit (air coil temp) (default 0) | Write | ||
| AV | 113 | filter_alm_hrs_c | Adjusts the filter alarm hours (default 1000) | hr | Write | |
| AV | 114 | filter_hours | Number of fan run hours since the last filter alarm reset | hr | Read | |
| AV | 115 | lock_stat_reg_a | Internal use; do not map to BAS | Read | ||
| AV | 116 | alarm_enum_a | Alarm value for ABC | Read | ||
| AVmin | 119 | alarm_enum | Combined system alarm value | Read | ||
| AV | 200 | ecm_speed_sw_a | Current ECM target speed (default 0) | Write | ||
| AV | 201 | ecm_pwm_pct_a | Current ECM PWM output percentage (default 0) | % | Write | |
| AV | 202 | vs_pump_spd_stat_a | Current target % of the VS Pump output (default 0) | % | Write | |
| AV | 203 | vs_pump_pct_stat_a | Current operating % of the VS Pump output (default 0) | % | Write | |
| AV | 206 | coax_temp_stat_a | Temperature of the refrigerant at the Coax | °F | Read | |
| AV | 207 | air_coil_temp_stat_a | Temperature of the refrigerant at the air coil | °F | Read | |
| AV | 210 | lwt_stat_a | LWT Input if the sensing hardware is present | °F | Read | |
| AV | 211 | ewt_stat_a | EWT Input if the sensing hardware is present | °F | Read | |
| AV | 212 | water_flow_stat_a | GPM flow rate if the sensing hardware is present | gpm | Read | |
| AV | 213 | loop_pres_stat_a | Loop pressure if the sensing hardware is present | psi | Read | |
| AV | 214 | lat_stat | Leaving air temperature that is connected to the AXB | °F | Read | |
| AV | 216 | suct_press_stat_a | Suction pressure if the sensing hardware is present | psi | Read | |
| AV | 217 | disch_press_stat_a | Discharge pressure if the sensing hardware is present | psi | Read | |
| AV | 218 | suct_temp_stat_a | Suction temperature if the sensing hardware is present | °F | Read | |
| AV | 219 | disch_temp_stat_a | Discharge temperature if the sensing hardware is present | °F | Read | |
| AV | 220 | liq_line_temp_stat_a | Heating liquid line temperature if the sensing hardware is present | °F | Read | |
| AV | 221 | sat_evap_temp_stat_a | Saturated evaporator temperature if the sensing hardware is present | °F | Read | |
| AV | 222 | cond_temp_stat_a | Condensor temperature if the sensing hardware is present | °F | Read | |
| AV | 223 | est_line_voltage_stat_a | Estimated line voltage from control voltage and calibration (default 0) | V | Write | |
| AV | 224 | control_voltage_stat_a | Low voltage circuit value that is powering the ABC | V | Read | |
| AV | 225 | hot_wtr_temp_stat_a | Hot water temperature input if the sensing hardware is present | °F | Read | |
| AV | 226 | univ_input_stat_a | Raw count value of the universal input (default 0) | Write | ||
| AV | 227 | superheat_stat_a | Super heat if the sensing hardware is present | °F | Read | |
| AV | 228 | htg_subcool_stat_a | Sub cooling calculation in the heating mode | °F | Read | |
| AV | 229 | clg_subcool_stat_a | Sub cooling calculation in the cooling mode | °F | Read | |
| AV | 230 | fan_current_stat_a | Amp draw for the Fan output if the sensing hardware is present | A | Read | |
| AV | 231 | aux_current_stat_a | Amp draw for the Auxiliary output if the sensing hardware is present | A | Read | |
| AV | 232 | comp_current_stat_a | Compressor amp draw on L1 or L2 | A | Read | |
| AV | 233 | comp1_current_stat_a | Compressor amp draw on L1 or L2 | A | Read | |
| AV | 234 | total_amps_stat_a | Calculated total amp draw if the sensing hardware is present | A | Read | |
| AV | 235 | comp_power_stat_a | Calculates and displays the compressor power if the sensing hardware is present | W | Read | |
| AV | 236 | fan_power_stat_a | Watt usage for Fan output if the sensing hardware is present | W | Read | |
| AV | 237 | aux_power_stat_a | Watt usage for Auxiliary output if the sensing hardware is present | W | Read | |
| AV | 238 | total_power_stat_a | Calculated total watt usage if the sensing hardware is present | W | Read | |
| AV | 239 | he_hr_stat_a | Heat of rejection / extraction (needs sensing hardware) | Btu/hr | Read | |
| AV | 240 | total_cap_stat_a | Calculated value total capacity if the sensing hardware is present | Btu/hr | Read | |
| AV | 241 | cop_stat_a | Calculated C.O.P if the sensing hardware is present | Read | ||
| AV | 242 | eer_stat_a | EER calculation if the sensing hardware is present | Read | ||
| AV | 296 | targ_blower_spd | Current target ECM blower speed (default 0) | Write | ||
| AV | 297 | mod_valve_pwm | Current modulating valve PWM output signal value (default 0) | % | Write | |
| AV | 298 | eev1_pos | Current position of EEV1 if present (default 0) | % | Write | |
| AV | 299 | eev2_pos | Current position of EEV2 if present (default 0) | % | Write | |
| AV | 301 | low_ecm_spd_c | Low speed ECM airflow setting (default 3) | Write | ||
| AV | 302 | med_ecm_spd_c | Medium speed ECM airflow setting (default 6) | Write | ||
| AV | 303 | high_ecm_spd_c | High speed ECM airflow setting (default 11) | Write | ||
| AV | 304 | aux_ht_ecm_spd_c | Auxiliary heat speed ECM airflow setting (default 12) | Write | ||
| AV | 305 | blwr_off_delay_c | Blower off delay after compressor stops, cycled blower (default 30) | seconds | Write | |
| AV | 306 | clg_cfm_offset_av_c | Selects dehumdiification operation for ECM blower (default 4) | Write | ||
| AV | 307 | occ_dehum_setpt_c | Adjustment of the occupied dehumidification set point (default 55) | %rh | Write | |
| AV | 308 | unocc_dehum_setpt_c | Adjustment of the unoccupied dehumidification set point (default 75) | %rh | Write | |
| AV | 309 | dehum_setpt | Acive dehumidification setpoint (default 0) | % | Write | |
| AV | 311 | vs_pump_min_spd_a_c | VS Pump minimum speed setting for circuit A (default 50) | % | Write | |
| AV | 312 | vs_pump_max_spd_a_c | VS Pump maximum speed setting for circuit A (default 100) | % | Write | |
| AV | 313 | pump_opt_a_c | Pump or loop option (default 0) | Write | ||
| AV | 317 | flow_meter_a_c | Flow meter option (default 0) | Write | ||
| AV | 319 | dhw_setpt_a_c | Hot water setpoint (default 130) | °F | Write | |
| AV | 321 | energy_mon_a_c | Energy monitor option (default 0) | Write | ||
| AV | 323 | acc1_delay_a_c | Adjust the time delay of the ACC-1 output (default 90) | seconds | Write | |
| AV | 325 | measured_line_volts_c | Calibration of the line voltage reading (default 230) | V | Write | |
| AV | 326 | blower_config_c | Blower configuration (default 9) | Write | ||
| AV | 330 | hum_enable_av_c | Configuration of humidity control option (None, Dehum, Hum, Both) (default 1) | Write | ||
| AV | 331 | occ_hum_setpt_c | Adjustment of the occupied humidification set point (default 30) | %rh | Write | |
| AV | 332 | unocc_hum_setpt_c | Adjustment of the unoccupied humidification set point (default 20) | %rh | Write | |
| AV | 400 | fact_test_c | Internal use; do not map to BAS | Write | ||
| AV | 401 | m401_cmd | Internal use; do not map to BAS | Write | ||
| AV | 402 | m402_cmd | Internal use; do not map to BAS | Write | ||
| AV | 403 | m403_cmd | Internal use; do not map to BAS | Write | ||
| AV | 404 | m404_cmd | Internal use; do not map to BAS | Write | ||
| AV | 405 | m405_cmd | Internal use; do not map to BAS | Write | ||
| AV | 406 | m406_cmd | Internal use; do not map to BAS | Write | ||
| AV | 407 | m407_cmd | Internal use; do not map to BAS | Write | ||
| AV | 408 | m408_cmd | Internal use; do not map to BAS | Write | ||
| AV | 409 | m409_cmd | Internal use; do not map to BAS | Write | ||
| AV | 410 | m410_cmd | Internal use; do not map to BAS | Write | ||
| AV | 411 | m411_cmd | Internal use; do not map to BAS | Write | ||
| AV | 412 | m412_cmd | Internal use; do not map to BAS | Write | ||
| AV | 413 | m413_cmd | Internal use; do not map to BAS | Write | ||
| AV | 414 | m414_cmd | Internal use; do not map to BAS | Write | ||
| AV | 415 | m415_cmd | Internal use; do not map to BAS | Write | ||
| AV | 416 | m416_cmd | Internal use; do not map to BAS | Write | ||
| AV | 417 | m417_cmd | Internal use; do not map to BAS | Write | ||
| AV | 418 | m418_cmd | Internal use; do not map to BAS | Write | ||
| AV | 420 | tstat_ovrd_c | Internal use; do not map to BAS | Write | ||
| AV | 430 | abc_fw_rev_a | Internal use; do not map to BAS | Read | ||
| AV | 431 | abc_sw_part_no_a | Internal use; do not map to BAS | Write | ||
| AV | 432 | abc_fw_beta_a | Internal use; do not map to BAS | Write | ||
| AV | 503 | zone_hum | Humidity value of the zone sensor (default 0) | %rh | Write | |
| AV | 504 | humidity_c | BAS can override the space humidity value if desired (default 0) | %rh | Write | |
| AV | 505 | co2_stat | CO2 value if the zone sensor is equipped with the sensor (default 0) | ppm | Write | |
| AV | 506 | co2_cmd_c | BAS-written CO2 value to the UPC if desired (default 0) | ppm | Write | |
| AV | 507 | voc_stat | VOC value if the zone sensor is equipped with the sensor (default 0) | ppm | Write | |
| AV | 508 | voc_cmd_c | BAS-written VOC value to the UPC if desired (default 0) | ppm | Write | |
| AV | 601 | o_damp_targ | Current outside air damper used for demand controlled ventilation (default 0) | % | Write | |
| AV | 606 | oat_override_c | BAS-written outdoor air temperature to the XPC (default 0) | °F | Write | |
| AV | 607 | oat_stat | Current usable outdoor air temperature value | °F | Read | |
| AV | 638 | min_dcv_pos_c | Minimum damper position for demand controlled ventilation (default 20) | % | Write | |
| AV | 642 | max_dcv_pos_c | Maximum damper position for demand controlled ventilation (default 40) | % | Write | |
| AV | 643 | low_dcv_val_c | DCV lower value, tied to the minimum damper position (default 600) | ppm | Write | |
| AV | 644 | high_dcv_val_c | DCV upper value, tied to the maximum DCV position (default 1200) | ppm | Write | |
| AV | 700 | comp_config | Internal use; do not map to BAS | Read | ||
| AV | 701 | comp_config_av | Internal use; do not map to BAS | Write | ||
| AV | 702 | eev_start_c | Internal use; do not map to BAS | % | Write | |
| AV | 703 | targ_comp_spd | Current target variable speed compressor speed (default 0) | Write | ||
| AV | 704 | actual_comp_spd | Current actual variable speed compressor speed (default 0) | Write | ||
| AV | 705 | amb_temp | Ambient temperature measured by compressor drive | °F | Read | |
| AV | 706 | supply_volts | Supply voltage measured by the compressor drive | V | Read | |
| AV | 707 | line_volts | Line voltage measured by the compressor drive (default 0) | V | Write | |
| AV | 708 | vdc_volts | Inverter DC voltage measured by the compressor drive (default 0) | V | Write | |
| AV | 709 | invert_temp | Measured inverter temperature | °F | Read | |
| AV | 710 | drive_temp | Measured compressor drive temperature | °F | Read | |
| AV | 711 | drive_fan_pct | Current compressor drive fan operating percent (default 0) | % | Write | |
| AV | 712 | thermo_power_pct | Current compressor drive thermo power percent (default 0) | % | Write | |
| AV | 720 | man_comp_spd_c | Internal use; do not map to BAS | Write | ||
| AV | 721 | man_eev_pos_c | Internal use; do not map to BAS | % | Write | |
| AV | 722 | man_odamp_pos_c | Internal use; do not map to BAS | Write | ||
| AV | 1000 | num_zones_c | Configures number of zones (default 2) | Write | ||
| AV | 1001 | z1size_av_c | Configures zone 1 size (default 1) | Write | ||
| AV | 1002 | z2size_av_c | Configures zone 2 size (default 1) | Write | ||
| AV | 1003 | z3size_av_c | Configures zone 3 size (default 1) | Write | ||
| AV | 1004 | z4size_av_c | Configures zone 4 size (default 1) | Write | ||
| AV | 1005 | z5size_av_c | Configures zone 5 size (default 1) | Write | ||
| AV | 1006 | z6size_av_c | Configures zone 6 size (default 1) | Write | ||
| AV | 1007 | z1mode_av_c | Configures zone 1 operating mode (default 1) | Write | ||
| AV | 1008 | z2mode_av_c | Configures zone 2 operating mode (default 1) | Write | ||
| AV | 1009 | z3mode_av_c | Configures zone 3 operating mode (default 1) | Write | ||
| AV | 1010 | z4mode_av_c | Configures zone 4 operating mode (default 1) | Write | ||
| AV | 1011 | z5mode_av_c | Configures zone 5 operating mode (default 1) | Write | ||
| AV | 1012 | z6mode_av_c | Configures zone 6 operating mode (default 1) | Write | ||
| AV | 1013 | clg_stage_av_c | Configures system staging for cooling (default 1) | Write | ||
| AV | 1014 | htg_stage_av_c | Configures system staging for heating (default 1) | Write | ||
| AV | 1015 | ah_lock_setpt_c | Outdoor temperature associated with Auxiliary Heat Lockout (default 20) | °F | Write | |
| AV | 1016 | occ_sens_on_time_c | Internal use; do not map to BAS | seconds | Write | |
| AV | 1017 | occ_sens_off_time_c | Internal use; do not map to BAS | min | Write | |
| AV | 1020 | azc_fw_rev | Internal use; do not map to BAS | Write | ||
| AV | 1021 | azc_fault | Zone panel fault code value (default 0) | Write | ||
| AV | 1022 | damp_time__c | Zone damper opening time (seconds) (default 90) | seconds | Write | |
| AV | 1036 | z1max | Maximum Damper Position Zone 1 (default 100) | % | Write | |
| AV | 1037 | z2max | Maximum Damper Position Zone 2 (default 100) | % | Write | |
| AV | 1038 | z3max | Maximum Damper Position Zone 3 (default 100) | % | Write | |
| AV | 1039 | z4max | Maximum Damper Position Zone 4 (default 100) | % | Write | |
| AV | 1040 | z5max | Maximum Damper Position Zone 5 (default 100) | % | Write | |
| AV | 1041 | z6max | Maximum Damper Position Zone 6 (default 100) | % | Write | |
| AV | 1042 | z1min | Minimum Damper Position Zone 1 (default 0) | % | Write | |
| AV | 1043 | z2min | Minimum Damper Position Zone 2 (default 0) | % | Write | |
| AV | 1044 | z3min | Minimum Damper Position Zone 3 (default 0) | % | Write | |
| AV | 1045 | z4min | Minimum Damper Position Zone 4 (default 0) | % | Write | |
| AV | 1046 | z5min | Minimum Damper Position Zone 5 (default 0) | % | Write | |
| AV | 1047 | z6min | Minimum Damper Position Zone 6 (default 0) | % | Write | |
| AVmin | 1100 | zone_temp_z1 | Current usable Zone 1 temperature value | °F | Read | |
| AV | 1101 | zone_temp_adj_z1_c | Zone 1 temperature reading (default 0) | °F | Write | |
| AV | 1102 | zone_temp_ovrd_z1_c | BAS override of zone 1 temperature (enable on BV 1100) (default 0) | °F | Write | |
| AV | 1103 | zone_hum_z1 | Humidity value of the zone 1 sensor | %rh | Read | |
| AV | 1105 | co2_stat_z1 | CO2 value if the zone 1 sensor is equipped with the sensor | ppm | Read | |
| AV | 1107 | voc_stat_z1 | VOC value if the zone 1 sensor is equipped with the sensor | ppm | Read | |
| AV | 1109 | occ_man_av_z1_c | BAS can command the occupancy of the unit (default 1) | Write | ||
| AVmin | 1110 | eff_occ_st_z1 | Current occupancy status of zone 1 | Read | ||
| AVmin | 1111 | occ_clg_setpt_z1_c | Zone 1 occupied cooling set point | °F | Write | |
| AVmin | 1112 | occ_htg_setpt_z1_c | Zone 1 occupied heating set point | °F | Write | |
| AV | 1113 | unocc_clg_setpt_z1_c | Zone 1 unoccupied cooling set point | °F | Write | |
| AV | 1114 | unocc_htg_setpt_z1_c | Zone 1 unoccupied heating set point | °F | Write | |
| AV | 1115 | standby_cool_setpt_z1_c | Zone 1 standby cooling set point (default 76) | °F | Write | |
| AV | 1116 | standby_heat_setpt_z1_c | Zone 1 standby heating set point (default 68) | °F | Write | |
| AV | 1117 | eff_clg_setpt_z1 | Zone 1 effective cooling set point | °F | Read | |
| AV | 1118 | eff_htg_setpt_z1 | Zone 1 effective heating set point | °F | Read | |
| AV | 1120 | occ_sensor_av_z1_c | BAS can select the operation of an occupancy sensor (default 1) | Write | ||
| AV | 1121 | setpt_diff_z1_c | Minimum temperature between the heating and cooling setpoints for zone 1 (default 2) | °F | Write | |
| AV | 1122 | setpt_span_z1_c | Adjusts the space temperature set point span for zone 1 (default 5) | °F | Write | |
| AV | 1123 | temp_occ_time_z1 | Temporary occupancy time left, zone 1 | m/sec | Read | |
| AV | 1125 | zone_sensor_temp_z1 | Zone 1 Temp as read by the zone sensors | °F | Read | |
| AV | 1150 | z1_demand | Numeric representation of current zone 1 demand (default 0) | % | Write | |
| AV | 1200 | zone_temp_z2 | Current usable Zone 2 temperature value | °F | Read | |
| AV | 1201 | zone_temp_adj_z2_c | Zone 2 temperature reading (default 0) | °F | Write | |
| AV | 1202 | zone_temp_ovrd_z2_c | BAS override of zone 2 temperature (enable on BV 1200) (default 0) | °F | Write | |
| AV | 1203 | zone_hum_z2 | Humidity value of the zone 2 sensor | %rh | Read | |
| AV | 1205 | co2_stat_z2 | CO2 value if the zone 2 sensor is equipped with the sensor | ppm | Read | |
| AV | 1207 | voc_stat_z2 | VOC value if the zone 2 sensor is equipped with the sensor | ppm | Read | |
| AV | 1209 | occ_man_av_z2_c | BAS can command the occupancy of the unit (default 1) | Write | ||
| AV | 1210 | eff_occ_st_z2 | Current occupancy status of zone 2 | Read | ||
| AV | 1211 | occ_clg_setpt_z2_c | Zone 2 occupied cooling set point | °F | Write | |
| AV | 1212 | occ_htg_setpt_z2_c | Zone 2 occupied heating set point | °F | Write | |
| AV | 1213 | unocc_clg_setpt_z2_c | Zone 2 unoccupied cooling set point | °F | Write | |
| AV | 1214 | unocc_htg_setpt_z2_c | Zone 2 unoccupied heating set point | °F | Write | |
| AV | 1215 | standby_cool_setpt_z2_c | Zone 2 standby cooling set point (default 76) | °F | Write | |
| AV | 1216 | standby_heat_setpt_z2_c | Zone 2 standby heating set point (default 68) | °F | Write | |
| AV | 1217 | eff_clg_setpt_z2 | Zone 2 effective cooling set point | °F | Read | |
| AV | 1218 | eff_htg_setpt_z2 | Zone 2 effective heating set point | °F | Read | |
| AV | 1220 | occ_sensor_av_z2_c | BAS can select the operation of an occupancy sensor (default 1) | Write | ||
| AV | 1221 | setpt_diff_z2_c | Minimum temperature between the heating and cooling setpoints for zone 2 (default 2) | °F | Write | |
| AV | 1222 | setpt_span_z2_c | Adjusts the space temperature set point span for zone 2 (default 5) | °F | Write | |
| AV | 1223 | temp_occ_time_z2 | Temporary occupancy time left, zone 2 | m/sec | Read | |
| AV | 1225 | zone_sensor_temp_z2 | Zone 2 Temp as read by the zone sensors | °F | Read | |
| AV | 1250 | z2_demand | Numeric representation of current zone 2 demand (default 0) | % | Write | |
| AV | 1300 | zone_temp_z3 | Current usable Zone 3 temperature value | °F | Read | |
| AV | 1301 | zone_temp_adj_z3_c | Zone 3 temperature reading (default 0) | °F | Write | |
| AV | 1302 | zone_temp_ovrd_z3_c | BAS override of zone 3 temperature (enable on BV 1300) (default 0) | °F | Write | |
| AV | 1303 | zone_hum_z3 | Humidity value of the zone 3 sensor | %rh | Read | |
| AV | 1305 | co2_stat_z3 | CO2 value if the zone 3 sensor is equipped with the sensor | ppm | Read | |
| AV | 1307 | voc_stat_z3 | VOC value if the zone 3 sensor is equipped with the sensor | ppm | Read | |
| AV | 1309 | occ_man_av_z3_c | BAS can command the occupancy of the unit (default 1) | Write | ||
| AV | 1310 | eff_occ_st_z3 | Current occupancy status of zone 3 | Read | ||
| AV | 1311 | occ_clg_setpt_z3_c | Zone 3 occupied cooling set point | °F | Write | |
| AV | 1312 | occ_htg_setpt_z3_c | Zone 3 occupied heating set point | °F | Write | |
| AV | 1313 | unocc_clg_setpt_z3_c | Zone 3 unoccupied cooling set point | °F | Write | |
| AV | 1314 | unocc_htg_setpt_z3_c | Zone 3 unoccupied heating set point | °F | Write | |
| AV | 1315 | standby_cool_setpt_z3_c | Zone 3 standby cooling set point (default 76) | °F | Write | |
| AV | 1316 | standby_heat_setpt_z3_c | Zone 3 standby heating set point (default 68) | °F | Write | |
| AV | 1317 | eff_clg_setpt_z3 | Zone 3 effective cooling set point | °F | Read | |
| AV | 1318 | eff_htg_setpt_z3 | Zone 3 effective heating set point | °F | Read | |
| AV | 1320 | occ_sensor_av_z3_c | BAS can select the operation of an occupancy sensor (default 1) | Write | ||
| AV | 1321 | setpt_diff_z3_c | Minimum temperature between the heating and cooling setpoints for zone 3 (default 2) | °F | Write | |
| AV | 1322 | setpt_span_z3_c | Adjusts the space temperature set point span for zone 3 (default 5) | °F | Write | |
| AV | 1323 | temp_occ_time_z3 | Temporary occupancy time left, zone 3 | m/sec | Read | |
| AV | 1325 | zone_sensor_temp_z3 | Zone 3 Temp as read by the zone sensors | °F | Read | |
| AV | 1350 | z3_demand | Numeric representation of current zone 3 demand (default 0) | % | Write | |
| AV | 1400 | zone_temp_z4 | Current usable Zone 4 temperature value | °F | Read | |
| AV | 1401 | zone_temp_adj_z4_c | Zone 4 temperature reading (default 0) | °F | Write | |
| AV | 1402 | zone_temp_ovrd_z4_c | BAS override of zone 4 temperature (enable on BV 1400) (default 0) | °F | Write | |
| AV | 1403 | zone_hum_z4 | Humidity value of the zone 4 sensor | %rh | Read | |
| AV | 1405 | co2_stat_z4 | CO2 value if the zone 4 sensor is equipped with the sensor | ppm | Read | |
| AV | 1407 | voc_stat_z4 | VOC value if the zone 4 sensor is equipped with the sensor | ppm | Read | |
| AV | 1409 | occ_man_av_z4_c | BAS can command the occupancy of the unit (default 1) | Write | ||
| AV | 1410 | eff_occ_st_z4 | Current occupancy status of zone 4 | Read | ||
| AV | 1411 | occ_clg_setpt_z4_c | Zone 4 occupied cooling set point | °F | Write | |
| AV | 1412 | occ_htg_setpt_z4_c | Zone 4 occupied heating set point | °F | Write | |
| AV | 1413 | unocc_clg_setpt_z4_c | Zone 4 unoccupied cooling set point | °F | Write | |
| AV | 1414 | unocc_htg_setpt_z4_c | Zone 4 unoccupied heating set point | °F | Write | |
| AV | 1415 | standby_cool_setpt_z4_c | Zone 4 standby cooling set point (default 76) | °F | Write | |
| AV | 1416 | standby_heat_setpt_z4_c | Zone 4 standby heating set point (default 68) | °F | Write | |
| AV | 1417 | eff_clg_setpt_z4 | Zone 4 effective cooling set point | °F | Read | |
| AV | 1418 | eff_htg_setpt_z4 | Zone 4 effective heating set point | °F | Read | |
| AV | 1420 | occ_sensor_av_z4_c | BAS can select the operation of an occupancy sensor (default 1) | Write | ||
| AV | 1421 | setpt_diff_z4_c | Minimum temperature between the heating and cooling setpoints for zone 4 (default 2) | °F | Write | |
| AV | 1422 | setpt_span_z4_c | Adjusts the space temperature set point span for zone 4 (default 5) | °F | Write | |
| AV | 1423 | temp_occ_time_z4 | Temporary occupancy time left, zone 4 | m/sec | Read | |
| AV | 1425 | zone_sensor_temp_z4 | Zone 4 Temp as read by the zone sensors | °F | Read | |
| AV | 1450 | z4_demand | Numeric representation of current zone 4 demand (default 0) | % | Write | |
| AV | 1500 | zone_temp_z5 | Current usable Zone 5 temperature value | °F | Read | |
| AV | 1501 | zone_temp_adj_z5_c | Zone 5 temperature reading (default 0) | °F | Write | |
| AV | 1502 | zone_temp_ovrd_z5_c | BAS override of zone 5 temperature (enable on BV 1500) (default 0) | °F | Write | |
| AV | 1503 | zone_hum_z5 | Humidity value of the zone 5 sensor | %rh | Read | |
| AV | 1505 | co2_stat_z5 | CO2 value if the zone 5 sensor is equipped with the sensor | ppm | Read | |
| AV | 1507 | voc_stat_z5 | VOC value if the zone 5 sensor is equipped with the sensor | ppm | Read | |
| AV | 1509 | occ_man_av_z5_c | BAS can command the occupancy of the unit (default 1) | Write | ||
| AV | 1510 | eff_occ_st_z5 | Current occupancy status of zone 5 | Read | ||
| AV | 1511 | occ_clg_setpt_z5_c | Zone 5 occupied cooling set point | °F | Write | |
| AV | 1512 | occ_htg_setpt_z5_c | Zone 5 occupied heating set point | °F | Write | |
| AV | 1513 | unocc_clg_setpt_z5_c | Zone 5 unoccupied cooling set point | °F | Write | |
| AV | 1514 | unocc_htg_setpt_z5_c | Zone 5 unoccupied heating set point | °F | Write | |
| AV | 1515 | standby_cool_setpt_z5_c | Zone 5 standby cooling set point (default 76) | °F | Write | |
| AV | 1516 | standby_heat_setpt_z5_c | Zone 5 standby heating set point (default 68) | °F | Write | |
| AV | 1517 | eff_clg_setpt_z5 | Zone 5 effective cooling set point | °F | Read | |
| AV | 1518 | eff_htg_setpt_z5 | Zone 5 effective heating set point | °F | Read | |
| AV | 1520 | occ_sensor_av_z5_c | BAS can select the operation of an occupancy sensor (default 1) | Write | ||
| AV | 1521 | setpt_diff_z5_c | Minimum temperature between the heating and cooling setpoints for zone 5 (default 2) | °F | Write | |
| AV | 1522 | setpt_span_z5_c | Adjusts the space temperature set point span for zone 5 (default 5) | °F | Write | |
| AV | 1523 | temp_occ_time_z5 | Temporary occupancy time left, zone 5 | m/sec | Read | |
| AV | 1525 | zone_sensor_temp_z5 | Zone 5 Temp as read by the zone sensors | °F | Read | |
| AV | 1550 | z5_demand | Numeric representation of current zone 5 demand (default 0) | % | Write | |
| AV | 1600 | zone_temp_z6 | Current usable Zone 6 temperature value | °F | Read | |
| AV | 1601 | zone_temp_adj_z6_c | Zone 6 temperature reading (default 0) | °F | Write | |
| AV | 1602 | zone_temp_ovrd_z6_c | BAS override of zone 6 temperature (enable on BV 1600) (default 0) | °F | Write | |
| AV | 1603 | zone_hum_z6 | Humidity value of the zone 6 sensor | %rh | Read | |
| AV | 1605 | co2_stat_z6 | CO2 value if the zone 6 sensor is equipped with the sensor | ppm | Read | |
| AV | 1607 | voc_stat_z6 | VOC value if the zone 6 sensor is equipped with the sensor | ppm | Read | |
| AV | 1609 | occ_man_av_z6_c | BAS can command the occupancy of the unit (default 1) | Write | ||
| AV | 1610 | eff_occ_st_z6 | Current occupancy status of zone 6 | Read | ||
| AV | 1611 | occ_clg_setpt_z6_c | Zone 6 occupied cooling set point | °F | Write | |
| AV | 1612 | occ_htg_setpt_z6_c | Zone 6 occupied heating set point | °F | Write | |
| AV | 1613 | unocc_clg_setpt_z6_c | Zone 6 unoccupied cooling set point | °F | Write | |
| AV | 1614 | unocc_htg_setpt_z6_c | Zone 6 unoccupied heating set point | °F | Write | |
| AV | 1615 | standby_cool_setpt_z6_c | Zone 6 standby cooling set point (default 76) | °F | Write | |
| AV | 1616 | standby_heat_setpt_z6_c | Zone 6 standby heating set point (default 68) | °F | Write | |
| AV | 1617 | eff_clg_setpt_z6 | Zone 6 effective cooling set point | °F | Read | |
| AV | 1618 | eff_htg_setpt_z6 | Zone 6 effective heating set point | °F | Read | |
| AV | 1620 | occ_sensor_av_z6_c | BAS can select the operation of an occupancy sensor (default 1) | Write | ||
| AV | 1621 | setpt_diff_z6_c | Minimum temperature between the heating and cooling setpoints for zone 6 (default 2) | °F | Write | |
| AV | 1622 | setpt_span_z6_c | Adjusts the space temperature set point span for zone 6 (default 5) | °F | Write | |
| AV | 1623 | temp_occ_time_z6 | Temporary occupancy time left, zone 6 | m/sec | Read | |
| AV | 1625 | zone_sensor_temp_z6 | Zone 6 Temp as read by the zone sensors | °F | Read | |
| AV | 1650 | z6_demand | Numeric representation of current zone 6 demand (default 0) | % | Write | |
| AV | 9000 | active_z1_setpt | Internal use; do not map to BAS | °F | Write | |
| AV | 9001 | active_z2_setpt | Internal use; do not map to BAS | °F | Write | |
| AV | 9002 | active_z3_setpt | Internal use; do not map to BAS | °F | Write | |
| AV | 9003 | active_z4_setpt | Internal use; do not map to BAS | °F | Write | |
| AV | 9004 | active_z5_setpt | Internal use; do not map to BAS | °F | Write | |
| AV | 9005 | active_z6_setpt | Internal use; do not map to BAS | °F | Write | |
| AV | 9006 | sensor_alarms | Internal use; do not map to BAS | Write | ||
| AV | 9007 | comp_config_m | Internal use; do not map to BAS | Write | ||
| AV | 9013 | supply_voltsl_m | Internal use; do not map to BAS | V | Write | |
| AV | 9014 | supply_voltsh_m | Internal use; do not map to BAS | V | Write | |
| AV | 9040 | abc_9013 | Internal use; do not map to BAS | Read | ||
| AV | 9041 | abc_9014 | Internal use; do not map to BAS | Read | ||
| AV | 9043 | abc_0036 | Internal use; do not map to BAS | Write | ||
| AV | 9044 | abc_9016 | Internal use; do not map to BAS | Write | ||
| AV | 9045 | abc_0002 | Internal use; do not map to BAS | Write | ||
| AV | 9047 | rand_start_delay_a | Internal use; do not map to BAS | Write | ||
| AV | 9048 | anti_short_cycle_a | Internal use; do not map to BAS | Write | ||
| AV | 9049 | low_spd_min_run_time_a | Internal use; do not map to BAS | Write | ||
| AV | 9050 | blow_off_dly_time_a | Internal use; do not map to BAS | Write | ||
| AV | 9051 | comp_strt_delay_a | Internal use; do not map to BAS | Write | ||
| AV | 9052 | slow_open_wtr_vlv_a | Internal use; do not map to BAS | Write | ||
| AV | 9053 | test_mode_timer_a | Internal use; do not map to BAS | Write | ||
| AV | 9054 | comp_run_time_l_a | Internal use; do not map to BAS | Write | ||
| AV | 9055 | comp_run_time_h_ma | Internal use; do not map to BAS | Write | ||
| AV | 9056 | comp_power_low_a | Internal use; do not map to BAS | Write | ||
| AV | 9057 | comp_power_high_a | Internal use; do not map to BAS | Write | ||
| AV | 9058 | fan_power_low_a | Internal use; do not map to BAS | Write | ||
| AV | 9059 | fan_power_high_a | Internal use; do not map to BAS | Write | ||
| AV | 9060 | aux_power_low_a | Internal use; do not map to BAS | Write | ||
| AV | 9061 | aux_power_high_a | Internal use; do not map to BAS | Write | ||
| AV | 9062 | total_power_low_a | Internal use; do not map to BAS | Write | ||
| AV | 9063 | total_power_high_a | Internal use; do not map to BAS | Write | ||
| AV | 9064 | heat_ext_low_a | Internal use; do not map to BAS | Write | ||
| AV | 9065 | heat_ext_high_a | Internal use; do not map to BAS | Write | ||
| AV | 9066 | heat_rej_low_a | Internal use; do not map to BAS | Write | ||
| AV | 9067 | heat_rej_high_a | Internal use; do not map to BAS | Write | ||
| AV | 9068 | heat_cap_low_a | Internal use; do not map to BAS | Write | ||
| AV | 9069 | heat_cap_high_a | Internal use; do not map to BAS | Write | ||
| AV | 9070 | cool_cap_low_a | Internal use; do not map to BAS | Write | ||
| AV | 9071 | cool_cap_high_a | Internal use; do not map to BAS | Write | ||
| AV | 9074 | zc_stat | Internal use; do not map to BAS | Write | ||
| AV | 9075 | lo_stat_a | Internal use; do not map to BAS | Write | ||
| AV | 9076 | alarm_enum_mod | Internal use; do not map to BAS | Write | ||
| AV | 9077 | alarm_msv_mod | Internal use; do not map to BAS | Write | ||
| AV | 9078 | alarm_flags_mod | Internal use; do not map to BAS | Write | ||
| AV | 9079 | dip_sw_over | Internal use; do not map to BAS | Write | ||
| AV | 9080 | axb1_comm_stat_a | Internal use; do not map to BAS | Write | ||
| AV | 9081 | axb2_comm_stat_a | Internal use; do not map to BAS | Write | ||
| AV | 9082 | za1_comm_stat_a | Internal use; do not map to BAS | Write | ||
| AV | 9083 | za2_comm_stat_a | Internal use; do not map to BAS | Write | ||
| AV | 9084 | abc_comm_stat_a | Internal use; do not map to BAS | Write | ||
| AV | 9085 | eev_man_pos | Internal use; do not map to BAS | hr | Read | |
| AV | 9091 | sys_dem | Internal use; do not map to BAS | % | Write | |
| AV | 9092 | fan_dem | Internal use; do not map to BAS | % | Write | |
| AV | 9102 | z1_eff_size | Internal use; do not map to BAS | % | Write | |
| AV | 9103 | z2_eff_size | Internal use; do not map to BAS | % | Write | |
| AV | 9104 | z3_eff_size | Internal use; do not map to BAS | % | Write | |
| AV | 9105 | z4_eff_size | Internal use; do not map to BAS | % | Write | |
| AV | 9106 | z5_eff_size | Internal use; do not map to BAS | % | Write | |
| AV | 9107 | z6_eff_size | Internal use; do not map to BAS | % | Write | |
| AV | 9110 | overshoot | Internal use; do not map to BAS | °F | Write | |
| AV | 9111 | pfactor | Internal use; do not map to BAS | Write | ||
| AV | 9112 | ifactor | Internal use; do not map to BAS | Write | ||
| AV | 9113 | dfactor | Internal use; do not map to BAS | Write | ||
| BVmin | 101 | em_shutdown_c | Emergency shutdown command to the unit | Write | ||
| BV | 102 | es_stat | Emergency Shutdown status of System | Write | ||
| BV | 103 | es_stat_a | Emergency Shutdown status of ABC | Write | ||
| BV | 105 | load_shed_c | Load shed command to the unit | Write | ||
| BV | 106 | ls_stat_a | Load Shed status of ABC | Write | ||
| BV | 127 | manual_ecm_c | Internal use; do not map to BAS | Write | ||
| BV | 128 | man_vs_pump_c | Internal use; do not map to BAS | Write | ||
| BVmin | 130 | alarm_reset_c | Command the alarm reset | Write | ||
| BV | 131 | alarm_reset_stat | Commanded status of the alarm reset command | Read | ||
| BV | 132 | abc_comm_flt_a | Status of the Modbus communication between the ABC and the XPC | Read | ||
| BV | 133 | modbus_comm_a | Status of the Modbus communication between the ABC and the XPC | Read | ||
| BV | 138 | filter_alm_reset_c | Reset the dirty filter alarm after the filter has been changed | Write | ||
| BV | 139 | dirty_filter_alarm | Status of the dirty filter alarm | Read | ||
| BV | 140 | cond_stat_a | Status of the condensate input on ABC | Read | ||
| BVmin | 141 | alarm_hdw_stat_a | Status of the ABC Alarm output | Read | ||
| BV | 142 | lock_hdw_stat_a | Status of the ABC Lockout output | Read | ||
| BV | 143 | lockout_stat_a | Lockout status of the ABC | Read | ||
| BV | 200 | comp_stat_a | Status of the CC compressor output on ABC | Write | ||
| BV | 201 | hi_comp_stat_a | Status of the CC2 compressor output on ABC | Write | ||
| BV | 202 | rev_vlv_stat_a | Status of the reversing valve output on ABC | Write | ||
| BV | 203 | fan_stat_a | Status of the Fan relay output on ABC | Write | ||
| BV | 204 | eh1_stat_a | Status of the EH1 output on ABC | Write | ||
| BV | 205 | eh2_stat_a | Status of the EH2 output on ABC | Write | ||
| BV | 206 | acc1_stat_a | Status of the ACC1 output on ABC | Write | ||
| BV | 214 | fp1_lim_a | FP1 limit temperature for ABC | Write | ||
| BV | 215 | fp2_lim_a | FP2 limit temperature for ABC | Write | ||
| BV | 216 | rv_setup_a | Reversing valve setup for ABC | Write | ||
| BV | 217 | sw_2_4_a | Position of SW2-4 on ABC which configures the operation of ACC1 | Write | ||
| BV | 218 | sw_2_5_a | Position of SW2-5 on ABC which configures the operation of ACC1 | Write | ||
| BV | 219 | comp_cap_a | Position of SW2-6 on ABC | Write | ||
| BV | 220 | lockout_cfg_a | Position of SW2-7 on ABC | Write | ||
| BV | 221 | reheat_cfg_a | Position of SW2-8 on ABC | Write | ||
| BV | 222 | sw1_test_a | Status of the SW1 test button on ABC | Write | ||
| BV | 232 | y1_hdw_a | Status of the physical Y1 input on ABC | Write | ||
| BV | 233 | y2_hdw_a | Status of the physical Y2 input on ABC | Write | ||
| BV | 234 | w_hdw_a | Status of the physical W input on ABC | Write | ||
| BV | 235 | o_hdw_a | Status of the physical O input on ABC | Write | ||
| BV | 236 | g_hdw_a | Status of the physical G input on ABC | Write | ||
| BV | 237 | dh_hdw_a | Status of the physical DH input on ABC | Write | ||
| BV | 238 | hp_hdw_a | Status of the physical LP input on ABC | Write | ||
| BV | 239 | lp_hdw_a | Status of the physical HP input on ABC | Write | ||
| BV | 240 | ls_hdw_a | Status of the physical LS input on ABC | Write | ||
| BV | 241 | es_hdw_a | Status of the physical ES input on ABC | Write | ||
| BV | 242 | abc_test_mode_a | Current status of the test mode for ABC | Write | ||
| BV | 299 | fan_stat | Current status of system fan output | Read | ||
| BV | 301 | sys_comm | Status of valid system communications with ABC controls | Read | ||
| BV | 306 | brine_select_c | Selects the anti-freeze setting for the use of performance monitoring calculations only | Write | ||
| BV | 308 | dhw_enable_a_c | Enable/disable DHW operation | Write | ||
| BV | 310 | sw2_1_a_c | Select the position of SW2-1 on ABC for override | Write | ||
| BV | 311 | sw2_2_a_c | Select the position of SW2-2 on ABC for override | Write | ||
| BV | 312 | sw2_3_a_c | Select the position of SW2-3 on ABC for override | Write | ||
| BV | 313 | sw2_4_a_c | Select the position of SW2-4 on ABC for override | Write | ||
| BV | 314 | sw2_5_a_c | Select the position of SW2-5 on ABC for override | Write | ||
| BV | 315 | sw2_6_a_c | Select the position of SW2-6 on ABC for override | Write | ||
| BV | 316 | sw2_7_a_c | Select the position of SW2-7 on ABC for override | Write | ||
| BV | 317 | sw2-8_a_c | Select the position of SW2-8 on ABC for override | Write | ||
| BV | 318 | dip_sw_ovrd_ena_a_c | Enable the BAS write privileges for dip switch overrides on ABC | Write | ||
| BV | 398 | dip_sw_ovrd_rel | Disable the BAS write privileges for dip switch overrides on ABC | Write | ||
| BV | 400 | test_mode_ena_c | Internal use; do not map to BAS | Write | ||
| BV | 401 | fact_test_ena_c | Internal use; do not map to BAS | Write | ||
| BV | 402 | clear_faults_c | Internal use; do not map to BAS | Write | ||
| BV | 403 | dev_enable_c | Internal use; do not map to BAS | Write | ||
| BV | 406 | axb_enable_a_c | Internal use; do not map to BAS | Write | ||
| BV | 407 | axb_enable_b_c | Internal use; do not map to BAS | Write | ||
| BV | 502 | schedule_select_c | Select between the internal or external schedule | Write | ||
| BV | 507 | temp_occ_c | Enables or disables temporary occupancy at zone sensors | Write | ||
| BV | 550 | archive_now_c | Forces XPC to Archive the current system settings and database values | Write | ||
| BV | 603 | dcv_status | Indicates if demand controlled ventilation logic is active | Write | ||
| BV | 622 | dem_ctrl_vent_c | Enables or disables Demand Controlled Ventlation | Write | ||
| BV | 623 | dcv_variable_c | Selects the control variable for Demand Controlled Ventilation | Write | ||
| BV | 700 | man_sys_c | Internal use; do not map to BAS | Write | ||
| BV | 701 | man_comp_c | Internal use; do not map to BAS | Write | ||
| BV | 702 | man_heat_cool_c | Internal use; do not map to BAS | Write | ||
| BV | 703 | set_eev_c | Internal use; do not map to BAS | Write | ||
| BV | 704 | man_damp_c | Internal use; do not map to BAS | Write | ||
| BV | 705 | man_damp1_c | Internal use; do not map to BAS | Write | ||
| BV | 706 | man_damp2_c | Internal use; do not map to BAS | Write | ||
| BV | 707 | man_damp3_c | Internal use; do not map to BAS | Write | ||
| BV | 708 | man_damp4_c | Internal use; do not map to BAS | Write | ||
| BV | 709 | man_damp5_c | Internal use; do not map to BAS | Write | ||
| BV | 710 | man_damp6_c | Internal use; do not map to BAS | Write | ||
| BV | 711 | man_o_damp_c | Internal use; do not map to BAS | Write | ||
| BV | 712 | man_y1_c | Internal use; do not map to BAS | Write | ||
| BV | 713 | man_y2_c | Internal use; do not map to BAS | Write | ||
| BV | 714 | man_w_c | Internal use; do not map to BAS | Write | ||
| BV | 715 | man_eh1_c | Internal use; do not map to BAS | Write | ||
| BV | 716 | man_eh2_c | Internal use; do not map to BAS | Write | ||
| BV | 1000 | system_cfg_c | Use MSV or AV objects for options offered as both | Write | ||
| BV | 1001 | z1priority_c | Sets the zone 1 operating priority | Write | ||
| BV | 1002 | z2priority_c | Sets the zone 2 operating priority | Write | ||
| BV | 1003 | z3priority_c | Sets the zone 3 operating priority | Write | ||
| BV | 1004 | z4priority_c | Sets the zone 4 operating priority | Write | ||
| BV | 1005 | z5priority_c | Sets the zone 5 operating priority | Write | ||
| BV | 1006 | z6priority_c | Sets the zone 6 operating priority | Write | ||
| BV | 1007 | z1_fan_c | Sets the zone 1 fan operation | Write | ||
| BV | 1008 | z2_fan_c | Sets the zone 2 fan operation | Write | ||
| BV | 1009 | z3_fan_c | Sets the zone 3 fan operation | Write | ||
| BV | 1010 | z4_fan_c | Sets the zone 4 fan operation | Write | ||
| BV | 1011 | z5_fan_c | Sets the zone 5 fan operation | Write | ||
| BV | 1012 | z6_fan_c | Sets the zone 6 fan operation | Write | ||
| BV | 1013 | operation_c | Sets the central or single zone operation | Write | ||
| BV | 1014 | fan_stage_c | Sets the normal or expanded fan staging | Write | ||
| BV | 1015 | aux_lockout_c | Allows selectionof auxiliary Heat Lockout operation | Write | ||
| BV | 1016 | damp_type_c | Allows selection between powered and spring dampers | Write | ||
| BV | 1017 | oat_source | Sets the source for OAT sensor (BAS or zone panel) | Write | ||
| BV | 1018 | oat_display_c | Sets the displaying OAT on tablet display | Write | ||
| BV | 1020 | z1status | Current status of the zone 1 damper | Read | ||
| BV | 1021 | z2status | Current status of the zone 2 damper | Read | ||
| BV | 1022 | z3status | Current status of the zone 3 damper | Read | ||
| BV | 1023 | z4status | Current status of the zone 4 damper | Read | ||
| BV | 1024 | z5status | Current status of the zone 5 damper | Read | ||
| BV | 1025 | z6status | Current status of the zone 6 damper | Read | ||
| BV | 1026 | central_op | Status of central zone operation | Read | ||
| BV | 1027 | y1_demand | Status of Y1 call from zoning system to ABC | Write | ||
| BV | 1028 | y2_demand | Status of Y2 call from zoning system to ABC | Write | ||
| BV | 1029 | w_demand | Status of W call from zoning system to ABC | Write | ||
| BV | 1030 | o_demand | Status of O call from zoning system to ABC | Write | ||
| BV | 1031 | dh_demand | Status of DH call from zoning system to ABC | Write | ||
| BV | 1032 | h_demand | Status of H call from zoning system to ABC | Write | ||
| BV | 1033 | eh1_demand | Status of EH1 call from zoning system to ABC | Write | ||
| BV | 1034 | eh2_demand | Status of EH2 call from zoning system to ABC | Write | ||
| BV | 1035 | g_demand | Status of G call from zoning system to ABC | Write | ||
| BV | 1100 | temp_selector_z1_c | Select between wall sensor and BAS for zone 1 space temperature value | Write | ||
| BV | 1101 | valid_sensor_z1 | Current status of having a valid zone 1 space temperature value | Read | ||
| BV | 1103 | sensor_occ_z1 | Enables or disables occupancy sensor connected to ABC input | Read | ||
| BV | 1104 | eff_occ_bv_z1 | Current zone 1 occupancy status | Read | ||
| BVmin | 1106 | occ_man_cmd_bv_z1_c | BAS occupancy signal for zone 1 | Write | ||
| BV | 1200 | temp_selector_z2_c | Select between wall sensor and BAS for zone 2 space temperature value | Write | ||
| BV | 1201 | valid_sensor_z2 | Current status of having a valid zone 2 space temperature value | Read | ||
| BV | 1203 | sensor_occ_z2 | Enables or disables occupancy sensor connected to ABC input | Read | ||
| BV | 1204 | eff_occ_bv_z2 | Current zone 2 occupancy status | Read | ||
| BV | 1206 | occ_man_cmd_bv_z2_c | BAS occupancy signal for zone 2 | Write | ||
| BV | 1300 | temp_selector_z3_c | Select between wall sensor and BAS for zone 3 space temperature value | Write | ||
| BV | 1301 | valid_sensor_z3 | Current status of having a valid zone 3 space temperature value | Read | ||
| BV | 1303 | sensor_occ_z3 | Enables or disables occupancy sensor connected to ABC input | Read | ||
| BV | 1304 | eff_occ_bv_z3 | Current zone 3 occupancy status | Read | ||
| BV | 1306 | occ_man_cmd_bv_z3_c | BAS occupancy signal for zone 3 | Write | ||
| BV | 1400 | temp_selector_z4_c | Select between wall sensor and BAS for zone 4 space temperature value | Write | ||
| BV | 1401 | valid_sensor_z4 | Current status of having a valid zone 4 space temperature value | Read | ||
| BV | 1403 | sensor_occ_z4 | Enables or disables occupancy sensor connected to ABC input | Read | ||
| BV | 1404 | eff_occ_bv_z4 | Current zone 4 occupancy status | Read | ||
| BV | 1406 | occ_man_cmd_bv_z4_c | BAS occupancy signal for zone 4 | Write | ||
| BV | 1500 | temp_selector_z5_c | Select between wall sensor and BAS for zone 5 space temperature value | Write | ||
| BV | 1501 | valid_sensor_z5 | Current status of having a valid zone 5 space temperature value | Read | ||
| BV | 1503 | sensor_occ_z5 | Enables or disables occupancy sensor connected to ABC input | Read | ||
| BV | 1504 | eff_occ_bv_z5 | Current zone 5 occupancy status | Read | ||
| BV | 1506 | occ_man_cmd_bv_z5_c | BAS occupancy signal for zone 5 | Write | ||
| BV | 1600 | temp_selector_z6_c | Select between wall sensor and BAS for zone 6 space temperature value | Write | ||
| BV | 1601 | valid_sensor_z6 | Current status of having a valid zone 6 space temperature value | Read | ||
| BV | 1603 | sensor_occ_z6 | Enables or disables occupancy sensor connected to ABC input | Read | ||
| BV | 1604 | eff_occ_bv_z6 | Current zone 6 occupancy status | Read | ||
| BV | 1606 | occ_man_cmd_bv_z6_c | BAS occupancy signal for zone 6 | Write | ||
| MVmin | 100 | mode_msv | Operating mode of the unit | Read | ||
| MV | 300 | clg_cfm_offset_msv_c | Selecting dehumdiification operation for ECM blower (default 4) | Write | ||
| MV | 301 | phase_select_c | Select the supply power phase (default 1) | Write | ||
| MV | 302 | flow_meter_a_msv_c | Selecting flow meter option (default 6) | Write | ||
| MV | 305 | hum_enable_msv_c | Configuration of humidity control option (default 1) | Write | ||
| MV | 306 | pid_select_c | Internal use; do not map to BAS | Write | ||
| MV | 502 | lockout_enum_msv | Internal use; do not map to BAS | Read | ||
| MV | 1000 | heatpump_c | Internal use; do not map to BAS | Write | ||
| MV | 1001 | z1size_msv_c | Configures zone 1 size (default 1) | Write | ||
| MV | 1002 | z2size_msv_c | Configures zone 2 size (default 1) | Write | ||
| MV | 1003 | z3size_msv_c | Configures zone 3 size (default 1) | Write | ||
| MV | 1004 | z4size_msv_c | Configures zone 4 size (default 1) | Write | ||
| MV | 1005 | z5size_msv_c | Configures zone 5 size (default 1) | Write | ||
| MV | 1006 | z6size_msv_c | Configures zone 6 size (default 1) | Write | ||
| MV | 1007 | z1mode_msv_c | Configures zone 1 operating mode (default 1) | Write | ||
| MV | 1008 | z2mode_msv_c | Configures zone 2 operating mode (default 1) | Write | ||
| MV | 1009 | z3mode_msv_c | Configures zone 3 operating mode (default 1) | Write | ||
| MV | 1010 | z4mode_msv_c | Configures zone 4 operating mode (default 1) | Write | ||
| MV | 1011 | z5mode_msv_c | Configures zone 5 operating mode (default 1) | Write | ||
| MV | 1012 | z6mode_msv_c | Configures zone 6 operating mode (default 1) | Write | ||
| MV | 1013 | clg_stage_msv_c | Configures system staging for cooling (default 1) | Write | ||
| MV | 1014 | htg_stage_msv_c | Configures system staging for heating (default 1) | Write | ||
| MV | 1100 | occ_man_cmd_msv_z1_c | Selecting the zone 1 occupancy status (default 1) | Write | ||
| MV | 1101 | eff_occ_msv_z1 | Current zone 1 occupancy status | Read | ||
| MV | 1103 | occ_sensor_msv_z1_c | Selecting zone 1occupancy sensor operation behavior (default 1) | Write | ||
| MV | 1200 | occ_man_cmd_msv_z2_c | Selecting the zone 2 occupancy status (default 1) | Write | ||
| MV | 1201 | eff_occ_msv_z2 | Current zone 2 occupancy status | Read | ||
| MV | 1203 | occ_sensor_msv_z2_c | Selecting zone 2 occupancy sensor operation behavior (default 1) | Write | ||
| MV | 1300 | occ_man_cmd_msv_z3_c | Selecting the zone 3 occupancy status (default 1) | Write | ||
| MV | 1301 | eff_occ_msv_z3 | Current zone 3 occupancy status | Read | ||
| MV | 1303 | occ_sensor_msv_z3_c | Selecting zone 3 occupancy sensor operation behavior (default 1) | Write | ||
| MV | 1400 | occ_man_cmd_msv_z4_c | Selecting the zone 4 occupancy status (default 1) | Write | ||
| MV | 1401 | eff_occ_msv_z4 | Current zone 4 occupancy status | Read | ||
| MV | 1403 | occ_sensor_msv_z4_c | Selecting zone 4 occupancy sensor operation behavior (default 1) | Write | ||
| MV | 1500 | occ_man_cmd_msv_z5_c | Selecting the zone 5 occupancy status (default 1) | Write | ||
| MV | 1501 | eff_occ_msv_z5 | Current zone 5 occupancy status | Read | ||
| MV | 1503 | occ_sensor_msv_z5_c | Selecting zone 5 occupancy sensor operation behavior (default 1) | Write | ||
| MV | 1600 | occ_man_cmd_msv_z6_c | Selecting the zone 6 occupancy status (default 1) | Write | ||
| MV | 1601 | eff_occ_msv_z6 | Current zone 6 occupancy status | Read | ||
| MV | 1603 | occ_sensor_msv_z6_c | Selecting zone 6 occupancy sensor operation behavior (default 1) | Write |
No points match these filters.
Object ID lookup: WaterFurnace IntelliZone2 IZ2 point IDs by name
AV102mode_avAV103man_ecm_speed_cAV105man_vs_pump_a_cAV109fp1_setpt_aAV110fp2_setpt_aAV113filter_alm_hrs_cAV114filter_hoursAV115lock_stat_reg_aAV116alarm_enum_aAV119alarm_enumAV200ecm_speed_sw_aAV201ecm_pwm_pct_aAV202vs_pump_spd_stat_aAV203vs_pump_pct_stat_aAV206coax_temp_stat_aAV207air_coil_temp_stat_aAV210lwt_stat_aAV211ewt_stat_aAV212water_flow_stat_aAV213loop_pres_stat_aAV214lat_statAV216suct_press_stat_aAV217disch_press_stat_aAV218suct_temp_stat_aAV219disch_temp_stat_aAV220liq_line_temp_stat_aAV221sat_evap_temp_stat_aAV222cond_temp_stat_aAV223est_line_voltage_stat_aAV224control_voltage_stat_aAV225hot_wtr_temp_stat_aAV226univ_input_stat_aAV227superheat_stat_aAV228htg_subcool_stat_aAV229clg_subcool_stat_aAV230fan_current_stat_aAV231aux_current_stat_aAV232comp_current_stat_aAV233comp1_current_stat_aAV234total_amps_stat_aAV235comp_power_stat_aAV236fan_power_stat_aAV237aux_power_stat_aAV238total_power_stat_aAV239he_hr_stat_aAV240total_cap_stat_aAV241cop_stat_aAV242eer_stat_aAV296targ_blower_spdAV297mod_valve_pwmAV298eev1_posAV299eev2_posAV301low_ecm_spd_cAV302med_ecm_spd_cAV303high_ecm_spd_cAV304aux_ht_ecm_spd_cAV305blwr_off_delay_cAV306clg_cfm_offset_av_cAV307occ_dehum_setpt_cAV308unocc_dehum_setpt_cAV309dehum_setptAV311vs_pump_min_spd_a_cAV312vs_pump_max_spd_a_cAV313pump_opt_a_cAV317flow_meter_a_cAV319dhw_setpt_a_cAV321energy_mon_a_cAV323acc1_delay_a_cAV325measured_line_volts_cAV326blower_config_cAV330hum_enable_av_cAV331occ_hum_setpt_cAV332unocc_hum_setpt_cAV400fact_test_cAV401m401_cmdAV402m402_cmdAV403m403_cmdAV404m404_cmdAV405m405_cmdAV406m406_cmdAV407m407_cmdAV408m408_cmdAV409m409_cmdAV410m410_cmdAV411m411_cmdAV412m412_cmdAV413m413_cmdAV414m414_cmdAV415m415_cmdAV416m416_cmdAV417m417_cmdAV418m418_cmdAV420tstat_ovrd_cAV430abc_fw_rev_aAV431abc_sw_part_no_aAV432abc_fw_beta_aAV503zone_humAV504humidity_cAV505co2_statAV506co2_cmd_cAV507voc_statAV508voc_cmd_cAV601o_damp_targAV606oat_override_cAV607oat_statAV638min_dcv_pos_cAV642max_dcv_pos_cAV643low_dcv_val_cAV644high_dcv_val_cAV700comp_configAV701comp_config_avAV702eev_start_cAV703targ_comp_spdAV704actual_comp_spdAV705amb_tempAV706supply_voltsAV707line_voltsAV708vdc_voltsAV709invert_tempAV710drive_tempAV711drive_fan_pctAV712thermo_power_pctAV720man_comp_spd_cAV721man_eev_pos_cAV722man_odamp_pos_cAV1000num_zones_cAV1001z1size_av_cAV1002z2size_av_cAV1003z3size_av_cAV1004z4size_av_cAV1005z5size_av_cAV1006z6size_av_cAV1007z1mode_av_cAV1008z2mode_av_cAV1009z3mode_av_cAV1010z4mode_av_cAV1011z5mode_av_cAV1012z6mode_av_cAV1013clg_stage_av_cAV1014htg_stage_av_cAV1015ah_lock_setpt_cAV1016occ_sens_on_time_cAV1017occ_sens_off_time_cAV1020azc_fw_revAV1021azc_faultAV1022damp_time__cAV1036z1maxAV1037z2maxAV1038z3maxAV1039z4maxAV1040z5maxAV1041z6maxAV1042z1minAV1043z2minAV1044z3minAV1045z4minAV1046z5minAV1047z6minAV1100zone_temp_z1AV1101zone_temp_adj_z1_cAV1102zone_temp_ovrd_z1_cAV1103zone_hum_z1AV1105co2_stat_z1AV1107voc_stat_z1AV1109occ_man_av_z1_cAV1110eff_occ_st_z1AV1111occ_clg_setpt_z1_cAV1112occ_htg_setpt_z1_cAV1113unocc_clg_setpt_z1_cAV1114unocc_htg_setpt_z1_cAV1115standby_cool_setpt_z1_cAV1116standby_heat_setpt_z1_cAV1117eff_clg_setpt_z1AV1118eff_htg_setpt_z1AV1120occ_sensor_av_z1_cAV1121setpt_diff_z1_cAV1122setpt_span_z1_cAV1123temp_occ_time_z1AV1125zone_sensor_temp_z1AV1150z1_demandAV1200zone_temp_z2AV1201zone_temp_adj_z2_cAV1202zone_temp_ovrd_z2_cAV1203zone_hum_z2AV1205co2_stat_z2AV1207voc_stat_z2AV1209occ_man_av_z2_cAV1210eff_occ_st_z2AV1211occ_clg_setpt_z2_cAV1212occ_htg_setpt_z2_cAV1213unocc_clg_setpt_z2_cAV1214unocc_htg_setpt_z2_cAV1215standby_cool_setpt_z2_cAV1216standby_heat_setpt_z2_cAV1217eff_clg_setpt_z2AV1218eff_htg_setpt_z2AV1220occ_sensor_av_z2_cAV1221setpt_diff_z2_cAV1222setpt_span_z2_cAV1223temp_occ_time_z2AV1225zone_sensor_temp_z2AV1250z2_demandAV1300zone_temp_z3AV1301zone_temp_adj_z3_cAV1302zone_temp_ovrd_z3_cAV1303zone_hum_z3AV1305co2_stat_z3AV1307voc_stat_z3AV1309occ_man_av_z3_cAV1310eff_occ_st_z3AV1311occ_clg_setpt_z3_cAV1312occ_htg_setpt_z3_cAV1313unocc_clg_setpt_z3_cAV1314unocc_htg_setpt_z3_cAV1315standby_cool_setpt_z3_cAV1316standby_heat_setpt_z3_cAV1317eff_clg_setpt_z3AV1318eff_htg_setpt_z3AV1320occ_sensor_av_z3_cAV1321setpt_diff_z3_cAV1322setpt_span_z3_cAV1323temp_occ_time_z3AV1325zone_sensor_temp_z3AV1350z3_demandAV1400zone_temp_z4AV1401zone_temp_adj_z4_cAV1402zone_temp_ovrd_z4_cAV1403zone_hum_z4AV1405co2_stat_z4AV1407voc_stat_z4AV1409occ_man_av_z4_cAV1410eff_occ_st_z4AV1411occ_clg_setpt_z4_cAV1412occ_htg_setpt_z4_cAV1413unocc_clg_setpt_z4_cAV1414unocc_htg_setpt_z4_cAV1415standby_cool_setpt_z4_cAV1416standby_heat_setpt_z4_cAV1417eff_clg_setpt_z4AV1418eff_htg_setpt_z4AV1420occ_sensor_av_z4_cAV1421setpt_diff_z4_cAV1422setpt_span_z4_cAV1423temp_occ_time_z4AV1425zone_sensor_temp_z4AV1450z4_demandAV1500zone_temp_z5AV1501zone_temp_adj_z5_cAV1502zone_temp_ovrd_z5_cAV1503zone_hum_z5AV1505co2_stat_z5AV1507voc_stat_z5AV1509occ_man_av_z5_cAV1510eff_occ_st_z5AV1511occ_clg_setpt_z5_cAV1512occ_htg_setpt_z5_cAV1513unocc_clg_setpt_z5_cAV1514unocc_htg_setpt_z5_cAV1515standby_cool_setpt_z5_cAV1516standby_heat_setpt_z5_cAV1517eff_clg_setpt_z5AV1518eff_htg_setpt_z5AV1520occ_sensor_av_z5_cAV1521setpt_diff_z5_cAV1522setpt_span_z5_cAV1523temp_occ_time_z5AV1525zone_sensor_temp_z5AV1550z5_demandAV1600zone_temp_z6AV1601zone_temp_adj_z6_cAV1602zone_temp_ovrd_z6_cAV1603zone_hum_z6AV1605co2_stat_z6AV1607voc_stat_z6AV1609occ_man_av_z6_cAV1610eff_occ_st_z6AV1611occ_clg_setpt_z6_cAV1612occ_htg_setpt_z6_cAV1613unocc_clg_setpt_z6_cAV1614unocc_htg_setpt_z6_cAV1615standby_cool_setpt_z6_cAV1616standby_heat_setpt_z6_cAV1617eff_clg_setpt_z6AV1618eff_htg_setpt_z6AV1620occ_sensor_av_z6_cAV1621setpt_diff_z6_cAV1622setpt_span_z6_cAV1623temp_occ_time_z6AV1625zone_sensor_temp_z6AV1650z6_demandAV9000active_z1_setptAV9001active_z2_setptAV9002active_z3_setptAV9003active_z4_setptAV9004active_z5_setptAV9005active_z6_setptAV9006sensor_alarmsAV9007comp_config_mAV9013supply_voltsl_mAV9014supply_voltsh_mAV9040abc_9013AV9041abc_9014AV9043abc_0036AV9044abc_9016AV9045abc_0002AV9047rand_start_delay_aAV9048anti_short_cycle_aAV9049low_spd_min_run_time_aAV9050blow_off_dly_time_aAV9051comp_strt_delay_aAV9052slow_open_wtr_vlv_aAV9053test_mode_timer_aAV9054comp_run_time_l_aAV9055comp_run_time_h_maAV9056comp_power_low_aAV9057comp_power_high_aAV9058fan_power_low_aAV9059fan_power_high_aAV9060aux_power_low_aAV9061aux_power_high_aAV9062total_power_low_aAV9063total_power_high_aAV9064heat_ext_low_aAV9065heat_ext_high_aAV9066heat_rej_low_aAV9067heat_rej_high_aAV9068heat_cap_low_aAV9069heat_cap_high_aAV9070cool_cap_low_aAV9071cool_cap_high_aAV9074zc_statAV9075lo_stat_aAV9076alarm_enum_modAV9077alarm_msv_modAV9078alarm_flags_modAV9079dip_sw_overAV9080axb1_comm_stat_aAV9081axb2_comm_stat_aAV9082za1_comm_stat_aAV9083za2_comm_stat_aAV9084abc_comm_stat_aAV9085eev_man_posAV9091sys_demAV9092fan_demAV9102z1_eff_sizeAV9103z2_eff_sizeAV9104z3_eff_sizeAV9105z4_eff_sizeAV9106z5_eff_sizeAV9107z6_eff_sizeAV9110overshootAV9111pfactorAV9112ifactorAV9113dfactorBV101em_shutdown_cBV102es_statBV103es_stat_aBV105load_shed_cBV106ls_stat_aBV127manual_ecm_cBV128man_vs_pump_cBV130alarm_reset_cBV131alarm_reset_statBV132abc_comm_flt_aBV133modbus_comm_aBV138filter_alm_reset_cBV139dirty_filter_alarmBV140cond_stat_aBV141alarm_hdw_stat_aBV142lock_hdw_stat_aBV143lockout_stat_aBV200comp_stat_aBV201hi_comp_stat_aBV202rev_vlv_stat_aBV203fan_stat_aBV204eh1_stat_aBV205eh2_stat_aBV206acc1_stat_aBV214fp1_lim_aBV215fp2_lim_aBV216rv_setup_aBV217sw_2_4_aBV218sw_2_5_aBV219comp_cap_aBV220lockout_cfg_aBV221reheat_cfg_aBV222sw1_test_aBV232y1_hdw_aBV233y2_hdw_aBV234w_hdw_aBV235o_hdw_aBV236g_hdw_aBV237dh_hdw_aBV238hp_hdw_aBV239lp_hdw_aBV240ls_hdw_aBV241es_hdw_aBV242abc_test_mode_aBV299fan_statBV301sys_commBV306brine_select_cBV308dhw_enable_a_cBV310sw2_1_a_cBV311sw2_2_a_cBV312sw2_3_a_cBV313sw2_4_a_cBV314sw2_5_a_cBV315sw2_6_a_cBV316sw2_7_a_cBV317sw2-8_a_cBV318dip_sw_ovrd_ena_a_cBV398dip_sw_ovrd_relBV400test_mode_ena_cBV401fact_test_ena_cBV402clear_faults_cBV403dev_enable_cBV406axb_enable_a_cBV407axb_enable_b_cBV502schedule_select_cBV507temp_occ_cBV550archive_now_cBV603dcv_statusBV622dem_ctrl_vent_cBV623dcv_variable_cBV700man_sys_cBV701man_comp_cBV702man_heat_cool_cBV703set_eev_cBV704man_damp_cBV705man_damp1_cBV706man_damp2_cBV707man_damp3_cBV708man_damp4_cBV709man_damp5_cBV710man_damp6_cBV711man_o_damp_cBV712man_y1_cBV713man_y2_cBV714man_w_cBV715man_eh1_cBV716man_eh2_cBV1000system_cfg_cBV1001z1priority_cBV1002z2priority_cBV1003z3priority_cBV1004z4priority_cBV1005z5priority_cBV1006z6priority_cBV1007z1_fan_cBV1008z2_fan_cBV1009z3_fan_cBV1010z4_fan_cBV1011z5_fan_cBV1012z6_fan_cBV1013operation_cBV1014fan_stage_cBV1015aux_lockout_cBV1016damp_type_cBV1017oat_sourceBV1018oat_display_cBV1020z1statusBV1021z2statusBV1022z3statusBV1023z4statusBV1024z5statusBV1025z6statusBV1026central_opBV1027y1_demandBV1028y2_demandBV1029w_demandBV1030o_demandBV1031dh_demandBV1032h_demandBV1033eh1_demandBV1034eh2_demandBV1035g_demandBV1100temp_selector_z1_cBV1101valid_sensor_z1BV1103sensor_occ_z1BV1104eff_occ_bv_z1BV1106occ_man_cmd_bv_z1_cBV1200temp_selector_z2_cBV1201valid_sensor_z2BV1203sensor_occ_z2BV1204eff_occ_bv_z2BV1206occ_man_cmd_bv_z2_cBV1300temp_selector_z3_cBV1301valid_sensor_z3BV1303sensor_occ_z3BV1304eff_occ_bv_z3BV1306occ_man_cmd_bv_z3_cBV1400temp_selector_z4_cBV1401valid_sensor_z4BV1403sensor_occ_z4BV1404eff_occ_bv_z4BV1406occ_man_cmd_bv_z4_cBV1500temp_selector_z5_cBV1501valid_sensor_z5BV1503sensor_occ_z5BV1504eff_occ_bv_z5BV1506occ_man_cmd_bv_z5_cBV1600temp_selector_z6_cBV1601valid_sensor_z6BV1603sensor_occ_z6BV1604eff_occ_bv_z6BV1606occ_man_cmd_bv_z6_cMV100mode_msvMV300clg_cfm_offset_msv_cMV301phase_select_cMV302flow_meter_a_msv_cMV305hum_enable_msv_cMV306pid_select_cMV502lockout_enum_msvMV1000heatpump_cMV1001z1size_msv_cMV1002z2size_msv_cMV1003z3size_msv_cMV1004z4size_msv_cMV1005z5size_msv_cMV1006z6size_msv_cMV1007z1mode_msv_cMV1008z2mode_msv_cMV1009z3mode_msv_cMV1010z4mode_msv_cMV1011z5mode_msv_cMV1012z6mode_msv_cMV1013clg_stage_msv_cMV1014htg_stage_msv_cMV1100occ_man_cmd_msv_z1_cMV1101eff_occ_msv_z1MV1103occ_sensor_msv_z1_cMV1200occ_man_cmd_msv_z2_cMV1201eff_occ_msv_z2MV1203occ_sensor_msv_z2_cMV1300occ_man_cmd_msv_z3_cMV1301eff_occ_msv_z3MV1303occ_sensor_msv_z3_cMV1400occ_man_cmd_msv_z4_cMV1401eff_occ_msv_z4MV1403occ_sensor_msv_z4_cMV1500occ_man_cmd_msv_z5_cMV1501eff_occ_msv_z5MV1503occ_sensor_msv_z5_cMV1600occ_man_cmd_msv_z6_cMV1601eff_occ_msv_z6MV1603occ_sensor_msv_z6_c
Integration notes
- Object names are the sheet's reference names (e.g. zone_temp_z1); the sheet also prints shorter display names (ZoneTempZ1).
- Sheet tab is dated 6-16-21. Zone blocks repeat at 1100-1199 (zone 1) through 1600-1699 (zone 6); all six are printed and listed.
- 133 rows are marked 'do not map to BAS' in the source; they are listed for completeness as internal-use points.
- Several options exist as both an AV and an MSV (zone size, zone mode, staging, occupancy); BV 1000 picks which set is used.
- Multistate state texts are not printed in this sheet, and the mode table it refers to is not included.
- The sheet does not state the BACnet transport or network settings.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IntelliZone2 (IZ2) Zoning System, Aurora BACnet and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet
How many BACnet points does the WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet have?
This list has 546 BACnet objects: 354 analog values, 152 binary values, 40 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet BACnet points are writable?
403 of the 546 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet BACnet documentation?
The source is IZ2 BACnet Point List, revision 2021-06-16, published free by WaterFurnace at https://www.waterfurnace.com/literature/intellizone/IZ2%20BACnet%20Point%20List.xlsx.
What are the minimum BACnet points to integrate the WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet?
Start with BV 101 em_shutdown_c (Emergency shutdown command); BV 1106 occ_man_cmd_bv_z1_c (Zone 1 occupancy from the BAS); AV 1111 occ_clg_setpt_z1_c (Zone 1 occupied cooling setpoint); AV 1112 occ_htg_setpt_z1_c (Zone 1 occupied heating setpoint); BV 130 alarm_reset_c (Alarm reset); MV 100 mode_msv (Unit operating mode); AV 1110 eff_occ_st_z1 (Zone 1 effective occupancy status); AV 1100 zone_temp_z1 (Zone 1 temperature in use); BV 141 alarm_hdw_stat_a (ABC alarm output status); AV 119 alarm_enum (Combined system alarm code).
How do I enable BMS control of the WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet?
BV 101 em_shutdown_c shuts the unit down and BV 105 load_shed_c sheds load from the network. Occupancy can come from the BAS per zone (BV 11x6, MV 11x0 or AV 11x9, depending on BV 1000) or from the internal schedule; BV 502 picks internal or external schedule.
Can the BMS supply sensor values to the WaterFurnace IntelliZone2 (IZ2) Zoning System, Aurora BACnet?
For a BAS zone temperature, set BV 11x0 (temp_selector) to BAS and write AV 11x2 (zone_temp_ovrd). AV 504, AV 506 and AV 508 accept BAS space humidity, CO2 and VOC values, and AV 606 a BAS outdoor air temperature (BV 1017 picks the OAT source).
How do I check these points on the real IntelliZone2 (IZ2) Zoning System, Aurora BACnet?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More WaterFurnace BACnet points lists
- Water-to-water heat pump controller
WaterFurnace Aurora HydroLink for NXW/SKW Water-to-Water Heat Pumps
WaterFurnace NXW and SKW dual-scroll water-to-water heat pumps (including header rack arrangements) with the Aurora HydroLink controller.
Also known as: PL2500EW, HydroLink, NXW, SKW, WCHDM, HYDWWB01 - Modular chiller / water-to-water heat pump controller
WaterFurnace Aurora HydroLink2 for TruClimate 100 / TruClimate 500 Modular Chillers
WaterFurnace TruClimate 100 dual scroll (NXW) and TruClimate 500 modular chillers with the Aurora HydroLink2 controller, including 4-pipe and 6-pipe header rack builds and variable speed modules.
Also known as: HydroLink2, HydroLink 2, TruClimate 100, TruClimate 500, NXW, HydroLink2 BACnet Objects 3.04 - Water-cooled screw chiller / heat pump controller
WaterFurnace Aurora HydroLink2 for TruClimate 700 Single Screw Chiller
WaterFurnace TruClimate 700 single screw water-to-water chillers with the Aurora HydroLink2 controller.
Also known as: HydroLink2 Single Screw, TruClimate 700, HydroLink2 - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Dual Compressor Rooftop Unit with Economizer
WaterFurnace dual-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Dual Compressor Water-Source Heat Pump
WaterFurnace dual-compressor water-to-air heat pumps with two Aurora Base Controllers (ABC A and B) and the Aurora UPC.
Also known as: PL1500EW, Aurora Universal Protocol Converter, Aurora UPC dual compressor - Rooftop unit controller (water-source, with economizer)
WaterFurnace Aurora UPC, Single Compressor Rooftop Unit with Economizer
WaterFurnace single-compressor water-source rooftop units with an economizer, Aurora controls and the Aurora UPC.
Also known as: PL1250EW, Aurora UPC rooftop economizer, Aurora Universal Protocol Converter - Water-source heat pump controller
WaterFurnace Aurora UPC, Single Compressor Water-Source Heat Pump
WaterFurnace single-compressor water-to-air heat pumps with the Aurora controls and the Aurora UPC protocol converter.
Also known as: AG1569EW, Aurora Universal Protocol Converter, Aurora UPC, UPCSWASTD01-01 - Water-source heat pump controller
WaterFurnace Aurora UPC, Variable Speed Water-Source Heat Pump
WaterFurnace variable speed water-to-air heat pumps with Aurora controls and the Aurora UPC.
Also known as: PL1700EW, Aurora Universal Protocol Converter, Aurora UPC variable speed - Water-source heat pump controller
WaterFurnace Dual Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace commercial dual-compressor water-to-air heat pumps fitted with the FX10 DDC controller.
Also known as: PRODCWA-05, PRODCWA, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Dual Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace dual-compressor water-to-air heat pumps with hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PRODCWA-RH-03, PRODCWA-RH, WaterFurnace dual compressor reheat FX10, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Envision Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Envision single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWWE-01, PROSSWWE, Envision Water-to-Water, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Envision Water-to-Air Heat Pump, 1-6 Ton
WaterFurnace Envision 1 to 6 ton water-to-air heat pumps with the DDC controller option.
Also known as: Envision BACnet Variables, Envision BACnet Variables with BI, Envision 1-6 Ton - Water-to-water heat pump / reversible chiller controller
WaterFurnace Reversible Chiller Water-to-Water Heat Pump (FX10)
WaterFurnace dual-compressor reversible chiller (water-to-water) heat pumps with the FX10 controller.
Also known as: PRODCWWE-06B, PRODCWWE-07B, PRODCWWE-08B, PRODCWWE - Water-source heat pump controller (console)
WaterFurnace Single Compressor Water-to-Air Console Unit (FX10)
WaterFurnace single-compressor water-to-air console heat pumps fitted with the FX10 DDC controller.
Also known as: PROSSWAC-02, PROSSWAC, WaterFurnace console heat pump FX10, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump (FX10)
WaterFurnace single-compressor water-to-air heat pumps without hot gas reheat, fitted with the FX10 DDC controller.
Also known as: PROFXENV-00, PROFXENV, Envision FX10, WaterFurnace FX10 - Water-source heat pump controller
WaterFurnace Single Compressor Water-to-Air Heat Pump with Hot Gas Reheat (FX10)
WaterFurnace single-compressor water-to-air heat pumps with hot gas reheat and the FX10 DDC controller.
Also known as: PROFXENV-RH-00, PROFXENV-RH, Envision hot gas reheat, WaterFurnace FX10 - Water-source DOAS controller with energy recovery
WaterFurnace Versatec 700 Indoor DOAS (Aurora UPC)
WaterFurnace Versatec 700 indoor dedicated outdoor air systems: up to four variable speed water-source heat pump modules with an energy recovery wheel, economizers and DCV, on the Aurora UPC.
Also known as: Versatec 700, Versatec DOAS, WaterFurnace DOAS, DOAS BACnet Point List 1.00 - Water-to-water heat pump controller
WaterFurnace Versatec Dual Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec dual-compressor water-to-water heat pumps with the FX10 DDC controller and expansion board.
Also known as: PRODCWW-02, PRODCWW, Versatec Dual Compressor, WaterFurnace FX10 - Water-to-water heat pump controller
WaterFurnace Versatec Single Compressor Water-to-Water Heat Pump (FX10)
WaterFurnace Versatec single-compressor water-to-water heat pumps with the FX10 DDC controller.
Also known as: PROSSWW-03, PROSSWW, Versatec Water-to-Water, WaterFurnace FX10
Source: IZ2 BACnet Point List · rev. 2021-06-16. Object names, instances and units are reproduced as published; descriptions are our own.